FaceDepot-7BL
User Manual
P a g e
| 67
Copyright©2020 ZKTECO CO., LTD. All rights reserved.
Access Control Options
9.1
To set the parameters of the access control, click
Access Control Options
on the Access Control interface.
Feature
Description
Gate control
mode
★
This feature decides whether to turn on the gate control mode or not. When set to
ON, this interface will remove the Door lock relay, Door sensor relay, and Door
sensor type function.
Door Lock Delay
(s)
The length of time that the device controls the electric lock to be unlocked. The
valid time range is 1 to 10 seconds; 0 second represents that the function is
disabled.
Door Sensor
Delay (s)
If the door is not closed and locked after opening for a certain duration (Door Sensor
Delay), an alarm will be triggered. The valid range of Door Sensor Delay is 1 to 255
seconds.
Door Sensor Type
There are three types: None, Normal Open, and Normal Close. None means the door
sensor is not in use; Normal Open means the door is always opened when electricity is
on; Normal Close means the door is always closed when electricity is on.
Door Alarm Delay
(s)
When the state of the door sensor is inconsistent with that of the door sensor type, an
alarm will be triggered after a specific time period, i.e. the Door Alarm Delay. The valid
value ranges from 1 to 999 seconds. 0 indicates an immediate alarm.