4. Select T_Grad, and then enter the temperature gradient (in ºC).
Possible values 1 to 20 (the default value is 5).
5. Select Aly_Dly, and then enter the configurable delay (in minutes).
Possible values 1 to 10 (the default value is 10).
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Sounder configuration
Assigning group addresses
Select the loop device configuration menu to assign a group address to control
the simultaneous activation of compatible addressable sounders. By default the
group address value is 0 (the simultaneous activation option is disabled).
Note:
At least five compatible sounders are required in a loop to apply
simultaneous activation. For loops with less than five sounders, devices are
activated individually.
To change the configuration:
1. Select Field setup from the Main menu, and then select Loop device config.
2. Select the corresponding loop and device.
The loop device configuration menu displays.
3. Select act_grp, and then assign the required group address.
For device types SDxG, SDx, and SCCx, the group address can be any
number from 112 to 126 that is not already assigned as a device address.
For device types DdG, SDd, SDBd, SDVBd, and SDVd, the group address
can be any number from 1 to 15.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Automatically silencing sounders (noise pollution)
Select the loop device configuration menu to automatically silence compatible
sounders 20 minutes after activation. By default this option is disabled (sounders
continue to sound).
To change the configuration:
1. Select Field setup from the Main menu, and then select Loop device config.
2. Select the corresponding loop and device.
The loop device configuration menu displays.