ZP2-A Series Operation Manual
23
Cancelling an active fire routing or fire protection delay
If a fire routing or fire protection delay is enabled and active (counting down),
press the corresponding ON/Acknowledged or Delay button to cancel the delay
and activate the feature immediately.
Fire routing and fire protection delay indications are shown in the table below.
Table 11: Fire routing and fire protection delay indications
Delay type
Delay indications
Fire routing
A steady Fire Routing Delay LED indicates that a delay is enabled.
A flashing Fire Routing Delay LED during a fire alarm indicates that the
configured delay is active (fire routing is activated when the configured delay
elapses or when the delay is cancelled).
The countdown for an active (counting) fire routing delay or extended fire
routing delay is also displayed on the product LCD (see Figure 3 on page
11):
• When a fire routing delay is counting (and has not been extended), the
LCD displays FR in T1: xxx sec.
• When an extended fire routing delay is counting (investigation time), the
LCD displays FR in T2: xxx sec.
Fire protection
A steady Fire Protection Delay LED indicates that a delay is enabled.
A flashing Fire Protection Delay LED during a fire alarm indicates that the
configured delay is active (fire protection is activated when the configured
delay elapses or when the delay is cancelled).
Note:
A fire alarm activated by a manual call point overrides any configured
delay and activates fire routing or fire protection immediately (if configured).
Manually starting evacuation sounders
See “Manually starting evacuation sounders” on page 27.
Note:
Evacuation panels only. Availability of this feature at this user level is
subject to previous configuration by your installation or maintenance contractor.