1.  The Zip Aquapoint III must be installed vertically. The connections should be at the rear 

of the unit. When facing the heater the hot supply (red) is to the left and the cold supply 
(blue) is to the right.

2.  The heater may be mounted above or below the intended outlets providing the 

water connections for the undersink models are at the top and for the oversink 
models underneath. 

 

NB. Undersink and oversink models are not interchangeable. 

The fixings must be capable of supporting the heater when full of water (see Technical 

data page 5).

3.  The undersink unit can be placed unsupported on the floor or cupboard base, but if 

additional support is required, securing screws are supplied that locate to the rear 

of the casing. [As shown in (fig.1)]

4.  Always position the Zip Aquapoint III to allow for its removal for future inspection and 

Maintenance.

5.  The Zip Aquapoint III is not recommended for installation above false ceilings.
6.  Do not install in a location where this unit or connecting pipelines can freeze.
7.  When considering the location of the heater, consideration should be given to the safe 

and visible disposal of any water resulting from leaks and seepage. 
This is particularly relevant when the heater is located in a roof space , cupboard or any 
concealed location. For guidance please call Zip Customer Service on 0845 6 005 005.

Wall Mounting

fig. 1

Positioning

Содержание AP3/05

Страница 1: ...e instructions carefully before commencing installation of this unvented water heater Please leave these instructions with the end user after installation Zip Heaters UK Ltd 14 Bertie Ward Way Dereham...

Страница 2: ...inside front cover inside back cover...

Страница 3: ...nd when correctly fitted to comply with the requirements of the United Kingdom Water Regulations Byelaws Scotland The products are listed under the WRAS Water Regulations Advisory Scheme Water Fitting...

Страница 4: ...fitted to the vessel to provide anti corrosion protection for the vessel and the heating element Description Gradual erosion of the anode will occur depending on local conditions and in extreme cases...

Страница 5: ...e appliance its wiring and piping must not be modified in any way In case of malfunction isolate the power supply immediately In case of leaks also isolate the water supply Repairs must only be carrie...

Страница 6: ...0845 6 005 005 for advice Zip Heaters UK Ltd cannot be held liable for any damages caused by failure to observe these instructions It is recommended that an HE45004 Water Block is fitted in the water...

Страница 7: ...pacity 6 Litre 10 Litre 15 Litre Weight kg Full 12 7 18 5 24 8 Weight kg Empty 6 7 8 5 9 8 Heat up time 15 C to 65 C 11 mins 18 mins 32 mins Re heat time 70 vol 7 mins 12 mins 18 mins Heat Loss kWh 24...

Страница 8: ...rol knob lens AQ0332 4 Thermostat AQ0333 5 Resettable cut out AQ0334 6 Sacrificial anode 10 15 litre AQ0335 7 Sacrificial anode 5 litre AQ0347 8 Indicator light AQ0336 9 Control knob with spring AQ033...

Страница 9: ...2 and AQ3 pressure reducing valve and line strainer see diagrams 2 3 fig2 page 10 6 If required a temperature and pressure relief valve accessory AQ1 can be used with any installation by fitting secur...

Страница 10: ...laced unsupported on the floor or cupboard base but if additional support is required securing screws are supplied that locate to the rear of the casing As shown in fig 1 4 Always position the Zip Aqu...

Страница 11: ...s Do not use plumbers paste to secure the joints as this can impair the operation of any valves connected to the heater 6 An isolating service valve not supplied should be fitted in the cold water sup...

Страница 12: ...1 NEAREST COLD WATER DRAW OFF HOT COLD EXPANSION RELIEF VALVE EXPANSION VESSEL SERVICE VALVE CHECK VALVE PRESSURE REDUCING VALVE DIAGRAM 3 Inlet pressure greater than 0 35 MPa 3 5 bar Using pack AQ2...

Страница 13: ...ole switched spur 2 If the cable length is insufficient it is recommended that the entire length of cable is replaced with no joins to the original To replace the cable a a Prise the temperature contr...

Страница 14: ...h a water temperature of 55 C is recommended for economical operation while minimising lime scale deposits and thermal losses Note Rotating the temperature control knob varies the temperature over the...

Страница 15: ...cated inside the cover DO NOT reset the over temperature cut out until the cause of it s operation has been correctly diagnosed and corrected 4 DO NOT use the water heater if it is suspected of being...

Страница 16: ...connect the wire between the anode and the vessel and check that the current between anode and vessel exceeds 0 4mA Ensure that the wire is reconnected afterwards If the current between the anode and...

Страница 17: ...the thermal controls when discharge ceases Replace the thermostat if faulty Continuous water discharge from tundish Pressure reducing valve not operating correctly Check with pressure gauge and repla...

Страница 18: ...Zip does not exclude restrict or modify any liability that cannot be excluded restricted or modified or which cannot except to a limited extent be excluded restricted or modified as between the owner...