2
GENERAL DESCRIPTION
2.1
Introduction
ZGR TOWER PRO 6 10 KVA is an intelligent, Single phase in - Single phase out, high frequency online UPS
double conversion online technology to protect your installation with maximum efficiency. Thanks to its excellent
electrical performance, perfect intelligent monitoring, its grid functions and an intelligent appearance, and
compliance with regulations on safety and electromagnetic compatibility, the UPS responds to an international
advanced level.
In this range of equipments there are 6 and 10 kVA available models with parallel function included up to 4 units.
This feature allows a gradual upgrade of user installation without the need to invest in a new UPS. It also
integrates Frecuency Converter function that enables to adapt the operating frequency in different countries 50 /
60Hz. Ideal for business continuity applications that require long battery operation.
It is possible to extend autonomy several hours using external batteries (LBT versions) with reinforced battery
charger.
POWER
NUMBER OF BATTERIES
6 kVA
16
~
20 external batteries (12 V/ud)
10 kVA
16
~
20 external batteries (12 V/ud)
Table 2-1 ZGR TOWER PRO 6 10 KVA range
2.2
Operation principle
Fig. 2-1 ZGR TOWER PRO 6 10 KVA block diagram
ZGR TOWER PRO 6 10 KVA combines the following components:
•
Input filter: Complete filtering the input AC utility power to provide the clean power for UPS.
•
AC/DC converter: Convert the filtered AC mains to DC power for the inverter and battery charger.
•
DC/DC booster: When the UPS works in battery mode, the circuit boosts the DC for DC/AC inverter.
•
DC/AC inverter: Convert the boosted DC power to stable AC output.
•
Bypass: When overload or UPS failure, it transfers to bypass mode to supply power to loads directly from
mains through and electronic switch.
•
Charger: Charge battery with intelligent power controller. Standard unit provides 1A; Long Backup unit (LBT)
provides up to 10A Max (settable).
•
Battery: Our recommendation is for Sealed Lead Acid Battery.
•
Output filter: Output filtering board to provide the clean power to loads.