When under the frequency setting press DOWN or when under battery quantity setting press UP, it goes to the 
battery capacity setting. The battery capacity line flashes as in above picture (Fig. 4-15).  

 

Use button ENTER/ON to choose the different battery capacity. Battery capacity range is 1-200Ah. (Note: 
long-press of UP or DOWM can adjustment battery capacity quickly)  

 

Press  ESC/OFF  button  to  exit  the  battery  capacity  setting  (save  the  capacity  setting)  and  goes  to 
frequency setting or battery quantity setting. 

 

 

 

Battery number/quantity setting (bN) 

 

Fig. 4-16 Battery quantity setting 

When under the battery capacity setting press DOWN or when under bypass voltage upper limit setting press UP, 
it goes to the battery quantity setting. The battery quantity line flashes as in above picture.  

 

Use button ENTER/ON to choose the different battery quantity. Battery quantity range is 16

18, 20.  

 

Press ESC/OFF button to exit the battery quantity setting (save the battery quantity setting) and goes to 
battery capacity setting or bypass voltage upper limit setting. 

 

 

Bypass High Level switch setting (HLS) 

 

Fig. 4-17 Bypass voltage upper limit setting 

 

 

When  under  the  battery  quantity  setting  press  DOWN  or  when  under  bypass voltage  lower  setting  press  UP,  it 
goes to the bypass upper limit setting. The bypass upper limit line flashes as in above picture (Fig. 4-17).  

 

Use  button  ENTER/ON  to  set  the  different  bypass  voltage  upper  limit.  The  bypass  voltage  upper  limit 
range is 5%, 10%, 15%,25% (25% only for 220 V output).  

 

Press ESC/OFF button to exit the bypass voltage upper limit setting (save the bypass voltage upper limit 
setting) and goes to battery quantity setting or bypass voltage lower limit setting. 

 

 

Содержание ZGR TOWER PRO 6

Страница 1: ...Operation Manual ZGR TOWER PRO 6 10 KVA Online single phase UPS www zigor com...

Страница 2: ......

Страница 3: ...Protective Devices 12 UPS input and output connection 14 External battery connection for extend model only LBT 14 3 5 15 4 OPERATION OF ZGR TOWER PRO 6 10 KVA 16 4 1 Start up and turn off UPS 16 Norma...

Страница 4: ...KVA 33 7 MAINTENANCE 34 7 1 Battery maintenance 34 8 TECHNICAL SPECIFICATIONS 36 9 STANDARDS 38 10 WARRANTY 39 2022 ZIGOR All rights reserved The total or partial reproduction of this User Manual or...

Страница 5: ...ined in the documentation The system shall be exposed only to admissible environmental conditions These are defined in the technical details provided for the equipment ZIGOR accepts no responsibility...

Страница 6: ...affected area must be washed immediately with clean water Only authorized personnel should repair or install the batteries Should you have any problems with the contents of this manual you must ask ZI...

Страница 7: ...l waste at the end of its useful life To preserve the environment manage them in accordance with current environmental regulations and requirements in each country or community In case of doubt consul...

Страница 8: ...or on one side of the unit Responsibility for the loss or damage of Products shall transfer to the Customer from the moment ZIGOR places these at his disposal in the place indicated by the Customer 1...

Страница 9: ...ration It is possible to extend autonomy several hours using external batteries LBT versions with reinforced battery charger POWER NUMBER OF BATTERIES 6 kVA 16 20 external batteries 12 V ud 10 kVA 16...

Страница 10: ...Inverter It completely isolates consumer loads from mains voltage and frequency variations and noise Management and monitoring Via software USB RS232 connection EPO Emergency Power OFF function Termin...

Страница 11: ...d by the UPS The minimum distance from the ventilation grills to walls or other obstacles must be 300mm Should the equipment not be installed immediately it must be stored in a room so as to protect i...

Страница 12: ...to take correct power configuration Fig 3 1 Correct power configuration U P S LOAD INPUT L OUTPUT L L N E INPUT N OUTPUT N Fig 3 2 Wrong power configuration 3 4 Electrical installation External Protec...

Страница 13: ...eplace batteries contact ZIGOR customer service and follow our recommendations WARNING Batteries must be installed exclusively by personnel authorised by ZIGOR ZIGOR takes no responsibility for damage...

Страница 14: ...External battery connection for extend model only LBT 1 Make sure battery quantity complies with the specs 16 18 20 pieces of 12V battery Measure the voltage of battery bank after finishing connectio...

Страница 15: ...s open Place and wire the batteries distributed over the cabinet divisions in accordance with the included battery assemble drawing Connect the battery cabinet s to the corresponding UPS terminals WAR...

Страница 16: ...ER PRO 6 10 KVA is a double conversion on line UPS that can operate in the following alternative modes Normal mode The rectifier charger derives power from the AC mains and supplies DC power to the in...

Страница 17: ...mode system expansion To achieve a higher capacity and or increase reliability the outputs of up to 4 UPS modules can be programmed to operate in parallel The built in parallel controller in each UPS...

Страница 18: ...allel amount set the amount of UPS in parallel C Power OFF UPS and continue with next unit 4 Now close output breakers to make work in parallel mode 5 Once all UPS was configured make sure all connect...

Страница 19: ...transfered to bypass mode To return to normal inverter mode reverse procedure must be done pushing ENTER ON on each UPS NOTE Pay attention because full load power could be assumed by only one UPS and...

Страница 20: ...battery is normal Turn on the battery switch The battery will feed the Auxiliary power board Trigger the cold start buttons at the position 9 in Fig 4 2 Fig 4 2 Cold Start button When battery normal...

Страница 21: ...S is in Battery mode Green Inverter is working Display information In the below table is shown and explained all the elements that can appear in the display SYMBOL DESCRIPTION UPS general information...

Страница 22: ...0 24 25 49 50 74 y 75 100 Indicates low battery level Load information Indicates load level 0 24 25 50 50 74 y 75 100 Indicates overload Indicates the load or the UPS output is short circuited Mute o...

Страница 23: ...age Current 04 Bat Voltage Current 05 Temperature PFC Internal temperature and ambient temperature 06 Load Current load refered to nominal 07 Bus voltage Internal bus voltage 08 Software version DSP v...

Страница 24: ...P DOWN for 3 seconds and then goes into the setting interface page After finishing setting the parameter press Operation Mode setting mod Fig 4 12 Mode setting After entering the setting menu it will...

Страница 25: ...nverter is ON it is necessary to turn off the inverter before setting voltage and frequency level Operation Output frequency setting OPF Fig 4 14 Frequency setting When under the output voltage settin...

Страница 26: ...y quantity setting The battery quantity line flashes as in above picture Use button ENTER ON to choose the different battery quantity Battery quantity range is 16 18 20 Press ESC OFF button to exit th...

Страница 27: ...voltage lower limit range is 20 30 45 Press ESC OFF button to exit the bypass voltage lower limit setting save the bypass voltage lower limit setting and goes to bypass upper limit setting or parallel...

Страница 28: ...UPS can transfer to Battery Mode automatically per 30 days And the Battery Self test Time is 10 seconds Fig 4 21 Fig 4 22 Autotest time On2 When choosing On2 UPS can transfer to Battery Mode automati...

Страница 29: ...lel redundancy quantity setting press UP it goes to the parallel quantity setting The parallel quantity flashes as in above picture Fig 4 25 Use button ENTER ON to set the parallel quantity The parall...

Страница 30: ...t LED lit 9 Fan fault Beep continuously Fault LED lit 10 Reserve Beep continuously Fault LED lit 11 Auxiliary power fault Beep continuously Fault LED lit 12 Initialization fault Beep continuously Faul...

Страница 31: ...LED lit 37 DC component over limit Once per 2 seconds INV blinking 38 Parallel Overload Once per 2 seconds INV blinking 39 Mains volt Abnormal Once per 2 seconds BATTERY LED lit 40 Mains freq abnorma...

Страница 32: ...Data Pin 4 GND Ground Fig 5 2 USB port pinout RS 232 communication data format 2400bps 8bit 1bit stop Parity none Fig 5 3 PC to UPS RS232 port PC RS232 PORT UPS RS232 PORT DEFINITION Pin 2 RX Pin 2 TX...

Страница 33: ...input UPS input breaker open circuit Press the breaker for reset Short back up time Battery not fully charged Keep UPS connecting with mains power for more than 8 hours to recharge battery UPS overloa...

Страница 34: ...trol of the event history searching for sporadic or repetitive failures 6 monthly o Check on the correct ventilation of the location o Cleaning of the equipment s air inlet filters o Removal of foreig...

Страница 35: ...the power is long term uninterrupted The battery will be fully discharge to low voltage protection shutdown Then it needs to be fully charged at once In high temperature area batteries should be manua...

Страница 36: ...nput Support OUTPUT ELECTRICAL CHARACTERISTICS Output type Single phase with Ground Rated voltage 220 230 240 Vac can be set Voltage regulation 1 0 Power factor 1 0 Crest factor 3 1 Harmonic distortio...

Страница 37: ...A Audible Visual alarms Line Failure Battery Low Overload System Fault Communications USB or RS232 SNMP card optional Relay card optional ENVIRONMENTAL AND MECHANIC CHARACTERISTICS Protection IP20 Noi...

Страница 38: ...ith the following European regulations I LVD Security directive LVD 2014 35 EU about Uninterruptible Power Supply UPS Standard EN IEC 62040 1 2019 II EMC directive 2014 30 EU about electromagnetic com...

Страница 39: ...eferring to the Installation Conditions When the customer not clearly proves the systematic realization of regular maintenance operations described in the Operating Manual Equipment deterioration due...

Страница 40: ...zigor com Consulte nuestra web para contactar con la red de delegaciones comerciales Refer to our website in order to contact the commercial branches network Veuillez consulter notre page web pour con...

Отзывы: