UFR1001E
12420-0751-13
Page
4 / 8
www.ziehl.de
Connection diagram, 1x section switch (VDE-AR-N 4105:2018-11)
1)
Feedback contacts Y1/Y2 not connected set
8
rel .
8
→
8
trel.
8
→
8
off.
8
2)
N connected set
8
Pr 1
8
,
8
Pr 3
8
or
8
Pr 5
8
3)
Nc- or no-contacts can be connected, automatic detection when switching on
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5)
Fuses only when line protection necessary, e.g. 16 A
6)
Contact closed suppresses evaluation of feedback contacts and vector shift
(
8
vsr .
8
→
8
on.
8
) suppresses feedback contacts (
8
vsr .
8
→
8
y1y2.
8
) or switches device into
standby (
8
vsr .
8
→
8
stby.
8
= default setting) e.g. through ripple control receiver or timer
7)
1 phase Application connect L1-L2-L3, 2 phase Application L1 / L2+L3 (only Pr 5, 7, 10, 13, 20)
8)
Additional switch-off of self generating plant.
Single-fault safety: shutdown of the self generation plant e.g. by ripple control input 0% with K2. Use
coupling relays ford contact multiplication of if safe isolation is required.
This second shutdown path must be tested separately during commissioning.
(
8
tst2
8
)
9)
UPS/buffer. Switches have to withstand undervoltage for min. 3 s (FRT)