TMU104V
12560-0702-02
Page
13 / 19
www.ziehl.de
Additional function from firmware version -03:
Connection from thermocouples:
•
Parameter to correct the internal reference temperature of thermocouples
Checking and setting of parameters:
•
switch off control voltage supply
•
press and keep pressed the Down (
▼) and the Set (►) key
•
switch on control voltage supply
•
wait at least 5s until tri appears in the display
Additional function from firmware version -04:
Hiding of interference and short temperature rises.
Parameters:
•
temperature rise (
tri
): the height of the temperature rise, who delay evaluation
•
temperature rise delay (
trd
): number of measurements after the measured value is accept
Checking and setting of parameters:
•
switch off control voltage supply
•
press and keep pressed the
Up (▲) and the Set (►) key
•
switch on control voltage supply
•
wait at least 5s until tri appears in the display
Display the firmware version:
Info Menü