background image

 

TMU104V 

12560-0702-02

 

Page

 

10 / 19 

www.ziehl.de 

  

9.11  Info menu 

Read-out of data on the device. 
Select the menu item with the Up/Down key until … 

 

  Display 

8

Inf.

8

 

 

  Press Set key

 

 

  Display the Firmware version of device,

 

8

FNR.

8

 / 

8

-00.

8

 (Firmware / Version) flash alternately

 

 

  Press Set key

 

 

  Display the serial number of device,

 

8

SNR.

8

 / 

8

123.

8

 (serial number in passing through figures)

 

 

  Press Set key

 

 

  Display the operating hours of device 

 

8

h  .

8

 / 

8

123.

8

 (operating hours in passing through figures)

 

 

  Press Set key

 

 

  Display the error memory of device,

 

8

Err.

8

 / 

8

  -.

8

 (no errors saved) 

8

Err.

8

 / 

8

1.23.

8

 (1 digit = number of error, 2 + 3 digit = count of errors) 

 

Delete error memory? 

 

Yes:  

Press Down key until display 

8

del.

8

 / 

8

yes.

8

 

 

  Press Set key -> 

8

yes.

8

 flashes -> deleted error memory

 

No:

   

Press Set key

 

 

  Move to the previous/next menu item with the Up and Down keys 

 
 

 

Содержание TMU104V

Страница 1: ... MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TMU104V updated 2018 11 09 sm TMU104V 12560 0702 02 Page 1 19 www ziehl de Measuring point multiplicator Measuring Transducer 1 input for temperature sensors 4 outputs Pt100 Fourfold Pt100 simulator ...

Страница 2: ...n 7 Putting into operation 7 9 1 General instructions for operation 7 9 2 Display mode 7 9 3 Menu mode 7 9 4 Parameter setting mode 7 9 5 Tips for operation 7 9 6 Switch on device 7 9 7 Configure the sensor input 7 9 8 Configure the RS485 interface 8 9 9 Sensor simulation 9 9 10 Code lock 9 9 11 Info menu 10 9 12 Possible indications in display 11 Operation 12 Error search and measures 14 Technica...

Страница 3: ... value C error codes Display of menu and configuration mode 5 Button Up Press short selection of menu item Change into display mode see 8 3 Press long 2s displays the max sensor value Reset press button Set 2s additionally 6 Button Set Press long 10 s displays the firmware version When simulating via interface Switch over to next output Pt 100 simulated value in LED OUTx on 7 Button Down Press sho...

Страница 4: ... connected to the input is available as signal Pt100 RTD at 4 insulated outputs Thus allows the connection of other sensors than Pt100 to inputs for Pt100 at other devices Normally only one input can be connected to a temperature sensor With help of TMU104 up to 4 devices controls displays monitoring devices with inputs Pt100 can be connected to one sensor at the same time Simulator for Pt100 Cont...

Страница 5: ...TMU104V 12560 0702 02 Page 5 19 www ziehl de Connecting diagram 5 1 Outputs S Sense wire 5 2 Connection of ZIEHL equipment ...

Страница 6: ...setting up and the use of electrical units The equipment are built according to DIN EN and checked and leave the plant according to security in perfect condition If in any case the information in the instructions manual is not sufficient please contact our company or the responsible representative Instead of the industrial norms and regulations written in this instructions manual valid for Europe ...

Страница 7: ...on Up Down Press short long Adjustment of parameter value slow fast Button Set Press short Storage of setting and choice of next parameter Change into menu mode after the last parameter 9 5 Tips for operation When the right decimal point in the 7 segment display is on the display mode has been left and the menu items can be chosen with up down menu mode When the right decimal point blinks you are ...

Страница 8: ... Parity 8par 8 Parity bit 8evn 8 8odd 8 8 no 8 even odd none Stop 8StP 8 Stop bit 8 1 8 8 2 8 1 2 from Firmware 02 Adjustment process Select the menu item with the Up Down key until Display 8bus 8 Press Set key Set the desired protocol using the Up and Down keys 8mod 8 8485 8 Press Set key Display 8Adr 8 8 1 8 address value flash alternately Set the desired address using the Up and Down keys Press...

Страница 9: ...de lock Here the set parameters can be protected by activating a code block The device acknowledges an incorrect entry with 8Err8 flashes three times Select the menu item with the Up Down key until Display 8Cod 8 Press Set key Display 8Pin 8 8 0 8 pin pin code flash alternately Use the Up and Down keys to set the saved pin code factory setting is 8504 8 Press Set key Set the desired code lock usin...

Страница 10: ...vice 8SNR 8 8123 8 serial number in passing through figures Press Set key Display the operating hours of device 8h 8 8123 8 operating hours in passing through figures Press Set key Display the error memory of device 8Err 8 8 8 no errors saved 8Err 8 81 23 8 1 digit number of error 2 3 digit count of errors Delete error memory Yes Press Down key until display 8del 8 8yes 8 Press Set key 8yes 8 flas...

Страница 11: ... thermocouple 8thn8 Type N thermocouple 8thr8 Type R thermocouple 8ths8 Type S thermocouple 8tht8 Type T thermocouple 8out 8 sensor output 81008 Pt100 8bus 8 RS485 interface 8Mod8 Modbus protocol 84858 Ziehl RS485 protocol 8Adr8 Device address 8 18 82478 Modbus 1 247 8 08 8 998 Ziehl RS485 protocol 0 99 8bd 8 Baud rate 8 4 88 4800 bd 8 9 68 9600 bd 819 28 19200 bd 8par8 Parity 8evn8 Even 8odd8 odd...

Страница 12: ...TMU104V 12560 0702 02 Page 12 19 www ziehl de Operation Display mode Configuration mode Menu mode Parameter ALL from firmware version 02 Stoppbit from firmware version 02 ...

Страница 13: ...at least 5s until tri appears in the display Additional function from firmware version 04 Hiding of interference and short temperature rises Parameters temperature rise tri the height of the temperature rise who delay evaluation temperature rise delay trd number of measurements after the measured value is accept Checking and setting of parameters switch off control voltage supply press and keep pr...

Страница 14: ...ew parameters of interface and connection cables The device cannot be programmed configured Cause Code lock Remedy The code block provides protection against unauthorized manipulation on the device When the code block is active the parameters cannot be changed The pin can be set by the user Pin code unknown perform a code reset While switching on the control voltage keep the Set key pressed for 2 ...

Страница 15: ...0 Measuring range C Precision Type min max B 0 1820 T 300 C 2 C E 270 1000 1 C J 210 1200 1 C K 200 1372 2 C L 200 900 1 C N 270 1300 2 C R 50 1770 2 C S 50 1770 2 C T 270 400 1 C Temperature drift 0 01 K Measuring error of the sensor wire 0 25 μV Ω Reference junction 5 C after warmup time of 15 minutes Measuring time 440 ms Sensor output OUT 1 OUT 4 Type Pt100 according to EN 60751 Reaction time ...

Страница 16: ... no condensation External wiring temperature range 5 C 70 C Vibration resistance EN 60068 2 6 2 25 Hz 1 6 mm Housing Design V6 switchgear mounting Mounting height 55 mm Width 6 TE Dimensions width x height x depth B x H x T 105 x 90 x 58 mm Wire connection one wire each 1 x 0 14 mm2 2 5 mm2 Stranded wire with insulated ferrules each 1 x 0 14 mm2 1 5 mm2 Strip length min 8 mm Torque 0 5 Nm 3 6 lb i...

Страница 17: ... ziehl de Housing Design V6 Dimensions in mm 1 Cover 5 Front panel 2 Base 6 Position downward 3 Bar for snap mounting 7 For fixing to wall with screws Ø 4 2 mm 4 Latch for sealing 48 58 45 3 61 8 16 5 90 Option 105 98 116 70 1 2 4 5 6 7 3 ...

Страница 18: ... Byte Line Feed LF 0xa 1 Byte 10 Byte 2 TMU104V sends the requested data TMU104V sends start Type of unit address of unit mode data BCC CR LF Start of message s ASCII Start sign same as start sign at data request S ASCII STX 0x2 1 Byte Data Type of unit TMU104V ASCII 7 Byte separated by Address of unit 00 99 ASCII 2 Byte separated by Mode of data 0 9 ASCII 1 Byte separated by Sensor value 199 9 85...

Страница 19: ...1 99 ASCII Start of message s s S or STX Block check s 115 exor 0 48 exor 1 49 exor r 114 exor 0 48 048 The values in brackets correspond with the ASCII code of the sign TMU104V answers s TMU104V 01 0 033 9 00 088 r n End of message CR LF Block check Internal error Sensor value Data mode Address of unit Type of unit Start of message 14 3 Modbus Information s for Modbus configuration and programmin...

Отзывы: