Adjustment values table BDEW June 2008, acc 3.2.3.3-1,
Medium Voltage Pr 5+6
Function
Adjustment range
of the protective
relay
Default settings
Voltage increase protection U>>
1.00
– 1.30 U
n
1.15 U
n
100 ms
Voltage increase protection U>
1.00
– 1.30 U
n
1.08 U
n
60 s
Voltage decrease protection U<
0.15
– 1.00 U
n
0.80 U
n
2.7 s
Voltage decrease protection U<< *
0.15
– 1.00 U
n
0.45 U
n
300 ms
* Not enabled in as delivered condition
4
Application and brief description
The SW32V voltage relay is a high-quality voltage monitor with a large measurement range for monitoring
direct, alternating and three-phase networks for overvoltage and/or undervoltage. In three-phase current
networks, phase symmetry and phase sequence can be monitored in addition.
The limits are set in volts. That allows using the unit with various rated voltages.
The digital display is used to display the measurements and to precisely set limits, response times and
functions.
5
Summary of the functions
For use as a voltage monitor in energy generation and distribution plants, especially in-plant systems such
as PV plants or combined heat and power plants.
Voltage monitoring in machines and plants to prevent errors, damage or failures in sensitive equipment or
devices.
•
Voltage monitoring in direct current networks DC 10.0…600 V
•
Voltage monitoring in alternating current networks AC 15.0…480 V
•
Voltage monitoring in three-phase current networks with//without N up to 3AC 830 V, asymmetrical
and phase failure monitoring connectible
•
Preset programs for grid- and plant protection according to bdew directive (medium voltage)
•
Real root mean square measurement (for AC, both half waves)
•
2 Alarms/output relays, 1 each change-over contact
•
Alarm and reset delay for every limit value can be individually set
•
Setting of limits and hysteresis in volts
•
Measurement value simulation to check the settings
•
Code lock can be enabled
•
Control voltage AC/DC 24-270 V
•
Distributor housing for panel mounting, 4 TE (70 mm), front-to-back size 55 mm
•
Mounting on 35 mm mounting rails DIN EN 60715