10.6  Parameters 

The device can be parameterized via the device's web pages or directly on the device. 
The function of the device is explained under "Detailed description". 
 

10.6.1  Machines 

On the device, Menu 
/ Machines 

In the web browser, Register 
Configuration, Machines 

Parameter, description 

Search. 

Not possible...

 

All correctly configured STW161M/STW168M connected 
to the RS485 BUS are registered 

On/off. 

On/off

 

Status 

On/off

 

Activate STW161M/STW168M with corresponding 
address (switch on/off) 

I-limit (Adr. 0.31) 

0.5.....9.9A / switch

 

I-limit (Adr. 0.31) 

0.5.....9.9A 

/ switch

 

If the I limit value is exceeded, the slider opens (detection, 
machine on). 
When using switches, a closed contact is interpreted as a 
switched on machine 

Delay on (Adr. 
0.....31) 

0......20s

 

Delay (Adr. 0.....31) 

0.....20s

 

Delay after switching on the machine until the 
corresponding slider opens 

Overrun time (Adr. 
0.....31) 

00:00.02:00 

mm:ss

 

Overrun time (Adr. 0.....31) 

0....120s

 

Delay after switching off the machine until the 
corresponding slider closes 

Volume flow (Adr. 
0....31) 

0.....100%

 

Volume flow (Adr. 0....31) 

0.....100%

 

Indication of the volume flow on the corresponding slider 

Line (Adr. 0.....31) 

1.....4

 

Line (Adr. 0.....31) 

1.....4

 

Extraction line in which the machine is integrated. Up to 
four lines are supported. 

Priority (Adr. 0.....31) 

1.....32

 

Priority (Adr. 0.....31) 

1.....32

 

Priority, in which order additional sliders open to reach the 
minimum volume flow (1 = highest). In each line, the 
priority must be unique. When setting on the device, no 
plausibility check is carried out, if necessary, an error 
message is displayed 

End position Y4 
(Address 0....31)  

off / 1.0....10.0s

 

End position Y4 (Address 
0....31) 

off / 1.0....10.0s

 

Evaluation of a limit switch on the sliders (input Y4 to 
STW161M). Within the set time, the limit switch must 
close. Otherwise, an error message is generated. This 
message can be parameterized to a relay (see relay) 

Y4 off after 

00.1.......25.0 ss,s

 

Global Settings: End 
position Y4 off after 

0.0.....25.0s

 

Delay in the evaluation of a limit switch on the sliders 
(when the slider closes again) 

Last overrun 

00:00.20:00 mm:ss

 

Global Settings: Last 
overrun 

0.....1200s

 

After switching off the last machine: 

• 

Overrun time slider elapses 

• 

Subsequently, the overrun time of the extraction 

• 

Extraction switches off 

• 

Overrun time "Last overrun" elapses 

• 

Slider closes 

Input Y1 

Switch /

 

00:00:00... 01:00:00

 

hh:mm:ss

 

Global Settings: Input Y1 
(I0&I31) 

Switch / 0.3600s

 

All sliders open and the extraction starts, Switch: 

Slider 

open static 

Time: 

Start with swipe signal, sliders remain 

open for the set time 

Offset open 

00.00.....02.50 ss,ss

 

Global Settings: Slider offset 
open 

0.0......2.5s

 

Time offset when multiple sliders open at the same time 

Содержание STW164IP

Страница 1: ...Operating Manual STW164IP updated 2023 12 05 dr from Firmware 0 00 For more information and help about this product please scan the QR Code or choose the following link STW164IP Operating manual Quick...

Страница 2: ...e 12 7 3 Discharge 12 7 3 1 Starts with extraction 12 7 3 2 Starts with cleaning 12 7 4 Input Y1 I0 I31 12 7 5 Input Y2 13 7 6 Relays K3 and K4 13 7 7 Analog output 13 8 Important Information 13 9 Ass...

Страница 3: ...6 Disposal 30 1 General Notes Compliance with the following instructions is mandatory to ensure the functionality and safety of the product If the following instructions given especially but not limit...

Страница 4: ...e table can be used by the customer to document the set values of the parameters enter values in tables Menu on the device Machines Parameters on website Configuration Machines Default value My data a...

Страница 5: ...flow line 1 10 Min Vol line 2 Min volume flow line 2 10 Min Vol line 3 Min volume flow line 3 10 Min Vol line 4 Min volume flow line 4 10 Open more Open more sliders Yes Cleaning Configuration Cleanin...

Страница 6: ...ditional sliders can be opened to optimize the air flow Assignment to different lines and prioritization is possible It is also possible to control cleaning and discharge The parameters are convenient...

Страница 7: ...ther sliders can be prevented o Message if exceeded Minimum volume flow of the entire extraction 1 100 o If necessary automatic opening of additional sliders o Sequence adjustable via priority of the...

Страница 8: ...ates Modbus TCP read Display and operation Color LCD display for displaying the operating conditions and for programming Intuitive operations via joystick Convenient display of operating states and pr...

Страница 9: ...beginning or end of the BUS line the terminating resistors must be switched on at the corresponding STW168M or STW161M beginning and end of the BUS line 6 1 Connection of additional power supplies It...

Страница 10: ...machine is switched on After delay time for machine The slider flap of the extraction channel opens After delay time for extraction Switches on the extraction system Machine I limit value exceeded Mac...

Страница 11: ...age is displayed on the device and in the web browser This message can be parameterized to a relay Extraction max vol Extraction open more Relay volume flow Min volume flow line 1 4 Smallest volume fl...

Страница 12: ...hes on and at least 50 of the continuous shaking time has not yet elapsed cleaning is restarted at the next opportunity 7 3 Discharge Two different discharge modes are available 7 3 1 Starts with extr...

Страница 13: ...output Proportional to the volume flow a voltage is output at the analogue output This can control a frequency converter on an extraction motor Output voltage DC 0 10 V at 0 volume flow Analog output...

Страница 14: ...to the BUS lines 9 Assembly The device can be fastened Distributor installation on 35mm mounting rail to EN 60715 With M4 screws for wall mounting additional bars not included Connect according to the...

Страница 15: ...e operation The device is operated via the integrated joystick button It can be operated in four directions up down left and right In conjunction with the graphical colour display operation of the dev...

Страница 16: ...resses of STW161M STW168M connected to the RS485 BUS Display of the current consumption of the individual machines measured bySTWA1 H converters When switches are used machine on off is displayed Meas...

Страница 17: ...u Press for 2s Press back to the display pages Press Down press Up press Submenu Call up submenu Exit submenu Call up parameter menu Navigate within the submenu From the main menu select the submenu a...

Страница 18: ...integrated Up to four lines are supported Priority Adr 0 31 1 32 Priority Adr 0 31 1 32 Priority in which order additional sliders open to reach the minimum volume flow 1 highest In each line the pri...

Страница 19: ...m volume flow of the entire system To achieve this additional valves flaps are opened if necessary Max Vol 5 100 Max volume flow 5 100 Maximum permissible volume flow of the entire system If exceeded...

Страница 20: ...ning time K2 off during the vibration intervals Continuous vibration time 00 00 20 00 mm ss Continuous vibration time 0 1200s The continuous vibration time starts after the vibration intervals Static...

Страница 21: ...eterize to a relay End position of slider open not reached within the parameterized time Fault off Relay K3 Relay K4 Fault off Rel K4 Rel K3 Reporting faults errors Error from RS485 BUS device not rea...

Страница 22: ...of the DNS server on the network Not possible Time server settings and Time zone settings Settings for date time for error memory In the event of operation without a time server the date time will not...

Страница 23: ...nfo In the web browser Register Counter Parameter description Operating hours Counter STW164IP and Counter STW161M STW168M Operating hours of devices controlled by the STW164IP The values can be reset...

Страница 24: ...rameters Display settings for LCD display see Parameters Code lock see Parameters Firmware update STW164IP o Update notification message when update is available o Firmware status if necessary the fir...

Страница 25: ...gged Storage in case of occurrence of a new error Storage in case of disappearance of an error Storage of o Status of all max possible STW161M STW168M on the BUS o Relay state K1 K4 o Status inputs Y1...

Страница 26: ...server but after 20 s at the latest 11 7 Register Counter STW164IP Operating hours counter STW164IP Switch on times of relay extraction cleaning K3 and K4 values can be reset STW161M STW168M Address 0...

Страница 27: ...nd position contact on the corresponding STW161M If necessary adjust parameters machine end position Y4 extend time Display website reports STW16xM 24V On display page 2 3 the measured value of the ST...

Страница 28: ...A Ue 24V DC 13 Ie 0 2A Ue 250VV Test conditions for relay outputs EN 61010 1 Rated impulse withstand voltage Overvoltage category Degree of contamination Rated insulation voltage Ui 4000V III 2 300V I...

Страница 29: ...61326 1 industrial environment Installation conditions Permissible ambient temperature Permissible storage temperature Installation height Climate resistance Permissible wiring temperature Oscillation...

Страница 30: ...30 www ziehl de 15 Design V8 16 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal provisions ZIEHL is registered with the EAR Foundati...

Отзывы: