10.6 Parameters
The device can be parameterized via the device's web pages or directly on the device.
The function of the device is explained under "Detailed description".
10.6.1 Machines
On the device, Menu
/ Machines
In the web browser, Register
Configuration, Machines
Parameter, description
Search.
Not possible...
All correctly configured STW161M/STW168M connected
to the RS485 BUS are registered
On/off.
On/off
Status
On/off
Activate STW161M/STW168M with corresponding
address (switch on/off)
I-limit (Adr. 0.31)
0.5.....9.9A / switch
I-limit (Adr. 0.31)
0.5.....9.9A
/ switch
If the I limit value is exceeded, the slider opens (detection,
machine on).
When using switches, a closed contact is interpreted as a
switched on machine
Delay on (Adr.
0.....31)
0......20s
Delay (Adr. 0.....31)
0.....20s
Delay after switching on the machine until the
corresponding slider opens
Overrun time (Adr.
0.....31)
00:00.02:00
mm:ss
Overrun time (Adr. 0.....31)
0....120s
Delay after switching off the machine until the
corresponding slider closes
Volume flow (Adr.
0....31)
0.....100%
Volume flow (Adr. 0....31)
0.....100%
Indication of the volume flow on the corresponding slider
Line (Adr. 0.....31)
1.....4
Line (Adr. 0.....31)
1.....4
Extraction line in which the machine is integrated. Up to
four lines are supported.
Priority (Adr. 0.....31)
1.....32
Priority (Adr. 0.....31)
1.....32
Priority, in which order additional sliders open to reach the
minimum volume flow (1 = highest). In each line, the
priority must be unique. When setting on the device, no
plausibility check is carried out, if necessary, an error
message is displayed
End position Y4
(Address 0....31)
off / 1.0....10.0s
End position Y4 (Address
0....31)
off / 1.0....10.0s
Evaluation of a limit switch on the sliders (input Y4 to
STW161M). Within the set time, the limit switch must
close. Otherwise, an error message is generated. This
message can be parameterized to a relay (see relay)
Y4 off after
00.1.......25.0 ss,s
Global Settings: End
position Y4 off after
0.0.....25.0s
Delay in the evaluation of a limit switch on the sliders
(when the slider closes again)
Last overrun
00:00.20:00 mm:ss
Global Settings: Last
overrun
0.....1200s
After switching off the last machine:
•
Overrun time slider elapses
•
Subsequently, the overrun time of the extraction
•
Extraction switches off
•
Overrun time "Last overrun" elapses
•
Slider closes
Input Y1
Switch /
00:00:00... 01:00:00
hh:mm:ss
Global Settings: Input Y1
(I0&I31)
Switch / 0.3600s
All sliders open and the extraction starts, Switch:
Slider
open static
Time:
Start with swipe signal, sliders remain
open for the set time
Offset open
00.00.....02.50 ss,ss
Global Settings: Slider offset
open
0.0......2.5s
Time offset when multiple sliders open at the same time