ZIEHL MU100U Скачать руководство пользователя страница 6

 

MU100U 

10730-0701-00

 

Page

 

6 / 8 

www.ziehl.de 

  

  For current output 0

…20 mA (terminals 6 and 7) adjust to 1.000 mA, 

  For voltage output 0

…10 V (terminals 8 and 7) adjust to 0.500 V. 

 
Full- scale: set the input to max. signal (20 mA or 10 V), adjust the current or voltage output with the 

potentiometer “Scale”. 

  For current output 0

…20 mA (terminals 6 and 7) adjust to 20.00 mA, 

  For voltage output 0

…10 V (terminals 8 and 7) adjust to 10.00 V. 

 
Check zero and Full- scale and repeat if necessary. 
 
 

10 

Error search 

The device has 2 inputs for DC voltage and current with common ground. If the connections are exchanged, 
no damage is possible, as a rule the transmitter will not deliver a signal at the output. 
At the same time a current and voltage signal can be applied. The output then has a summed signal, limited 
by the maximum output value. The signals at the output are at the same time and can be loaded with their 
rated load. The offset adjustment has an effect on both outputs but can optionally be optimized for one output 
only. 
 
 

11 

Technical data 

 

Rated supply voltage Us 

DC/AC 24 

– 240 V 

0/50…120Hz 

Tolerance 

DC 20.4 - 297 V   

AC 20 - 264 V 

Power consumption 

< 3 W 

 

 

< 5 VA 

 

Inputs 

Voltage or current with GND1 

Voltage input 

DC 0…10 V 

Max. permissible voltage 

DC 200 V 

Nominal input resistance 

>500 

kΩ 

 

 

Current input 

DC 0…20 mA or 4… 20 mA  

Max. permissible current 

DC 50 mA 

Nominal input resistance 

50 

Ω 

 

Connection or external transmitter 

DC -5V1 / GND1 / DC +16V1 

current 

Max. 30 mA 

 

Outputs 

Voltage or current with GND2 

Voltage output 

DC 0…10 V 

Max. open circuit voltage 

DC 12 V 

Load 

>1 

kΩ 

 

 

Current output 

DC 0…20 mA or 4… 20 mA  

Max. short circuit current 

DC 50 mA (short circuit protection) 

Load 

<500 

Ω 

Accuracy at Tu = 23 °C 

Class 0.5 

Temperature coefficient 

0,025% *K

-1

 

Nominal rise time t= 0,9 

50 ms 

 

Test conditions 

EN 61010-1 / EN 50178 

Rated impulse voltage 

4000 V 

Overvoltage category 

III 

Pollution degree 

Rated insulation voltage Ui 

300 V 

On-period 

100 % 

Содержание MU100U

Страница 1: ...ehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU100U updated 2018 11 09 sm MU100U 10730 0701 00 Page 1 8 www ziehl de Universal Transmitter Isolation Amplifier ...

Страница 2: ...rt description 3 3 Overview of functions 3 4 Connecting diagram 3 5 Important Information 4 6 Installation 4 7 Connection examples 5 8 Commissioning 5 9 Adjustment examples 5 10 Error search 6 11 Technical data 6 12 Housing Type K 8 1 Display and controls Adjust Full scale Adjust Zero LED green in Operation ...

Страница 3: ... eliminates these problems The universal supply voltage and various input and output signals in one device drastically simplify warehousing The universal transmitter MU100U can be connected to any supply voltage between 24 V and 240 V DC or AC voltage can be connected Input and output signals are galvanically isolated Signals DC 0 4 20 mA or 0 0 V can be connected to the inputs Current and voltage...

Страница 4: ...ndition you must observe the safety instructions in this instruction manual titled Important Information Failure to follow the safety instructions may result in death personal injury or property damage to the equipment itself and other equipment and facilities Instead of the industrial norms and regulations written in this instruction manual valid for Europe you must observe out of their geographi...

Страница 5: ...o point with zero signal at the input set 0 mA or 0 V or bridge input adjust the current or voltage output with the potentiometer Zero For current output 4 20 mA terminals 6 and 7 adjust to 4 00 mA For voltage output 2 10 V terminals 8 and 7 adjust to 2 00 V Full scale set the input to max signal 20 mA or 10 V adjust the current or voltage output with the potentiometer Scale For current output 4 2...

Страница 6: ...ame time and can be loaded with their rated load The offset adjustment has an effect on both outputs but can optionally be optimized for one output only 11 Technical data Rated supply voltage Us DC AC 24 240 V 0 50 120Hz Tolerance DC 20 4 297 V AC 20 264 V Power consumption 3 W 5 VA Inputs Voltage or current with GND1 Voltage input DC 0 10 V Max permissible voltage DC 200 V Nominal input resistanc...

Страница 7: ...tic conditions 5 85 rel humidity no condition Installation height 2000 m over N N Housing Type K Dimension H x W x D 75 x 22 5 x 110 mm Width 1 TE Line connection solid wire 1 x 0 5 mm2 2 5 mm2 AWG 22 14 Standard wire with insulated ferrules 1 x 0 14 mm2 1 5 mm2 AWG 28 16 Torque 0 5 Nm Protection class housing terminals IP40 IP 20 Mounting Snap mounting on 35 mm standard rail EN60715 or M4 screws ...

Страница 8: ... Page 8 8 www ziehl de 12 Housing Type K Dimension in mm 1 lower part 2 upper part 3 bar 4 screw 5 holes for screw mount 19 8 19 8 35 4 22 5 75 0 82 5 110 0 1045 1940 19 45 19 60 19 45 19 60 4 2 100 5 5 0 2 1 3 4 3 1 3 2 5 ...

Отзывы: