Connection examples
8
Commissioning
The following in-
/ output ranges can be set with the two trimming potentiometers “Zero” and “Scale”.
Input
Output
0…20 mA
0…20 mA
0...10 V
Factory Setting
0…10 V
2...10 V
4…20 mA
0…20 mA
0...10 V
2...10 V
4...20 mA
Can be adjusted by the
customer
To ensure that the accuracy class 0.5 is maintained even after the customer has been readjusted, the
measuring instrument used should be at least class 0.1.
9
Adjustment examples
1) Input
0…20 mA or 0…10 V
Output
4…20 mA or 2…10 V
Zero point: with zero signal at the input (set 0 mA or 0 V or bridge input), adjust the current or voltage output
with the potentiometer “Zero”.
•
For current output 4…20 mA (terminals 6 and 7) adjust to 4.00 mA,
•
For voltage output 2…10 V (terminals 8 and 7) adjust to 2.00 V.
Full- scale: set the input to max. signal (20 mA or 10 V), adjust the current or voltage output with the
potentiometer “Scale”.
•
For current output 4…20 mA (terminals 6 and 7) adjust to 20.00 mA,
•
For voltage output 2…10 V (terminals 8 and 7) adjust to 10.00 V.
Check zero and Full- scale and repeat if necessary.
2) Input
4
…20 mA or 2…10 V
Output 0
…20 mA or 0…10 V
Zero point: at the input (terminals 1 and 2) set current constant to 4.800 mA. Adjust the current or voltage
output with the
potentiometer “Zero”.