Commissioning 

When switched on, all LEDs light up for 1s. 
 

9.1  Normal operation 

PTC thermistor T1 .. T8 

Button 

Alarm messages 

Sensor  

LED 

Reset 

 

(Ohm) 

red 

green 

Y1, Y2 

 

< 1600 

off 

on 

 

No alarm 

> 3650 

on 

on 

 

Alarm, response temperature exceeded 

< 1600  flashes 

on 

 

Storage of an alarm 

< 1600 

off 

on 

Reset an alarm 

 

< 20 

on 

flashes 

 

Alarm, sensor short circuit 

> 40 

off 

on 

 

No alarm 

 

9.2  Switching PTC thermistor circuits on and off 

During operation, individual PTC thermistor circuits can be switched on or off. 

Button 

Function 

Sensor Select 
press 

  Selection of the PTC thermistor circuit 

  red LED of selected circuit flashes quickly 

On/Off (Reset) 
press 

  green LED on, PTC thermistor circuit switched on 

  green LED off, PTC thermistor circuit switched off 

Sensor Select 
press 

  Selection of the next PTC thermistor circuit 

  after PTC thermistor circuit T8, return to normal operation takes 

place 

≥ 2s Sensor Select 
press 

  immediate return to normal operation 

≥ 5s no button 

  Return to normal operation 

 
 

 

Содержание MSR820V

Страница 1: ...nd Plant Protection Operating Manual MSR820V updated 2023 07 11 dr For more information and help about this product please scan the QR Code or choose the following link MSR820V Operating manual Quick...

Страница 2: ...7 9 4 Display of the configuration settings 7 10 Error search 8 11 Technical data 9 12 Housing Type V4 10 13 Disposal 10 1 General Notes Compliance with the following instructions is mandatory to ens...

Страница 3: ...n to turn the circuit off or on o The green LED indicates the status on off o Button 2s pressed return to normal operation o 5s no button actuation return to normal operation 2 5 Red sensor LEDs T1 T8...

Страница 4: ...ce 1500 each Simple activation deactivation of individual PTC thermistor circuits display via LEDs 2 potential free relay outputs indication of switching status via LEDs Status display of the PTC ther...

Страница 5: ...lt according to DIN VDE EN IEC and checked and leave the plant according to security in perfect condition If in any case the information in the instruction s manual is not sufficient please contact ou...

Страница 6: ...2 Switching PTC thermistor circuits on and off During operation individual PTC thermistor circuits can be switched on or off Button Function Sensor Select press Selection of the PTC thermistor circui...

Страница 7: ...X N C contact Reset Sensor green T2 red Relay function X K1 K2 Quiescent current Reset X K1 K2 Working current Reset X X K1 quiescent current K2 working current Reset Sensor green T3 red Zero voltage...

Страница 8: ...uits T1 T8 lights up Remedy Check the wiring of the PTC thermistors PTC thermistor circuits where the red LED lights up have a resistance 3650 Ohm Cause At least one red LED of the PTC thermistor circ...

Страница 9: ...t Ie for changers AC15 Ie 3 A DC13 Ie 0 2 A Recommended back up fuse max 4 A Mechanical contact life 107 operations Electrical contact life Resistive 1 x 105 AC Resistive 5 x 104 DC Testing conditions...

Страница 10: ...ling 5 front panel 6 position downward 7 for fixing to wall with screws 4 2 mm 13 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal pr...

Отзывы: