9.3.7
Indication of the digital display:
Pr1
...
Pr9
= program number
A1
,
A2
= alarm 1 or alarm 2 active
A12
= alarm 1 and alarm 2 active
additional
L
= alarm locked, for setting back „reset“ is necessary.
S
= sensor
100
,
1000
= Pt 100, Pt 1000
83
,
84
= KTY-sensor 83, 84
LA
= 2-wire cable resistance
3-L
= 3-wire configuration
Thermocouples (th..)
Display
thb
thE
thJ
thk
thL
thn
thr
thS
tht
Type
B
E
J
K
L
N
R
S
T
CoMP
= compensation of the reference temperature of thermocouples
int
= internal reference temperature or fix reference temperature
0-10
= 0-10 V voltage input
0/4-20
= 0/4-20 mA current input
SCAL
= scaling of display for voltage- and current input
Auto
= to adopt zero point, full scale and decimal point from the chosen type
USEr
= free scaling of zero point, full scale and decimal point
____
= zero point value for 0 V, 0/4 mA
,,,,
= full scale value for 10 V, 20 mA
dP
= decimal point
AL 1
,
AL 2
= alarm limit
ALd
= alarm limit day
Aln
= alarm night
H
= hysteresis
dAL
= alarm delay (time delay until alarm)
doF
= switch back delay (time delay until alarm switches back to good)
rEL
= function of relay
r
,
A
= closed-circuit current mode, operating current mode
r-L
,
A-L
= closed-circuit- / operating current with interlocked switching (
L
ocked)
tst
= relay test periodically in hours after the time
don
for the duration
doF
don
= periodical time in hours for testing alarm/relay (
oFF
= no test)
doF
= duration of test
E
= exit (leave loop)
ovt
= analogue output:
oFF
, 0-10 V, 0-20 mA, 4-20mA
SEn
= sensor select for analogue output
S12,
= maximum value of sensor 1 or sensor 2 is put out
S12_
= minimum value of sensor 1 or sensor 2 is put out
____
= value, at which 0 V, 0/4 mA is put out
,,,,
= value, at which 10 V, 20 mA is put out
diF
= difference sensor 2 minus sensor 1
on
,
oFF
= on/off
Si
= simulation
CodE
= code (pin)
Pin
= factory setting of Pin: 504