background image

 

TR210 

12430-0701-02

 

Page

 

9 / 24 

www.ziehl.de 

  

9.3.7 

Indication of the digital display:

 

 

Pr1

 ... 

Pr9

 

= program number 

A1

A2

 

 

= alarm 1 or alarm 2 active 

A12

    

 

= alarm 1 and alarm 2 active 

additional 

L

  

= alarm locked, for setting back „reset“ is necessary. 

 
S

 

= sensor 

 

100

1000

 

= Pt 100, Pt 1000 

 

83

,

 84

 

= KTY-sensor 83, 84 

 

LA

 

= 2-wire cable resistance 

 

3-L

 

= 3-wire configuration 

 

Thermocouples (th..) 

Display 

thb

 

thE

 

thJ

 

thk

 

thL

 

thn

 

thr

 

thS

 

tht

 

Type 

 

 

CoMP

 

= compensation of the reference temperature of thermocouples 

 

int

 

= internal reference temperature or fix reference temperature 

 

0-10

 

= 0-10 V voltage input 

 

0/4-20

 

= 0/4-20 mA current input 

 

SCAL

 

= scaling of display for voltage- and current input  

 

Auto

 

= to adopt zero point, full scale and decimal point from the chosen type 

 

USEr

 

= free scaling of zero point, full scale and decimal point 

 

____

 

= zero point value for 0 V, 0/4 mA 

 

,,,,

 

= full scale value for 10 V, 20 mA 

 

dP

 

= decimal point 

AL 1

AL 2

 

= alarm limit 

 

ALd

 

= alarm limit day 

 

Aln

 

= alarm night 

 

H

 

= hysteresis 

 

dAL

 

= alarm delay (time delay until alarm) 

 

doF

 

= switch back delay (time delay until alarm switches back to good) 

 

rEL

 

= function of relay 

 

r

A

 

= closed-circuit current mode, operating current mode 

 

r-L

A-L

 

= closed-circuit- / operating current with interlocked switching (

L

ocked) 

tst 

= relay test periodically in hours after the time 

don

 for the duration 

doF

 

 

 

don

 

= periodical time in hours for testing alarm/relay (

oFF

 = no test) 

 

doF

 

= duration of test 

= exit (leave loop) 

ovt

 

= analogue output: 

oFF

, 0-10 V, 0-20 mA, 4-20mA 

   

SEn

 

= sensor select for analogue output 

     

S12,

 

= maximum value of sensor 1 or sensor 2 is put out 

     

S12_

 

= minimum value of sensor 1 or sensor 2 is put out 

 

____

 

= value, at which 0 V, 0/4 mA is put out 

 

,,,,

 

= value, at which 10 V, 20 mA is put out 

diF

 

 

= difference sensor 2 minus sensor 1 

on

oFF

 

= on/off 

Si 

 

= simulation 

CodE

 

= code (pin) 

Pin

 

= factory setting of Pin: 504 

 

 

Содержание MINIPAN TR210

Страница 1: ...s Grid and Plant Protection Operating Manual TR210 updated 2022 12 01 dr from Firmware 0 00 For more information and help about this product please scan the QR Code or choose the following link TR210...

Страница 2: ...Program 7 16 10 8 Program 8 17 10 9 Program 9 18 11 Action chart 18 12 Factory setting 19 13 Error search and measures 20 14 Technical data 21 15 Housing Design V4 24 16 Disposal 24 1 General Notes C...

Страница 3: ...technology 3 Overview of functions 2 Sensor inputs Pt 100 Pt 1000 KTY 83 or KTY 84 in 2 or 3 wire configuration Thermocouples Type B E J K L N R S T Input signal DC 0 10 V DC 0 4 20 mA 0 1 C resolutio...

Страница 4: ...gram each parameter is being reset to factory setting see chart factory setting Choosing the programs When applying the power supply hold the pushbutton Set for 10 s Then the program Pr 1 Pr 9 can be...

Страница 5: ...of their geographical scope the valid and relevant regulations of the corresponding country DANGER Hazardous voltage Will cause death or serious injury Turn off and lock out all power supplying this d...

Страница 6: ...ton SET RESET Push short two sensors Display sensor 1 sensor 2 difference one sensor Display sensor alarm limit 1 alarm limit 2 Push for 2 s Reset restart interlock Push for 4 s Display of chosen prog...

Страница 7: ...it is reached and switches back when the signal is fallen by the hysteresis E g limit 130 C and hysteresis 5 C Relay switches at 130 C and switches back at 125 C Positive hysteresis vice versa MIN swi...

Страница 8: ...de lock is activated all parameters can be seen but not be changed anymore In case of problems with the code lock forgotten Pin the lock can be switched off and the Pin can be set back to 504 by pushi...

Страница 9: ...mal point ____ zero point value for 0 V 0 4 mA full scale value for 10 V 20 mA dP decimal point AL 1 AL 2 alarm limit ALd alarm limit day Aln alarm night H hysteresis dAL alarm delay time delay until...

Страница 10: ...280 2000 Up Set Down Reset 2s Set of f 1 9999 h AL 2 Limit Zero Fullscale Limit alarm 1 10 Operation 10 1 Program 1 Pr1 1 temperature sensor 2 limit values Operation with pushbuttons LEDs on type pla...

Страница 11: ...ullscale S 2 Typ ____ Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit alarm 1 10 2 Program 2 Pr2 2 temperature sensors each 1 limit value Operation with pushbuttons LE...

Страница 12: ...s Set 280 2000 Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit day 1 10 3 Program 3 Pr3 1 temperature sensor 2 limit values day and 2 limit values night Operation with...

Страница 13: ...Typ ALd2 Limit Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit day 1 10 4 Program 4 Pr4 2 temperature sensors each 1 limit value day and 1 limit value night Operation...

Страница 14: ...s r EL r A r L A L Er r on oFF Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit alarm 1 10 5 Program 5 Pr5 2 temperature sensors temperature difference S 2 minus S 1 Op...

Страница 15: ...Fullscale ____ ____ Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit alarm 1 10 6 Program 6 Pr6 1 input 0 10 V or 0 4 20 mA 2 limit values Operation with pushbuttons L...

Страница 16: ...S 2 Typ AL 2 Limit Zero Fullscale Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit alarm 1 10 7 Program 7 Pr7 2 inputs 0 10 V or 0 4 20 mA each 1 limit value Operation...

Страница 17: ...nsor 2 2 s Max 2 s Min Difference 2 s Max 2 s Min Pi n 0 9999 3x Er r on EL oFF 3x on EL O FF CodE on EL oFF o k Pi n 0 9999 Limit alarm 1 10 8 Program 8 Pr8 2 inputs 0 10 V or 0 4 20 mA difference S...

Страница 18: ...me of the unit depends on the number of the connected sensors and the measuring function If the temperature is changing constantly the measuring time t M is about 2 s If the temperature is changing ra...

Страница 19: ...H Hysteresis 2 0 2 0 2 0 2 0 2 0 020 020 020 dAL Alarm delay 0 0 0 0 0 0 0 0 dof Delay Alarm off 0 0 0 0 0 0 0 0 rel Relay function r r r r r r r r Err Sensor Error on on on on on on on on Alarm 2 AL...

Страница 20: ...tton Set Code oFF Pin 504 Indicated temperature does not correspond to the sensor temperature Check connected sensor type Check cable resistance Display indicates Er1 or Er2 Er1 Sensor short circuit E...

Страница 21: ...d fuses for contact T 3 15 A gL Expected contact life mechanical 3 x 107 operations Expected contact life electrical 1 x 105 operations at AC 250 V 6 A Test conditions EN 61010 1 Rated impulse voltage...

Страница 22: ...0 4100 KTY 84 40 150 150 4000 4100 Tolerance 0 2 of measured value 0 5K KTY 5 K Sensorstrom 0 8 mA Temperaturdrift 0 04 C K Thermocouples according to EN 60 584 DIN 43 710 Measuring range C Precision...

Страница 23: ...ut 0 20 mA 0 mA Input 4 20 mA 3 7mA sensor break Er2 11V 22mA over current over voltage Er3 11V 22mA for all other faults Er4 Er8 Er9 11V 22mA Housing Design V4 switchgear mounting Mounting height 55...

Страница 24: ...ling 5 Front panel 6 Position downward 7 For fixing to wall with screws 4 2 mm 16 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal pr...

Отзывы: