Operating Instructions PAE10E-M / PSE-6/14V  

 

 

Date 0618

 

R-TBL95_35_GB 0618   Part-No. 00158612-GB

 

 

- 9 - 

5.5 Stabilisation of the output voltage for fluctuations in the line voltage 

By means of the integrated voltage stabilisation function, the output voltage and hence the speed of the connected 
motor remain essentially constant throughout fluctuations in the line voltage. 
The unit supplies the maximum output voltage (approximately the line voltage) for line voltages above the signal input 
which are less than the specified output voltage. The output voltage of the unit cannot rise above the line voltage for 
system reasons. 
 

Characteristic for ohmic loads 
By comparison, units without integrated voltage stabilisation for line v and -10 %. 
 

0

50

100

150

200

250

1

2

3

4

5

6

7

8

9

10

Setpoint signal Uv [V]

On-load voltage U_load [V

]

Ideal curve

Nominal voltage
+10% stab.
Nominal voltage -10%
stab.

Nominal voltage
+10%

Nominal voltage -10%

 

 (BA_PAE.xls/ds) 
 

Stabilisation of the output voltage can be switched on and off again with the jumper J3. 
 
Jumper J3 “up”:  

without stabilisation (

factory setting

Jumper J3 “down”:  

with stabilisation 

 

The stabilisation must be switched off when loading the voltage supply for external 
units (+15 V / +24 V) (section 5.3 Voltage supply) or for running from a mains 
transformer. 

 

It is not meaningful to operate with stabilisation for control (0-10 V) by a control unit 
(e.g. when used as a “follower controller”). 

 

The function “stabilisation” serves to specify a voltage as constant as possible, e.g. 
over a potentiometer. 

5.6 Output voltage 0-10 V 

The output voltage 0-10 V, (terminal “A” / “GND”) is almost proportional to the regulated motor voltage. This can be used 
for example, if a speed controller, type PAE / PASTE, or valve positioning motor, is installed. The output is set to a fixed 
voltage of 10 V at the factory for supply to a potentiometer. A switchover to 0-10 V proportional to the motor voltage is 
possible by means of the connector J10 in the terminal compartment. 
 
J10 „up“ position „A“ (

standard setting

)  = fixed voltage to terminal „A“ (+10 V for potentiometer) 

J10 „down“ position „B“ 

= voltage to terminal „A“ 0-10 V proportional to the controlled motor 

 
Max. load output voltage 0-10V 
- PAE10E-M and PSE-14: I

max

 10 mA  

- PSE-6V: I

max

 1 mA  

6. Faults and their rectification 

6.1 Line faults 

The controller switches off in the event of a line fault, e.g. fuse or network failures. The controller switches on again 
automatically following restoration of the voltage. 

Содержание PAE10E-M

Страница 1: ...V Part No 303585 Electronic speed controller for variable voltage 1 motors Manufacturer ZIEHL ABEGG AG Heinz Ziehl Stra e D 74653 K nzelsau Phone 49 0 7940 16 0 Fax 49 0 7940 16 200 Internet http www...

Страница 2: ...commissioning 6 4 5 Systems with current operated circuit breaker 6 4 6 Potential of control voltage connections 6 4 7 Interference Emissions Cable installation 7 4 8 Electrical installation 7 5 Basic...

Страница 3: ...ration If used in intensive animal environments any malfunctions in the air supply must be detected as soon as possible to prevent the development of a life threatening situation for the animals The d...

Страница 4: ...nsation Interference emission EN 61000 6 3 Harmonics current EN 61000 3 2 Interference immunity EN 61000 6 2 The units comply with EN 61000 3 2 for a professional unit Up to a maximum current of 4 amp...

Страница 5: ...x speed potentiometer speed limiter and cos adjustment Setting range from 100 down to setting n min This adjustment has to be made with full load condition i e when radial fans are used all dampers mu...

Страница 6: ...to the installation of several devices next to each other illustration When installing several devices on top of each other the danger of reciprocal heating exists This layout is only then permissible...

Страница 7: ...be longer than 30 m Screened control cables must be used when the cable length is longer than 20 m When using a screened cable the screen must be connected to the protective conductor at one end i e o...

Страница 8: ...nal circuit resistor 499 0 25 W between the terminals E and GND 5 3 Voltage supply for external equipment There is an integrated power supply for external equipment A selection between 15 V and 24 V i...

Страница 9: ...stabilisation must be switched off when loading the voltage supply for external units 15 V 24 V section 5 3 Voltage supply or for running from a mains transformer It is not meaningful to operate with...

Страница 10: ...upted KT00008G 15 07 2004 PE L N Netz oder geregelte Spannung line or controlled voltage Reseau ou tension variable Nat eller reglerad spanning 1 60V 250V 50 60Hz 1 2 4 6 12 11 24 23 Option ZB ZK 2S K...

Страница 11: ...s PAE10E M PSE 6 14V Date 0618 R TBL95_35_GB 0618 Part No 00158612 GB 11 Switch off the main supply before removing the cover Vor ffnen des Deckels Ger t spannungsfrei schalten 7 2 Dimension sheet PAE...

Отзывы: