- 8 - 

5. Basic settings / connections possible 

5.1 Adjustment of the speed by an external potentiometer 

The external potentiometer (10 k

) is connected to the terminals “A” and “GND”. Depending on the setting, a voltage of 

0-10 V is returned to the input terminal “E” by the potentiometer pick-off (for 10 V max. output voltage). The connector J 
10 (in the terminal compartment) must be inserted in the “up” position, i.e. in position “A”, to do this,(see terminal 
connection plan). 
 
J10 “up” position “A” (

factory setting

)   = fixed voltage at terminal “A” (+ 10 V for potentiometer) 

J10 “down” position “B”  

= voltage at terminal “A” = 0-10 V proportional to the motor voltage. 

 

5.2 Adjustment of the speed by an external signal 

The external signal for selecting the speed is connected to terminals “E” and “GND” (see terminal connection plan). The 
speed of the motors connected is controlled as a direct variance of the signal at the input terminals (for max. 10 V output 
voltage). 
 
Subsequent change from 0-10 V to 0-20 mA for the input signal: 
Control by a 0-20 mA signal is possible by an external circuit resistor (499 

 / 0.25 W) between the terminals “E” and 

“GND”. 
 

5.3 Voltage supply for external equipment 

There is an integrated power supply for external equipment. A selection b15 V and +24 V is possible by mean 
of jumper J15. 
 
Reference point for voltage = next GND-terminal, max. 20 mA 
 
J15 up position “A“ +15 V 

 

 

 

 

output voltage ± 5 %. 

J15 down position “B“ +24 V (

standard setting

 

output voltage ± 20 %. 

 
 
 

The voltage stabilisation function for the motor voltage is limited for a load on this voltage 
supply. Thus this must be interrupted in the terminal compartment by connector J 3 (

)

Section 

5.5 Stabilisation of output voltage) 
 
 
 

5.4 Running several fans from one controller 

Several fans can be connected to the controller. The maximum total current of all motors (maximum rated current for 
electronic control of the voltage) must not exceed the current rating of the controller. 

 

 
If the maximum control current for the electronic voltage control is not known, then allowance for an increase up to 20 % 
in the motor nominal current must be made.  
 
For the control of motors made by other manufacturers (not Ziehl-Abegg), the control characteristics and the maximum 
current for electronic regulation of the voltage should be enquired from the manufacturer. 
 

 

It is recommended that a separate motor surveillance unit (e.g. S-ET10) is foreseen for each fan. 

Содержание PAE10E-M

Страница 1: ...V Part No 303585 Electronic speed controller for variable voltage 1 motors Manufacturer ZIEHL ABEGG AG Heinz Ziehl Stra e D 74653 K nzelsau Phone 49 0 7940 16 0 Fax 49 0 7940 16 200 Internet http www...

Страница 2: ...commissioning 6 4 5 Systems with current operated circuit breaker 6 4 6 Potential of control voltage connections 6 4 7 Interference Emissions Cable installation 7 4 8 Electrical installation 7 5 Basic...

Страница 3: ...ration If used in intensive animal environments any malfunctions in the air supply must be detected as soon as possible to prevent the development of a life threatening situation for the animals The d...

Страница 4: ...nsation Interference emission EN 61000 6 3 Harmonics current EN 61000 3 2 Interference immunity EN 61000 6 2 The units comply with EN 61000 3 2 for a professional unit Up to a maximum current of 4 amp...

Страница 5: ...x speed potentiometer speed limiter and cos adjustment Setting range from 100 down to setting n min This adjustment has to be made with full load condition i e when radial fans are used all dampers mu...

Страница 6: ...to the installation of several devices next to each other illustration When installing several devices on top of each other the danger of reciprocal heating exists This layout is only then permissible...

Страница 7: ...be longer than 30 m Screened control cables must be used when the cable length is longer than 20 m When using a screened cable the screen must be connected to the protective conductor at one end i e o...

Страница 8: ...nal circuit resistor 499 0 25 W between the terminals E and GND 5 3 Voltage supply for external equipment There is an integrated power supply for external equipment A selection between 15 V and 24 V i...

Страница 9: ...stabilisation must be switched off when loading the voltage supply for external units 15 V 24 V section 5 3 Voltage supply or for running from a mains transformer It is not meaningful to operate with...

Страница 10: ...upted KT00008G 15 07 2004 PE L N Netz oder geregelte Spannung line or controlled voltage Reseau ou tension variable Nat eller reglerad spanning 1 60V 250V 50 60Hz 1 2 4 6 12 11 24 23 Option ZB ZK 2S K...

Страница 11: ...s PAE10E M PSE 6 14V Date 0618 R TBL95_35_GB 0618 Part No 00158612 GB 11 Switch off the main supply before removing the cover Vor ffnen des Deckels Ger t spannungsfrei schalten 7 2 Dimension sheet PAE...

Отзывы: