9.10.2.11
Setting Max. Speed ON / OFF function
|
11D
|
The value for
“
Max Speed
”
adjusted in menu
“
Settings
”
, is activated over a digital input. I.e. the unit
works independently of the controller function
fi
rm with this value.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
15.05.2009
v_11d_max_drehzahl.vsd
Controller
24V
D1 D1
= 80 %
1
0
- - - - -
1
0
= 0 .. 100 %
1
1
Setting
“
Max. Speed
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Max. Speed
”
active at closed contact
•
“
D1 Inverting
”
=
“
ON
”
:
“
Max. Speed
”
active at opened contact
9.10.2.12
Motorheating ON / OFF, Function
|
12D
|
In order to avoid a sticking or a freezing of standing fans in cold environment, the
“
motor heating
system
”
can be switched on.
11.05.2007
v_12d_motorheizung.vsd
Controller
24V
D1 D1
- - - - -
TB/TP
1
1
Setting
“
dc brake level
”
The motor heating can be activated over a digi-
tal input.
E.g. over a freeze protection thermostats at
digital input
“
Digital In 1
”
(depending on device
type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Motor heating active at closed contact, if no
modulation of the controller is present (for
“
D1
”
= Inverting
“
OFF
”
)
The motor heating function corresponds to the braking function in which a direct current puts the
motor into standstill. The height of the
“
brake level
”
is set in
“
Motor Setup
”
.
Setting range: 1 - 50 %
Factory setting: 5 %
A current is impressed here, which does not permit any rotation of the fans. The value required to
prevent any freezing depends on the ambient conditions and the connected motor
’
s technical data.
The setting effected is to be checked under real conditions. The higher the setting, the greater the
heating output generated in the motor (heat dissipation). The motor heating or stationary heating can
only become active, where there is no given modulation as a result of regulation.
To prevent any overheating, motor protection in the form of thermal protection installed in the motor is
required (
motor protection). The heating function is switched off when the motor protection function
of the regulating unit responds.
Motorheating
The activated motor heating is indicated alternating with the actual value
Operating Instructions
Fcontrol
–
model series FXET4/6/10AMQ
Programming
L-BAL-E079-GB 1706 Index 008
Part.-No.
55/87