AM-MODBUS-WB

Part.-No. 349077

Bluetooth communication module for frequency inverters from the 
Basic series and fans from the ECblue (D+G), AMblue and PMblue 
series

Quick Start Guide

Attention, electrostatically sensitive components!

Note chapter mounting the module.

L-BAL-E281-GB 2021/36 Index 004

Part.-No. 

english

Содержание AM-MODBUS-WB

Страница 1: ...module for frequency inverters from the Basic series and fans from the ECblue D G AMblue and PMblue series Quick Start Guide Attention electrostatically sensitive components Note chapter mounting the module L BAL E281 GB 2021 36 Index 004 Part No english ...

Страница 2: ... MODBUS WB 10 3 3 Transport 11 3 4 Storage 11 3 5 Disposal recycling 11 4 Mounting the module 11 5 Installation 13 5 1 Safety precautions 13 5 2 Connection terminal type A G 247NW for service 13 5 3 RS 485 interface for MODBUS 14 5 3 1 Automatic addressing 15 6 Operating by terminal 17 6 1 Menu operation 17 6 2 Menu structure 18 7 Bluetooth for wireless communication 19 7 1 AM MODBUS WB with Bluet...

Страница 3: ...9 Enclosure 27 9 1 Connection diagram 27 9 2 Manufacturer reference 28 9 3 Service information 28 Quick Start Guide AM MODBUS WB L BAL E281 GB 2021 36 Index 004 Part No 3 28 ...

Страница 4: ...y use installation and quick start up and is only valid in connection with the assembly instructions or operating instructions of the device in which this module is installed The remarks concerning safety installation and connection described there must be followed 1 2 Exclusion of liability Concurrence between the contents of these operating instructions and the described hardware and software in...

Страница 5: ... of radio spectrum EN 300 328 V2 1 1 2016 11 The CE symbol confirms compliance with the directive The final product in which the module and the fan or frequency inverter is installed must meet the requirements of 2014 53 EU The modules may be used in the following countries Austria Belgium Cyprus Czech Republic Denmark Estonia Finland France Ger many Greece Hungary Ireland Italy Latvia Lithuania Lux...

Страница 6: ...lass B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee tha...

Страница 7: ...ense IC 216Q 1740 Manufacturers of mobile fixed or portable devices incorporating this module are advised to clarify any regulatory questions and ensure compliance for SAR and or RF exposure limits Users can obtain Canadian information on RF exposure and compliance from www ic gc ca This device has been designed to operate with the antennas listed in the Table above having a maximum gain of 0 9 dBi...

Страница 8: ... d un autre émetteur ni être utilisée conjointement avec une autre antenne ou un autre émetteur En raison de la taille du produit l identifiant IC est fourni dans le manuel d installation Labeling Requirements The Original Equipment Manufacturer OEM must ensure that IC labelling requirements are met This includes a clearly visible label on the outside of the OEM enclosure specifying the appropriate...

Страница 9: ...nd PE and the mains connection Waiting period at least 3 minutes Opening the device in which the module is to be installed fan inverter is only allowed when the mains power is switched off and after waiting at least three minutes Through use of capacitors danger of death exists even after switching off the device through directly touching the energized parts or due to parts that have become energi...

Страница 10: ...p can be downloaded from Google Play Store or iTunes RS 485 interface The RS 485 interface for MODBUS RTU allows access to the MODBUS registers and also enables menu guided programming with the A G 247NW manual terminal Devices with integrated auxiliary module AM MODBUS WB offer the following functions The ECblue fan and the frequency inverter can be communicated with via the module To program des...

Страница 11: ...pecialist company with the waste disposal 4 Mounting the module Danger due to electric current Always read the safety instructions chapter before mounting The terminating device fan converter in which the module is to be installed must be disconnected from the line voltage for at least 3 minutes before opening Attention electrostatic sensitive devices Damage to electronic components by electrostat...

Страница 12: ... torque of connection terminals MA 0 24 Nm When an AM MODBUS W WB module is installed in a fan or converter from ZIEHL ABEGG the enclosed label must be stuck to the housing of the terminating device FCC IC label for AM MODBUS W FCC IC label for AM MODBUS WB Example for mounting the add on module Example Sticking the FCC IC label AM MODBUS W onto a fan housing Quick Start Guide AM MODBUS WB Mountin...

Страница 13: ... an external terminal can be connected This can be e g necessary to adapt the pre setting during start up The connection is made at the terminals A D B D and GND E g by a 4 wire telephone cable type J Y St Y 2x2x0 6 or similar maximum cable length approx 250 m AM MODBUS B D GND A D B D fout GND GND A D A G 247NW 3 3 V IRDA RXD IRDA TXD IRDA SD A D B D GND 5 V 13 12 2018 v_modbus_link_terminal vsd ...

Страница 14: ...wing chapter no further cable cores of the data line may be used Pay attention to sufficient distance from powerlines and motor wires min 20 cm A maximum of 64 participants can be directly connected to one another and a further 63 participants via a repeater To support automatic addressing the repeater type Z G 1NE is available Example for MODBUS connection MODBUS 26 02 2007 v_modbus_verbindung vsd...

Страница 15: ...bits 1 Handshake none Information Addressing is performed depending on version by display an external terminal or a PC with the appropriate software automatic addressing following chapter The MODBUS register description and the information sheet Network structure of MODBUS can be requested from our Support Department V STE for control systems ventilation 5 3 1 Automatic addressing Automatic addres...

Страница 16: ...ng signal Maximum number of members in automatic addressing With hand held terminal type A G 247 and control unit NETcon type CXG 327ANE max 63 members With control module UNIcon MODBUS Master max 32 members On the first user that is connected directly to a terminal MODBUS Master or PC GND and ID1 or ID2 must be bridged This is recognised as a result and occupied by address 1 For the following user...

Страница 17: ...lue depending on device type Speed rpm Frequency Hz Modulation By pushing the P key one reaches the menu item Start Return to the menu group Start using arrow key Esc P One moves up and down within the menu group using the arrow keys Display for english menu language GB Quick Start Guide AM MODBUS WB Operating by terminal L BAL E281 GB 2021 36 Index 004 Part No 17 28 ...

Страница 18: ... menu and one area for installation service The service area can be protected against unauthorized access by using a PIN To make adjustments press the P key after selecting the menu item If the previously set value starts to flash it can be adjusted with the keys and then saved with the P key To exit the menu without making any changes use the Esc key i e the originally set values remain Informatio...

Страница 19: ...munication but it is still read and displayed during a Bluetooth scan This means that you can also identify the device via its MODBUS address if one has been assigned Therefore it is a good idea to assign a MODBUS address even if the MODBUS network is not in use You can change the MODBUS address via the app in the device IO Setup see the Bus Address parameter Then apply the same procedure to the n...

Страница 20: ...shing the Bluetooth connection Proceed as follows Depending on your device download and install the ZAset mobile app from Google Play Store or Apple App Store Switch on the line voltage to the fan frequency converter in compliance with the safety instructions Activate the Bluetooth connection on the mobile device smartphone Additionally allow location determination in Android Start the app Icon of...

Страница 21: ...Bluetooth LE data connection ZAset checks whether Bluetooth is activated on your smartphone and prompts you to activate it if necessary Main page Choose Bluetooth Quick Start Guide AM MODBUS WB Bluetooth for wireless communication L BAL E281 GB 2021 36 Index 004 Part No 21 28 ...

Страница 22: ...ist Scanning process 3 Connections made Briefly tap the desired device in the list to select it ZAset mobile then immediately establishes a data connection with this device Quick Start Guide AM MODBUS WB Bluetooth for wireless communication L BAL E281 GB 2021 36 Index 004 Part No 22 28 ...

Страница 23: ...ry setting acess code and confirm with OK Set a new PIN to prevent unauthorised access Setting PIN 9999 Change PIN Quick Start Guide AM MODBUS WB Bluetooth for wireless communication L BAL E281 GB 2021 36 Index 004 Part No 23 28 ...

Страница 24: ...name of your choice alias Change alias Example 01_ECblue Touch the device s button to establish a connection Quick Start Guide AM MODBUS WB Bluetooth for wireless communication L BAL E281 GB 2021 36 Index 004 Part No 24 28 ...

Страница 25: ... Start List my devices Settings 2 Info BLE vesion MODBUS address identification etc 3 Speed control via slider or variable 4 Error history 5 Analysis 6 back to Dashboard 7 Parameter 8 Statistic 9 Disconnecting the Bluetooth connection Quick Start Guide AM MODBUS WB Bluetooth for wireless communication L BAL E281 GB 2021 36 Index 004 Part No 25 28 ...

Страница 26: ...mains Flashes once per second when connected to the mobile device via Bluetooth 3 Flashes every 2 seconds when connected to the mains Flashes once per second when connected to the mobile device via Bluetooth Information The LEDs are not visible when the lid of the ECblue or frequency inverter is closed Quick Start Guide AM MODBUS WB Diagnostic L BAL E281 GB 2021 36 Index 004 Part No 26 28 ...

Страница 27: ... when used in ECblue see Assembly Instructions n f AM MODBUS n f x 60 2 AM MODBUS W n f x 60 Information The full connection diagram for the terminating device is a combination of the connection diagram of the module plus the connection diagram of the device in which the module is installed see appropriate Operating Instructions Quick Start Guide AM MODBUS WB Enclosure L BAL E281 GB 2021 36 Index ...

Страница 28: ...ehl abegg de http www ziehl abegg com 9 3 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outside of Ger many see www ziehl abegg...