E1 Analog In (factory setting 0 - 10 V)
12.03.2012
v_pde_jumper_e1_dip_s1_mode.vsd
A
E1
GND
0 - 10 V
10 k
0 - 10 V
E1
1.01
ON
OFF
4
3
2
1
S1
24V
E1
GND
YE
DSG..
WH
BN
0 -10 V
24V
E1
GND
3
MAL1/10
2
1
0 -10 V
0 - 10 V
E1
4.01
ON
OFF
4
3
2
1
S1
4 - 20 mA
(0 - 20 mA)
E1
7.2 Select operation mode
Simple installation is possible through the use of modes of operation.
Mode
Signal or Sensor
(input)
Function
1.01
Signal 0 - 10 V
Speed controller, Two step operation
4.01
Sensor DSG.. (E1)
Pressure control for ventilation systems (Factory setting)
Sensor MAL.. (E1)
Air velocity control e.g. clean room Sensor (Factory setting)
Operating Instructions
Acontrol
PDE-6 / PDE-10
Base setup
L-BAL-E048-GB 1921 Index 005
Part.-No.
17/29