5.10 Potential at control voltage connections

The connections for the control voltage (< 30 V) relate to the common GND potential 
(exception: relay contacts are potential-free). There is a potential isolation between the 
connections for the control voltage and the PE conductor. It must be ensured that the 
maximum external voltage at the connections for the control voltage cannot exceed 30 V 
(between the 

GND

 and 

PE

 conductor terminals). A connection to the PE conductor 

potential can be made if required; 

t a bridge between the 

GND

 terminal and the 

PE

connection (terminal for shield).

6 Operating and display elements 

18.11.2008

v_pde_bedien_anzeige.VSD

V

mA

E1

 

 

%

0

 

100

 

n-min

 

%

0

 

100

 

 

R47

set

ON

OFF

 

 

 

 

 

 

4

3

2

1

S1

V13

R

4

8

 

 

 

n-max / 

P-band

R

4

9

 

%

 

5

30

Operating Instructions 

Acontrol

 PDE-6 / PDE-10 Operating and display elements

L-BAL-E048-GB 1921 Index 005

Part.-No. 

15/29

Содержание Acontrol PDE-6

Страница 1: ...trol PDE 6 PDE 10 Controller unit PI controller and speed controller for variable voltage 1 fans Operating Instructions Software version D1475A from Version 01 L BAL E048 GB 1921 Index 005 Part No eng...

Страница 2: ...2 9 Employment of external personnel 9 3 Product overview 9 3 1 Operational area 9 3 2 Maintenance 9 3 3 Transport 9 3 4 Storage 9 3 5 Disposal recycling 9 4 Mounting 10 4 1 General notes 10 4 2 Minim...

Страница 3: ...inimum speed cut off DIP 2 18 7 5 1 For mode Speed controller 1 01 18 7 5 2 For operation as P Controller 4 01 19 8 Start up 19 8 1 Prerequisites for commissioning 19 9 Setting for operation 20 9 1 Sp...

Страница 4: ...ing elevated ambient temperatures 25 11 2 Connection diagram 26 11 3 Dimensions mm 28 11 4 Manufacturer reference 29 11 5 Service information 29 Operating Instructions Acontrol PDE 6 PDE 10 L BAL E048...

Страница 5: ...ting instructions at any time Keep the operating instructions for continued use They must be passed on to all successive owners users and nal customers 1 2 Target group The operating instructions addr...

Страница 6: ...arising from non intended use 2 2 Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows Attention General haz...

Страница 7: ...ulations Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person This also applies to personnel undergoing general...

Страница 8: ...e made on the device All planned modi cations must be authorized by the manufacturer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG These parts were...

Страница 9: ...The controller described is used for continuous speed adjustment on variable voltage 1 motors used to drive ventilators or pumps 3 2 Maintenance The device must be checked for soiling and if necessary...

Страница 10: ...alled in a location where it will not be disturbed but at the same time can be easily accessed Depending on the housing model use supplied stoppers for cable inlets cut off necessary cable inlets resp...

Страница 11: ...d in electricity under the supervision of an electrician in accordance with electrical engineering regulations The 5 electrical safety rules must be observed It is forbidden to carry out work on elect...

Страница 12: ...r than 20 m When using a shielded cable connect the shielding to one side only i e only to the control unit with the protective ground keep cable short and with as little inductance as possible 5 2 3...

Страница 13: ...ise may be dominant in the lower speed range due to the occurrence of resonance For systems where noise is critical we recommend using our Fcontrol series frequency converters with integrated sinusoid...

Страница 14: ...ort circuit 24 V GND the external power supply is shut down multi fuse The device performs a Reset and continues operation It is not permissible to connect voltage outputs of several devices to each o...

Страница 15: ...at the connections for the control voltage cannot exceed 30 V between the GND and PE conductor terminals A connection to the PE conductor potential can be made if required t a bridge between the GND t...

Страница 16: ...ction Speed controller PI Control ler It is possible to use the device as a Speed controller or as a PI controller Selection of the function must rst be made by setting the internal jumper E1 and dips...

Страница 17: ...mA E1 7 2 Select operation mode Simple installation is possible through the use of modes of operation Mode Signal or Sensor input Function 1 01 Signal 0 10 V Speed controller Two step operation 4 01 S...

Страница 18: ...compared with the nominal value that has been set The output voltage and hence the rotational speed of the connected motor automatically change as a function of the parameter settings The desired func...

Страница 19: ...s place I e always a minimum ventilation is ensured fan does not go under setting n min With minimum air switch off DIP 2 ON For PI controller only in special applications of importance When the setpo...

Страница 20: ...er set without function 0 100 n min R 4 8 28 08 2008 v_nmin_pke VSD n min Setting of output voltage at the device 0 100 For setting via external signal Minimum output voltage basic speed Setting range...

Страница 21: ...wo variable output voltages two steps Switchover between two steps via external potential free contact possible Step 1 low speed When there is no input signal connected to the input terminal E1 then t...

Страница 22: ...er n max 28 08 2008 v_nmax_pband_pke VSD n max P band R 4 9 5 30 n max Pband Maximal output voltage speed limiter Setting range 100 n min 9 2 2 Example Pressure control for ventilation systems Pressur...

Страница 23: ...ult Operation as controller 1 01 only for selection 2 10 V or 4 20 mA signal For interruption or short circuit at E1 With reaching minimum or maximum signal values after approx 1 minute de pending on...

Страница 24: ...k of 10 fuses 349026 25 W 0 8 1 At rated 230 V values for different speci cations on request 2 Max supply side line fuse according to DIN EN 60204 1 classi cation VDE0113 chapter 1 3 Semiconductor fus...

Страница 25: ...t Housing protection IP54 11 1 1 Performance reduction during elevated ambient temperatures The maximum permissible temperature for the rated current at rated voltage is speci ed as rated temperature...

Страница 26: ...mA 4 1 E1 V mA GND 24 V M 1 PE U1 U2 1 Motor ohne Thermostatschalter without thermostats 2 1 Line 1 230 V 50 60 Hz 2 1 motor without thermostats 3 Output 10 V Imax 10 mA 4 Input 0 10 V 2 10 V 0 20 mA...

Страница 27: ...lerad spanning 1 60 250 V 50 60 Hz N L1 PE max 25 A 1 5 2 4 6 S ET10E I ZB M 1 U1 U2 PE TB q TB Option ZB ZK 2S Kontaktbelastung der Hilfskontakte Contact rating of auxiliary contacts Pouvoir de coupu...

Страница 28: ...11 3 Dimensions mm PDE 6 PDE 10 Operating Instructions Acontrol PDE 6 PDE 10 Enclosure L BAL E048 GB 1921 Index 005 Part No 28 29...

Страница 29: ...4 info ziehl abegg de http www ziehl abegg de 11 5 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for contro...

Отзывы: