INSTALLATION –
GENERAL NOTES
Before beginning the installation of your heater, you should note the following precautions:
-
WARNING: THE APPLIANCE AND FLUE-SYSTEM SHALL BE INSTALLED IN
ACCORDANCE WITH AS/NZS 2918 AND THE APPROPRIATE REQUIREMENTS OF
THE RELEVANT BUILDING CODE OR CODES.
-
CAUTION: CRACKED AND BROKEN COMPONENTS, e.g. GLASS PANELS OR
CERAMIC TILES, MAY RENDER THE INSTALLATION UNSAFE.
-
It is strongly recommended that a certified/qualified installer perform the installation.
-
You may need to get council approval prior to installation.
-
You should also check with your insurer for any requirements they may have.
-
Ensure all visible joints are sealed.
HEARTH REQUIREMENTS
If your pellet heater is to be installed on carpet, timber or any other combustible material, you
must place a hearth (also known as a floor protector) underneath the heater. Please observe
the following:
-
The hearth must consist of at least 6 mm of non-combustible material for a freestanding
heaters or 75 mm of non-combustible material for an inbuilt heater.
-
It is not recommended that you make your own hearth
-
The hearth and heater assembly must be placed on a firm and level surface.
FLUE INSTALLATION
The correct flue system is critical to the performance of your pellet heater. It must either be
tested with the heater or be a default flue kit.
CAUTION: MIXING OF APPLIANCE OR FLUE-SYSTEM COMPONENTS FROM DIFFERENT
SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY
RESULT IN HAZARDOUS CONDITIONS. WHERE SUCH ACTION IS CONSIDERED, THE
MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE.
FLUE HEIGHT REQUIREMENTS
Your flue must extend the required height above your roof to promote sufficient draught. If your
flue is not high enough, the heater will not “draw” properly. If this is the case, please contact
your retailer.
The minimum height of the active flue must be 4.6m in length measured from the hearth plate to
the flue termination point. The flue must extend at least 1m out of the roof. The flue must clear
any ridge or obstruction within a 3m radius by a minimum of 1m.