7.  POWER TOOLS AND AMALL 

APPLIANCES 

This test would also apply to other similar equipment that has 
a  line  cord.  For  double  insulated  power  tools,  the 
megohmmeter  lead  shown  connected  to  the  housing  would 
be connected to some metal part lf the tool(e..g chuck,blade). 
Note:The  switch  of  the  device  must  be  in  the  “ON”position 
and the main power should be disconnected. 
 

MOTORS 

AC-Disconnect the motor from the line by disconnecting the 
wires at    the motor terminals or by opening the main switch. 
If the main switch is    used and the motor also has a starter 
then the starter must be held, by some means, in the “ON” 
position.  In  the  latter  case,  the  measured  resistance  will 
include  the  resistance  of  the  motor,  wire  and  all  other 
components  between  the  motor  and  the  main  switch.  If  a 
weakness  is  in  dicated,  the  motor  and  other  components 
should be checked  individually. If the motor is  disconnected 
at  the  motor  terminals,  connect  one  megohmmeter  lead  to 
the grounded motor housing and the other lead to One of the 
motor leads. DC-Disconnect the motor from the line. To test 
the  brush  rigging,field  coils  and  armature  connect  one 
megohmmeter  lead to  the  grounded  motor  housing  and  the 
other lead to the brush on the commutator. If the resistance 
measurement indicates a weakness,raise the brushes off the 
commutator and separately test the armature, field coils and 

brush rigging by connecting one megohmmeter lead to each 
of  them  individually,  leaving  the  other  connected  to  the 
grounded  motor  housing.  The  above  also  applies  to  DC 
Gemerators.   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание ZI-9100

Страница 1: ...maged Use extreme caution when working around bare conductors or bus bars Accidental contact with the conductor could result in electric shock Use the meter only as specified in this manual otherwise the protection provided by the meter may be impaired Read the operating instructions before use and follow all safety Information Caution when working with voltages above 60V DC or 30V AC RMS Such vol...

Страница 2: ...riodically wipe the case with a dry cloth Do not use abrasives or solvents on this instruments Display Large LCD with dual display Measurement Range 200Ω 200kΩ 200MΩ 250V 200MΩ 500V 2000MΩ 1000V 750V ACV 1000V DCV Sampling Rate 2 5 times per second Zero Adjustment Automatic adjustment Over Range Indicator Number 1 of highest digit is displayed Low Battery Indication The is displayed when the batte...

Страница 3: ...40Ω 4 5V 250Vrms Short circuit current 200mA DC Voltage Range Resolution Accuracy Input Impedance Overload Protection 1000V 1V 0 8 3 10MΩ 1000Vrms AC Voltage 40Hz 400Hz Range Resolution Accuracy Input Impedance Overload Protection 750V 1V 1 2 10 10MΩ 750Vrms Meg OHMS Range Resolution Accuracy Terminal Voltage 200MΩ 250V 0 1MΩ 3 5 250V 10 0 200MΩ 500V 0 1MΩ 500V 10 0 0 1000MΩ 1000V 1MΩ 1000V 10 0 1...

Страница 4: ... of 6 pcs new batteries type 1 5V size AA is Required b Place back the battery cover and four the screws 3 3 Test leads check Set the range select switch to the 200Ω range With the tip and alligator clip of the test leads connected The indicator should read 00 0Ω When the leads are not connected the display will read infinity indicated by 1 This will ensure that test lead are under working conditi...

Страница 5: ...V and then proceed as indicated in a above for 500V testing The above note also applies to testing at 1000V In addition the following applies Note Make sure that the circuit under does not include components Which will be damaged by the 1000V applied Many normal components of an installation are likely to be damaged if tested at 1000V Examples are power factor correction capacitors low voltage min...

Страница 6: ...l include the resistance of the motor wire and all other components between the motor and the main switch If a weakness is in dicated the motor and other components should be checked individually If the motor is disconnected at the motor terminals connect one megohmmeter lead to the grounded motor housing and the other lead to One of the motor leads DC Disconnect the motor from the line To test th...

Страница 7: ...e from other equipment Check each conductor to ground and or lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in turn Check insulation resistance between conductors by connecting megohmmeter leads to conductors in pairs ...

Отзывы: