ALARM CIRCUIT MODULE INSTRUCTION MANUAL 

Wiring recommendations 

The SCM-ACM circuits are rated for 500mA each. The table shows the maximum wire run in metres for different wire 
gauges and alarm loads. 

 

 

 

 

Front Unit LED Indications 

LED Indication

 

Description

 

LED Indication

 

Description

 

 

Flashing yellow when a wire break in 

the circuit is detected. 

 

Flashing green when the module is 

programmed as an unsynchronized bell 

output. 

Solid green when the module is programmed 

to provide a 24v auxiliary output. 

 

Flashing yellow when a short in the 

circuit is detected. 

 

Pulses to show communication between the 

module and the motherboard. 

 

Specifications 

Specification 

SCM-ACM 

Design Standard 

EN54-2 

Approval 

LPCB (Pending) 

Circuit Voltage 

29VDC Nominal (19V – 29V) 

Circuit Type 

Regulated 24V DC. Power limited & Supervised. 

Maximum Alarm Circuit Current 

2 x 500mA 

Maximum Aux 24V Current 

2 x 400mA 

Maximum RMS current for a single sounder device 

350mA 

Maximum Line Impedance 

3.6Ω total (1.8Ω per core) 

Wiring Class 

2 x Class B [Power limited & Supervised] 

End of Line Resistor 

4K7Ω 

Recommended cable sizes 

18 AWG to 14 AWG (0.8mm

2

 to 2.5mm

2

Special Applications 

24V auxiliary voltage output 

Operating Temperature 

-5°C (23°F) to 40°C (104°F) 

Max Humidity 

93% Non-Condensing 

Size (mm) (HxWxD) 

105mm x 57mm x 47mm 

Weight 

0.15KG 

 

Compatible Warning Devices 

 

 

Wire Gauge 

125mA Load 

250mA Load 

500mA Load 

18 AWG 

765 m 

510 m 

340 m 

16 AWG 

1530 m 

1020 m 

680 m 

14 AWG 

1869 m 

1246 m 

831 m 

Alarm Circuit Devices 
ZXT 

Xtratone Conventional Wall Sounder 

ZXTB  Xtratone Conventional Combined Wall Sounder Beacon 
ZRP 

Conventional Raptor Sounder 

ZRPB  Conventional Raptor Sounder Beacon 

RECOMMENDED CABLE: 

Cable should be BS approved FPL, 
FPLR, FPLP or equivalent.  

Содержание SMART CONNECT SCM-ACM

Страница 1: ...DOC GLT 294 7 12 ISS 001 DATE 10 02 2021 ALARM CIRCUIT MODULE INSTRUCTION MANUAL SCM ACM ...

Страница 2: ...the DIN rail to mount the module Also ensure that the DIN clip underneath the module is in the open position 2 Place the module onto the DIN rail hooking the metal earth clip underneath onto the rail first 3 Once the earth clip is hooked push the bottom of the module onto the rail so that the module sits flat 4 Push the plastic DIN clip located at the bottom of the module upwards to lock and secur...

Страница 3: ...odule and after the last module on each rail Before Powering the Panel On 1 To prevent the risk of a spark do not connect the batteries Only connect the batteries after powering on the system from its main AC supply 2 Check that all external field wiring is clear from any open shorts and ground faults 3 Check that all the modules have been installed properly with correct connections and placement ...

Страница 4: ...correctly inserted Note that the panel will need at least one module fitted to run The panel has detected a new module added to a port that was previously empty This is the usual message seen the first time a panel is configured The panel has detected a different type of module fitted to a port that was previously occupied The panel has detected a module fitted to a port that is the same type but ...

Страница 5: ...ntermittently sounding the Fault buzzer and displaying battery removed message on the screen 4 Connect the batteries ensuring that the polarity is correct Red wire ve Black wire ve Acknowledge the Fault event via the display screen and reset the panel to clear the battery fault 5 The panel should now remain in the normal condition and you can configure the panel as normal Field Wiring Typical Wiri...

Страница 6: ...n ACM is configured as a bell output the 24V On LED on the front of the module will be flashing ON OFF NOTE This wiring diagram demonstrates the option to program one or more SCM ACM outputs to become a regulated constant 24VDC output NOTE When an alarm circuit is configured as a 24v aux output the 24V On LED on the front of the module will be ON ...

Страница 7: ...it Type Regulated 24V DC Power limited Supervised Maximum Alarm Circuit Current 2 x 500mA Maximum Aux 24V Current 2 x 400mA Maximum RMS current for a single sounder device 350mA Maximum Line Impedance 3 6Ω total 1 8Ω per core Wiring Class 2 x Class B Power limited Supervised End of Line Resistor 4K7Ω Recommended cable sizes 18 AWG to 14 AWG 0 8mm2 to 2 5mm2 Special Applications 24V auxiliary volta...

Страница 8: ...TION MANUAL Maximum Warning Devices per Circuit Some of the above warning devices have selectable settings for sound and beacon output Please refer to the device manuals to calculate the maximum number allowed on each alarm circuit ...

Отзывы: