5
ALARM CIRCUIT MODULE INSTRUCTION MANUAL
1.
Check that the module configuration is as expected using the
and
to navigate the through the port
numbers. Press the
icon to
confirm the changes.
2.
The new module is now configured into the panel and is ready for use.
3.
Since the batteries are not connected, the panel will report them as removed, lighting the yellow “Fault” LED,
intermittently sounding the Fault buzzer, and displaying battery removed message on the screen.
4.
Connect the batteries, ensuring that the polarity is correct (Red wire = +ve) & (Black wire = -ve). Acknowledge
the Fault event via the display screen, and reset the panel to clear the battery fault.
5.
The panel should now remain in the normal condition, and you can configure the panel as normal.
Field Wiring
Typical Wiring Diagram – Zeta Conventional Sounders
NOTE:
The terminal blocks are removable to make wiring easier.
ATTENTION:
DO NOT EXCEED POWER SUPPLY RATINGS, OR MAXIMUM CURRENT RATINGS.