PREMIER QUATRO INSTALLATION MANUAL
Software Versions: PANEL 1.52 & LOOP CARD 2.0
Doc No. GLT.MAN-134
PAGE 49
Issue: 1.33 Author: GW/NJ Date: 14/1/2013
20. STANDBY BATTERY REQUIREMENTS
20.1 PANEL & DEVICE CURRENT RATINGS
The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Premier QUATRO Fire Alarm System:
DEVICE
PRODUCT
CODE
I
Q
(MA)
I
FLT
(MA)
I
ALM
(MA)
MAX
PER
LOOP
MAX
PER
SYSTEM
Premier Quatro 1 Loop Analogue Addressable Fire Alarm
Panel
QT/1–37-500
140
140
190
N/A
32
Premier Quatro 2 Loop Analogue Addressable Fire Alarm
Panel
QT/2–37-501
190
190
240
N/A
32
Premier Quatro 3 Loop Analogue Addressable Fire Alarm
Panel
QT/3–37-502
240
240
300
N/A
32
Premier Quatro 4 Loop Analogue Addressable Fire Alarm
Panel
QT/4–37-503
300
300
360
N/A
32
Zeta Addressable Manual Call Point
ZT-CP2/AD
1
N/A
2.9
125
500
Zeta Addressable Weatherproof Manual Call Point
ZT-CP2/AD/WP
1
N/A
2.9
125
500
Zeta Input Unit
ZIU
0.9
2.8
2.9
125
500
Zeta Input Output Unit
ZIOU
0.9
2.8
10.6
16
64
Zeta Input Output Unit – mains switching
ZIOU/230
0.9
2.8
19
10
40
Zeta Sounder Control Module
ZSCC
0.9
2.8
10.6
16
64
Zeta Sounder Control Module – 4 circuits
ZSCC/4
0.8
1.09
0.8
16
64
Zone Monitor Unit
ZTZM/1
1.08
1.09
1.09
10
40
Zone Monitor Unit – 4 zones
ZTZM/4
1.08
1.09
1.09
10
40
Zeta Loop Powered Door Magnet interface
ZTA-DH
1.0
3.0
16.6
12
48
Fyreye Extra Addressable Optical Smoke Detector
FEAOE2000
0.48
N/A
2.3
125
500
Fyreye Extra Addressable Heat Detector
FEAHE2000
0.44
N/A
2.4
125
500
Fyreye Extra High Temperature Heat Detector
FEAHHE2000
0.44
N/A
2.4
125
500
Fyreye Extra Addressable Opto-Heat Detector
FEAOH2000
0.52
N/A
2.3
125
500
Zeta Addressable Common Sounder Base
ZTA-CSB
0.4
N/A
4
64
256
Zeta Addressable Common Sounder Flasher Base
ZTA-CSFIB
0.7
N/A
5.5
48
192
Zeta Addressable Maxitone Sounder
ZAMT
0.6
N/A
12
32
128
Zeta Addressable Maxitone Sounder Flasher
ZAMTF
0.6
N/A
15
24
96
Zeta Addressable Securetone 2 Sounder
ZAS2/R
0.5
N/A
4
64
256
Zeta Addressable Securetone 2 Sounder Flasher
ZAS2/RFI
0.9
N/A
5.5
48
192
Zeta Addressable Remote LED Indicator
ZTA/LE2
1.5
N/A
10
32
128
Zeta Addressable 3 wire Remote LED
ZTA/LE3
0
N/A
10
32
128
Fyreye Addressable Beam Detector (5-50m)
ZT-50RA
5
7
9
20
80
Fyreye Addressable Beam Detector (50-100m)
ZT-100RA
5
7
9
20
80
Conventional Sounders Via 2 Sounder Circuits
450mA
per Conv
Circuit
Zeta Conventional Maxitone Sounder
ZMT/8
0
N/A
15
N/A
60
Zeta Conventional Miditone Sounder
ZMD/8
0
N/A
15
N/A
60
Zeta Conventional Securetone Sounder
ZST/8
0
N/A
15
N/A
60
Zeta Conventional Megatone Sounder
ZIDC
0
N/A
200
N/A
4
Zeta Conventional Flasher
ZFL2RR
0
N/A
90
N/A
10
Zeta Conventional Sounder Flasher
ZLT/8RR
0
N/A
110
N/A
8
Zeta Conventional 6” Bells
ZTB6B/24
0
N/A
25
N/A
36
Zeta Conventional 8” Bells
ZTB8B
0
N/A
35
N/A
25
Conventional Detectors (via a Zone Monitor)
Fyreye Conventional Optical Detector
FEO2000
0.06
N/A
25
N/A
N/A
Fyreye Conventional Heat Detector (A1R)
FEHR2000
0.04
N/A
25
N/A
N/A
Fyreye Conventional Heat Detector (CS)
FEFH2000
0.04
N/A
25
N/A
N/A
GSM COMMUNICATOR
GSM-COM
200
500
500
N/A
1
20.2 STANDBY BATTERY CALCULATION
In order to calculate the standby battery size required, the following formula can be used:-
Battery Size (Standby time in Amp Hours) = 1.25 x [(T
ALM
x I
ALM
) + (T
SBY
x (I
QP
+ I
QZ
))]
Where:
T
ALM
= Maximum time in hours required for the alarm [½ hour is most common time]