PREMIER QUATRO INSTALLATION MANUAL
Software Versions: PANEL 1.52 & LOOP CARD 2.0
Doc No. GLT.MAN-134
PAGE 27
Issue: 1.33 Author: GW/NJ Date: 14/1/2013
found, and the number of double addresses (i.e. points with the same address), and
the number of addresses that have been modified since the last search.
Check that the number of VALID devices is the same as the number of devices
actually installed on the loop.
If the panel reports an open or short circuit for a loop, select Autocheck. This checks
the number of points found when the loop is checked from the start of the loop (S)
and then checked from the end of the loop (R). The Start and Return values indicate
the position of the loop fault from each end of the loop.
Loop > Autosearch
Autocheck
LED Flash Setup
Protocol Setup
Loop 1 is now configured. Press Accept and then repeat the operations above for the
remainder of the loops fitted to the panel.
Press Accept then Cancel then the
◄
key until the screen either shows SYSTEM
NORMAL or FAULT. The panel will now function as a basic system.
SEARCH LOOP REPORT 1
VALID :115 DOUBLE ADDRESS :003
CHANGED TYPE :002
[Accept][Cancel] [Reports]
11.6 ZONE LABELS
The subdivision of a fire alarm system was explained in Section 3, the Premier Quatro panel being capable of assigning 20 zones.
When a fire is enunciated, the zone number in which the fire is located is indicated on the alphanumeric display. In addition to its
numerical description, a zone can be identified by a text label, e.g. 3rd floor west ext. If the installer associates a text label with each
zone of a fire alarm system, this will be displayed on the LCD when a fire is detected. The maximum length of the zone text label is
18 characters.
To access the menu for selecting Zone Labels:
Turn the keyswitch clockwise to the Controls Enabled Position.
The controls Active LED will light.
ZONE EDIT
ZONE :<XXX> MODE: ENABLE
TEXT :[3RD FLOOR WEST EXT]
[-] [+] [Points] [Exit]
Press any key followed by the level 2 password (default is 2222).
Select Zone edit, and then the zone number by either using the alphanumeric
keypad, or the function keys F1 and F2 to increment or decrement the zone number.
Type in the text label between the brackets on the 3rd line of the display. Selecting F3
allows one or more points (i.e. devices) to be added to the loop.
ADD POINTS
ZONE :<XXX> LOOP : [1]
RANGE: [001] TO :[001]
[Accept] [Exit]
The LCD also indicates the current mode of each zone – enabled or disabled.
11.7 ADDRESS LABELS AND ZONES
Premier Quatro is an addressable panel, i.e. it will indicate the address or location of a fire that has been detected. The address
number of each point or device on each loop has already been selected according to its DIP switch setting. The installation engineer
must now assign a label or location for each device, e.g. ROOM 107. A maximum of 20 characters can be used for each label. At the
same time each point can be allocated to a zone.
To access the menu for selecting Address Labels:
Turn the keyswitch clockwise to the Controls Enabled Position. The controls Active LED will light.
Press any key followed by the Password 2222. Select Points followed by Edit Point. For each point the following data can be
entered:
Loop Number , Address Number, Zone Number & the Text Label (e.g. ROOM 107)
The LCD also indicates the MODE of a point, i.e. ENABLED or DISABLED, the analogue
value (V) that the device is sending to the panel, and the type. Pressing the F keys
below [–] and [+], decreases or increases the address number.
LOOP :<1> ADR :[019] ZONE:[023]
TYPE :Optical MODE :ENABLE V:023
TEXT :[ROOM 107 ]
[-]
[+]
[Exit]
When a fire is detected, the address label of the device which has been triggered can be displayed by using the keys
►
and
◄
to scroll
through the list of fires detected and stored by the panel.