Extinguishing Panel - USER MANUAL 

 

Approved Document No: GLT.MAN-132

 

 

PAGE 7

 

Issue : 1.2         Author: NRPJ      Date: 06/10/2010

 

PANEL OPERATION 

Normal Operation 

 

With  the  “CONTROL”  Key  in  the  “OFF”  position  and  under  normal  conditions  the 
system will be silent and the green “POWER LED” illuminated.  

 

The system may either be in “Automatic” or “Manual” mode of operation.  This will be 
evident  by  the  illumination  of  either  the  “Automatic”  or  “Manual”  LED.  In  Manual 
Mode,  the  bottle  output  will  not  be  activated  automatically.  It  must  be  started 
manually by pressing a manual release call point. 

Fire Alarm Condition (Peripheral Zones) 

 

The Premier EX8 signals an alarm by the following:- 

 

 

Turn on the General Fire LED 

 

Turn on the Zonal Fire Indicator 

 

Turn on internal buzzer 

 

Start any sounders connected to the panel`s sounder circuits 

 

Activate the fire relay 

What to do in the event of a fire. 

 

1.  Follow the building evacuation procedure, and check that everyone has left 

the building safely. 

2.  The building fire officer or suitably trained responsible person should 

CAREFULLY enter the building, and locate the area of the alarm from the fire 
alarm panel. 

3.  Investigate to determine the cause of the alarm. Look for the detector in the 

zone in alarm that signalled the fire. The detector that signalled an alarm will 
have its RED ALARM LED on. 

4.  If a small fire is found, a suitably trained person could tackle this with a 

suitable fire extinguisher. 

5.  If a larger fire is found, leave the building immediately, and contact the fire 

brigade. 

6.  If no fire is found, make a note of the detector that signalled fire, and look for 

anything nearby that could be the cause of the activation, eg cooking, or use 
of a hot air gun etc. 

7.  Record findings in the fire alarm log book. 

Resetting from an alarm condition 

 

After the relevant action has been taken, the Premier EX8 fire alarm panel can be reset by the 
following:- 
 

Press Start/Stop sounder button, This will silence the external sounders. 

Press Silence Fault Tone button. This will silence the panel`s internal buzzer. 

Press the Reset button. This will return the panel to it`s normal condition. 

 
If the panel goes straight back into alarm, then the cause of the alarm has not been cleared. This 
could be a detector still exposed to smoke, or a call point still in the active position. Press 
Start/Stop Sounder button, followed by silence buzzer button on the panel, then investigate for a 
call point, or detector that still has it`s RED ALARM LED on. Reset the call point, or clear the 
smoke. If the problem persists, contact an engineer. 

Содержание PREMIER EX8

Страница 1: ...EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 EN54 PARTS 2 4 USER MANUAL Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06...

Страница 2: ...PANEL OPERATION 7 Normal Operation 7 Fire Alarm Condition Peripheral Zones 7 What to do in the event of a fire 7 Resetting from an alarm condition 7 First Stage Alarm 8 Second Stage Alarm 8 Hold Abor...

Страница 3: ...fired The panel has remote inputs for Start Stop Sounders Silence Reset to allow the panel to be controlled remotely The panel has Open collector repeat outputs for most panel status indications eg 1s...

Страница 4: ...L Y SILENCE FIRE Each function has its own indication LED There are Alarm Active Fault Test Disablement LEDs for most panel inputs outputs Some of these indications are not applicable for certain func...

Страница 5: ...tage sounder is on 1S T STAGESNDRFAULT YELLOW Lights when the first stage sounder has a wiring fault 1 S T STAGESNDRTEST YELLOW Lights when the first stage sounder is in test mode 1S T STAGESNDRDISABL...

Страница 6: ...tic manual only mode GAS RELEASE COUNTER Used to view or alter Gas Release Counter RELEASE DURATION TIME Used to view or alter Release Duration Time Counter RESET INHIBIT TIME Used to view or alter Re...

Страница 7: ...m Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED on 4 If a small fire is found a suitably trained person could tack...

Страница 8: ...he second stage cannot be silenced and after a delay period Set by the the installer the extinguishing output will be initiated releasing the extinguishing agent and the second stage sounder will now...

Страница 9: ...automatic mode the panel cannot be reset until the reset inhibit timer has finished it s countdown The panel can NOT be reset from a fault condition All faults are non latching so when a fault clears...

Страница 10: ...peated Press SELECT button The GENERAL DISABLEMENT LED will light steady and the Crossed Zone 1 Disabled LED will flash 4 quick flashes off The panel is now in SELECT DISABLEMENT MODE The select butto...

Страница 11: ...Panel USER MANUAL Approved Document No GLT MAN 132 PAGE 11 Issue 1 2 Author NRPJ Date 06 10 2010 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQ...

Страница 12: ...No GLT MAN 132 PAGE 12 Issue 1 2 Author NRPJ Date 06 10 2010 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDINGS CATEG...

Страница 13: ...el USER MANUAL Approved Document No GLT MAN 132 PAGE 13 Issue 1 2 Author NRPJ Date 06 10 2010 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE CO...

Отзывы: