Extinguishing Panel - USER MANUAL 

 

Approved Document No: GLT.MAN-132

 

 

PAGE 3

 

Issue : 1.2         Author: NRPJ      Date: 06/10/2010

 

INTRODUCTION 

 

The Premier EX 8 is a combined 2 zone , 1 area extinguishing panel, and 4 zone 
conventional fire alarm panel.  

 

It has 2 zones dedicated to the extinguishing section. These are known as crossed or 
co-incidence zones. Both circuits will need to be triggered in order to activate the 
extinguishing circuit. This kind of operation also referred to as “double – knock” 

 

It has 4 zones for fire detection (referred to as peripheral zones, or fire zones). These 
will not trigger the extinguishing circuit. 

 

The Extinguishing section is designed to BSEN12094-1:2003. 

 

The fire alarm section is designed to EN54-2:1998 A1 + A2. 
The Power Supply section is designed to EN54-4:1998 A1 + A2 

 

This design allows the same panel to protect an extinguishing area, and also monitor 
the rest of the site for a fire. 

 

The panel has an integral Manual Release call point fitted to the front of the panel. 

 

The panel has monitored inputs for field connections, such as manual release, 
emergency hold, etc. 

 

The panel has relay outputs for first & second stage alarms, fault & gas fired. 

 

The panel has remote inputs for Start/Stop Sounders, Silence & Reset, to allow the 
panel to be controlled remotely. 

 

The panel has Open collector repeat outputs for most panel status indications (eg 1

st

 

stage alarm, 2

nd

 stage alarm, Automatic mode, Manual mode etc) 

 

The panel has a connection for a serial repeater unit (4 wire) 

 

The Premier EX8 can be in any of the following conditions:- 

 

Quiescent condition 

– ie System Normal 

 

Fire condition 

– ie a fire on one of the peripheral zones 

o

  The Premier EX8 will enter the fire condition within 1 second of a 

detector on a peripheral zone signalling an alarm. 

 

Fault condition 

 

Disabled condition 

 

Test condition 

 

Pre-activated condition 

o

  The Premier EX8 will enter the pre-activated condition (first stage 

alarm) within 1 second of a detector on one of the crossed zone 
signalling an alarm. 

 

Activated condition 

o

  The Premier EX8 will enter the activated (second stage alarm) 

condition within 1 second of the second crossed zone signalling an 
alarm. 

 

Released condition 

o

  The Premier EX8 will enter the released condition (bottle output 

activated) within 1 second of establishing the activated condition, OR 
after the delay configured in the bottle output timer. 

 

 
WARNING: Access to live components inside this fire alarm enclosure. The key 
to open the door to gain internal access should be held by authorised 
personnel only. 

Содержание PREMIER EX8

Страница 1: ...EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 EN54 PARTS 2 4 USER MANUAL Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06...

Страница 2: ...PANEL OPERATION 7 Normal Operation 7 Fire Alarm Condition Peripheral Zones 7 What to do in the event of a fire 7 Resetting from an alarm condition 7 First Stage Alarm 8 Second Stage Alarm 8 Hold Abor...

Страница 3: ...fired The panel has remote inputs for Start Stop Sounders Silence Reset to allow the panel to be controlled remotely The panel has Open collector repeat outputs for most panel status indications eg 1s...

Страница 4: ...L Y SILENCE FIRE Each function has its own indication LED There are Alarm Active Fault Test Disablement LEDs for most panel inputs outputs Some of these indications are not applicable for certain func...

Страница 5: ...tage sounder is on 1S T STAGESNDRFAULT YELLOW Lights when the first stage sounder has a wiring fault 1 S T STAGESNDRTEST YELLOW Lights when the first stage sounder is in test mode 1S T STAGESNDRDISABL...

Страница 6: ...tic manual only mode GAS RELEASE COUNTER Used to view or alter Gas Release Counter RELEASE DURATION TIME Used to view or alter Release Duration Time Counter RESET INHIBIT TIME Used to view or alter Re...

Страница 7: ...m Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED on 4 If a small fire is found a suitably trained person could tack...

Страница 8: ...he second stage cannot be silenced and after a delay period Set by the the installer the extinguishing output will be initiated releasing the extinguishing agent and the second stage sounder will now...

Страница 9: ...automatic mode the panel cannot be reset until the reset inhibit timer has finished it s countdown The panel can NOT be reset from a fault condition All faults are non latching so when a fault clears...

Страница 10: ...peated Press SELECT button The GENERAL DISABLEMENT LED will light steady and the Crossed Zone 1 Disabled LED will flash 4 quick flashes off The panel is now in SELECT DISABLEMENT MODE The select butto...

Страница 11: ...Panel USER MANUAL Approved Document No GLT MAN 132 PAGE 11 Issue 1 2 Author NRPJ Date 06 10 2010 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQ...

Страница 12: ...No GLT MAN 132 PAGE 12 Issue 1 2 Author NRPJ Date 06 10 2010 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDINGS CATEG...

Страница 13: ...el USER MANUAL Approved Document No GLT MAN 132 PAGE 13 Issue 1 2 Author NRPJ Date 06 10 2010 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE CO...

Отзывы: