Extinguishing Panel - USER MANUAL 

 

Approved Document No: GLT.MAN-132

 

 

PAGE 10

 

Issue : 1.2         Author: NRPJ      Date: 06/10/2010

 

 

DISABLEMENT 

 

The Premier EX8 allows any of the following to be disabled to aid commissioning and assist routine 
maintenance work:- 

 

Crossed zones 

 

Peripheral Zones 

 

First stage sounders 

 

Second stage sounders & Bottle output (Disabled together) 

 

First Stage Relay 

 

Second Stage Relay 

 

External Equipment Relay 

 
When an zone is disabled, the panel will not respond to any fault or fire signals it receives from that 
input. When an output is disabled, the panel will not activate that output. 
 
This might be used if the system requires routine maintenance, and the customer needs the system to 
continue running, but does

n’t want spurious false alarms or fault signals. 

 
The panel will respond in the usual manner to any events in any non-disabled inputs. 

 

To Programme an Input or Output as Disabled 

 
Any number of inputs or outputs can be disabled, but it is good practice to only disable the minimum 
requirement at a time. 
 
Insert and turn control key to enabled position; 
 
Press DISABLE button and the GENERAL DISABLEMENT LED will come on (flashing fast, 4 flashes 
then off, repeated); 
 
Press SELECT button. The GENERAL DISABLEMENT LED will light steady, and the Crossed Zone 1 
Disabled LED will flash 4 quick flashes & off. The panel is now in SELECT DISABLEMENT MODE. 
 
The select button is used to highlight (flash) the section that needs to be disabled. Press select button 
until the correct LED is flashing, then press confirm. The LED will now flash 4 quick flashes & on, to 
indicate that this section is disabled. 
  
If more than one section needs to be disabled, then press SELECT button again until the required 
zone is selected. (The previously disabled section will now have its disabled LED lit steady.) 
 
If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on another 
part of the system), turn the keyswitch off, then back on again. 
 
Once all the work has been done the zones need to be enabled again. If the panel is not in SELECT 
DISABLEMENT MODE, turn the keyswitch to controls enabled, press DISABLE button. 
 
Press the scroll button until the disabled section has been selected. Press CONFIRM button to re-
enable. Scroll to any other disabled section and enable in the same way. When all sections are 
enabled again, turn the keyswitch to off to return the system to normal. 
 

 

NOTE: During a Disabled condition, sections of the fire alarm system will be 
inoperative. Extra caution should be used in the disabled part of the premises

.  

 

Содержание PREMIER EX8

Страница 1: ...EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 EN54 PARTS 2 4 USER MANUAL Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06...

Страница 2: ...PANEL OPERATION 7 Normal Operation 7 Fire Alarm Condition Peripheral Zones 7 What to do in the event of a fire 7 Resetting from an alarm condition 7 First Stage Alarm 8 Second Stage Alarm 8 Hold Abor...

Страница 3: ...fired The panel has remote inputs for Start Stop Sounders Silence Reset to allow the panel to be controlled remotely The panel has Open collector repeat outputs for most panel status indications eg 1s...

Страница 4: ...L Y SILENCE FIRE Each function has its own indication LED There are Alarm Active Fault Test Disablement LEDs for most panel inputs outputs Some of these indications are not applicable for certain func...

Страница 5: ...tage sounder is on 1S T STAGESNDRFAULT YELLOW Lights when the first stage sounder has a wiring fault 1 S T STAGESNDRTEST YELLOW Lights when the first stage sounder is in test mode 1S T STAGESNDRDISABL...

Страница 6: ...tic manual only mode GAS RELEASE COUNTER Used to view or alter Gas Release Counter RELEASE DURATION TIME Used to view or alter Release Duration Time Counter RESET INHIBIT TIME Used to view or alter Re...

Страница 7: ...m Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED on 4 If a small fire is found a suitably trained person could tack...

Страница 8: ...he second stage cannot be silenced and after a delay period Set by the the installer the extinguishing output will be initiated releasing the extinguishing agent and the second stage sounder will now...

Страница 9: ...automatic mode the panel cannot be reset until the reset inhibit timer has finished it s countdown The panel can NOT be reset from a fault condition All faults are non latching so when a fault clears...

Страница 10: ...peated Press SELECT button The GENERAL DISABLEMENT LED will light steady and the Crossed Zone 1 Disabled LED will flash 4 quick flashes off The panel is now in SELECT DISABLEMENT MODE The select butto...

Страница 11: ...Panel USER MANUAL Approved Document No GLT MAN 132 PAGE 11 Issue 1 2 Author NRPJ Date 06 10 2010 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQ...

Страница 12: ...No GLT MAN 132 PAGE 12 Issue 1 2 Author NRPJ Date 06 10 2010 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDINGS CATEG...

Страница 13: ...el USER MANUAL Approved Document No GLT MAN 132 PAGE 13 Issue 1 2 Author NRPJ Date 06 10 2010 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE CO...

Отзывы: