17. PANEL SPECIFICATIONS
17.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION VALUE
ENCLOSURE SIZE
480 x 395 x 100 mm
TOP CABLE ENTRIES
20 x 19mm DIA GROMMETED ENTRIES
BOTTOM CABLE ENTRIES
10 x 19mm KNOCKOUT ENTRIES
REAR CABLE ENTRIES
2 SNAP OUTS, 60 x 20mm
17.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE
24V DC (2 X 12V SLA BATTERY)
SYSTEM VOLTAGE
24V DC NOMINAL (18 – 32 V)
SYSTEM VOLTAGE RIPPLE
2V PK-PK MAX
CHARGER SIZE
UP TO 7AH in 24 Hours
ZONE VOLTAGE
24V DC NOMINAL (+9 volt data)
SOUNDER ALARM OUTPUTS
4 x 250mA @ 24V DC (Nominal)
AUXILIARY FAULT OUTPUT
1 x RELAY SELV (1A MAX)
AUXILIARY FIRE OUTPUT
1 x RELAY SELV (1A MAX)
NUMBER OF LOOPS
2 LOOPS
MAXIMUM NUMBER OF ZONES
16 ZONES
MAXIMUM LOOP CAPACITY
126 DEVICES PER LOOP
MAXIMUM ZONE CAPACITY
16 DEVICES PER ZONE
MAXIMUM LOOP RESISTANCE
25 ohms
MAXIMUM LOOP CAPACITANCE
0.3
μ
F
MAXIMUM VOLTAGE PICKUP ALLOWED
50mV
REMOTE SOUNDER ACTIVATION
VIA N/O CONTACTS
SOUNDER END OF LINE DEVICE
10 K RESISTOR
CHARGER VOLTAGE
28.3V @ 22-24
o
C (NO BATTERY CONNECTED)
LOOP SHORT CIRCUIT PROTECTION
750mA
CHARGER SHORT CIRCUIT PROTECTION
Batteries less than 20V
TOTAL CHARGER OUTPUT
1.5 Amp