FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE

Alternative Soft Addressing Option

Using our hand held MkII programmer (Part No: 48-004), the unit can be addressed 

electronically.

Step 1:

  Set all addresses to zero 0000000

Step 2:

  Connect leads to LOOP IN+ and LOOP IN- as shown below

Step 3:

  Follow the procedure as described in the handheld programmer manual.

NOTE: When a device is soft addressed as above, the address CANNOT BE CHANGED by 

mechanical setting of the dip-switch. In order to re-enable the dip-switch the unit needs 

to be set electronically back to zero first.

Isolator Function

The Isolator Function can be enabled or disabled according to the wiring method.
B. Enabling the Isolator Function

A. By-passing the Isolator Function

Содержание FYREYE MKII ZASC-MI

Страница 1: ...up Note the input voltage should provide adequate current to operate the ZASC MI in addition to operating the connected alarm load Model No ZASC MI Fyreye MkII Addressable Sounder Control Module With...

Страница 2: ...o 012 Author NRP Jones Date 10 05 2021 Page 2 FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR INSTALLATION GUIDE Wiring Details All wiring terminals will accept solid or stranded cables u...

Страница 3: ...On Current Ext 32V 9 5mA Plus Sounder Load Sounder Output Rating 500 mA Isolating Current 7 3mA Sounder End of Line 10K tolerance 7 5K to 15K Operating Temperature 10 C to 55 C Max Humidity 95 RH Non...

Страница 4: ...OFF OFF OFF ON ON 61 OFF ON OFF OFF OFF OFF ON ON 62 ON OFF OFF OFF OFF OFF ON ON 63 OFF OFF OFF OFF OFF OFF ON ON ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 64 ON ON ON ON ON ON OFF ON 65 OFF ON ON ON...

Страница 5: ...OFF OFF OFF 248 ON ON ON OFF OFF OFF OFF OFF 249 OFF ON ON OFF OFF OFF OFF OFF 250 ON OFF ON OFF OFF OFF OFF OFF 251 252 253 254 255 ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 128 ON ON ON ON ON ON ON OF...

Страница 6: ...000000 Step 2 Connect leads to LOOP IN and LOOP IN as shown below Step 3 Follow the procedure as described in the handheld programmer manual NOTE When a device is soft addressed as above the address C...

Страница 7: ...er is connected correctly Input Illuminated when no external fault signal present Functional Test Data Command Bit Function Input Bit Function 3 Not Used 3 Not Used 2 Not Used 2 Not Used 1 PULSED MODE...

Страница 8: ...value unstable Dual address Loop data fault data corruption 0905 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN 14 GLT 234 DoP 1 EN54 18 2005 EN54 17 2005 Fire detection and fire alarm systems I...