FYREYE MKII ADDRESSABLE SOUNDER CONTROL MODULE WITH ISOLATOR - INSTALLATION GUIDE
Faultfinding
Problem
Possible Cause
No response or missing
Incorrect address setting
Incorrect loop wiring
Fault condition reported
IIncorrect address setting
Incorrect wiring of sounder zone or fault input
Faulty sounder
Local supply faulty or polarity incorrect
Fuse blown on sounder PCB
Sounders do not operate
Incorrect wiring
Fuse blown on sounder PCB
Incorrect cause and effect programming
Faulty sounder
Panel Fault
Sounders operate continuously
Incorrect sounder zone wiring
Analogue value unstable
Dual address
Loop data fault, data corruption
0905
Zeta Alarms Limited,
72-78 Morfa Road, Swansea SA1 2EN
14
GLT-234-DoP-1
EN54-18: 2005
EN54-17: 2005
Fire detection and fire alarm systems – Input/Output Devices
Fire detection and fire alarm systems – Short Circuit Isolators
Zeta Addressable Sounder Control Module with Isolator
ZASC-MI
Intended for use in fire detection and fire alarm systems in and around buildings
Response delay (response time) - PASS
Performance under fire conditions - PASS
Operational reliability - PASS
Durability of operational reliability: temperature resistance - PASS
Durability of operational reliability; vibration resistance - PASS
Durability of operational reliability; humidity resistance - PASS
Durability of operational reliability; corrosion resistance - PASS
Durability of operational reliability; electrical stability - PASS