User Guide of ZT-20EX & ZT-500EX
15
SPST volt-free contacts rated 5A at 30VDC or 250VAC
0-20mA (stepped)
Source & Sink, Isolated/Non-isolated configuration
Fault: 0 +1mA
Normal: 4mA
±
10%
Warning:
16mA
±
5%
Alarm: 20mA
±
5%
Resistance Loop : max. 500
Ω
RS-485 <optional>
RS-485 Modbus compatible communication link that
can be used in computer controlled installations
MECHANICAL SPECIFICATIONS
Materials
- Heavy duty copper free aluminium with bright grey
- Stainless Steel 316L
Mounting Bracket
<Optional>
- Heavy duty copper free aluminium with bright grey
- Stainless Steel 316L
Dimensions
Detector:
83(D) x 126(L) mm
Weight
Detector (aluminium):
1.0 kg
Detector (ST 316L):
2.7kg
Mounting Bracket (aluminium/ St.): 0.3kg / 0.7kg
APPROVALS
Hazardous Area
ATEX Ex II 2 G, Exd IIC T6, -40
℃
to +75
℃
Performance
- Designed to meet FM3260/EN-54-10
- KFI(for Korea) approved
For additional details or assistance, please contact:
Zeta Alarms Limited
Detection House, 72-78 Morfa Road, Swansea, SA1 2EN, United Kingdom
Phone: +44(0)1792 455175 Fax: +44(0)1792 455176