SIMPLICITY PLUS / SIMPLICITY MICRO – ADDITIONAL FEATURES.  

 

Software Version  :PANEL-R6180 (Plus) R5780 (Micro)

 

Approved Document No: GLT.MAN-139

 

 

 

PAGE 6 

Issue 1.00         Authorised: GH      Date: 02/06/2010

 

6 CHANGING THE ALARM RESPONSE 

– I/O UNITS 

 
Because a system could have several I/O units, each reacting to different types of events the simplicity system 
adopts the following method for configuring I/O units:- 
 
1. Select a default I/O unit operation (This is done from the Alarm Operation Menu) 
This will then be the default operation of all I/O units on the system. 
 
2. Any I/O units which need a different operation can be edited individually from the edit device screen 
 

6.1 Types of I/O UNIT Operation 

 
The simplicity now has the following types of I/O operation:- 
  
I/O Com  

Operates output on ANY alarm 

I/O Zn-D  

Operates it`s output on a DETECTOR alarm from it`s own ZONE 

I/O Zn-A  

Operates it`s output on any alarm from it`s own ZONE 

I/O Addr  

Operates it`s output ONLY when it`s own INPUT is triggered 

I/O Link   

Special type used for Inter-panel link. Output operates on any alarm , EXCEPT from its own 

 

 

address, AND the input is non latching and behaves similar to class change. 

 

6.2 Setting Default I/O UNIT Operation 

 
To set the simplicity panels default I/O operation, enter configuration menu 2, then 
select config system to bring up the system menu 
 
 
Select Option 3 (Alarms) to bring up the alarm operation Menu. 
 
Select option 5 (I/O). This brings up the following screen.  
 
 
Press Prev & Next to select the default operation, then press enter. 
 

 
 

6.3 Setting Individual I/O UNIT Operation 

 
To alter the operation mode of an individual I/O unit, go to configuration menu 2 
 
Select Edit Device. 
 
Scroll to the required Address 
 
Press V to cycle through the different 

V

ariations of I/O configuration 

 
 

7 SETTING THE LCD LANGUAGE 

 
From Configuration menu 2, Select configure system (option 6)  
 
Then from the system menu, select option 1 (Language) 
 
Pressing Prev / Next will scroll through the available languages. 
 
The currently supported languages are:- 
 
English 
Spanish 
Portuguese 
Hungarian 
French 
 
Other languages are available on request.

System Menu 
1: Clock  4: Timing 
2: Zones  5: Misc 
3: Alarms 6: Reset

 

Alarm Operation 
1: Det    4: Bases 
2: MCP    5: I/O 
3: Sounder

 

 

 I/O Unit Operation 
       Common 
 
   ENTER to Confirm

 

 

Configuration Menu 2 
4:Configure Loops 
5:Edit Device 
6:Config System    < 

 

I/O-COM    



  

Analog:  16  Normal 
Interface to Main FA 
Zone:01       Ad:013 

System Menu 
1: Clock  4: Timing 
2: Zones  5: Misc 
3: Alarms 6: Reset

 

Misc Settings 
1: Language 
2: Version Info 

     Set Language 
       English 
 
Press ENTER to Save 

Содержание SIMPLICITY PLUS

Страница 1: ...MPLICITY MICRO ADDITIONAL FEATURES Software Version PANEL R6180 Plus R5780 Micro Approved Document No GLT MAN 139 PAGE 0 Issue 1 00 Authorised GH Date 02 06 2010 ANALOGUE ADDRESSABLE FIRE ALARM PANEL ADDITIONAL FEATURES ...

Страница 2: ...Alarm Response 5 5 2 Changing MCP Alarm Response 5 5 3 Zonal Sounder to Common Sounder Delay 5 5 4 Associated Sounder Base Settings 5 6 CHANGING THE ALARM RESPONSE I O UNITS 6 6 1 Types of I O UNIT Operation 6 6 2 Setting Default I O UNIT Operation 6 6 3 Setting Individual I O UNIT Operation 6 7 SETTING THE LCD LANGUAGE 6 8 ALARM VERIFICATION 7 8 1 How Alarm Verification Works 7 8 2 Setting the Al...

Страница 3: ...st sees devices A device out of the panel s address range will be reported EG a detector at address 80 on a Simplicity 64 User definable zones Option for zonal or common alarm operation Options for I O operation Alarm Verification User selectable languages Options to reset panel to factory settings On the Simplicity Plus the CPU card is now integrated on the display PCB so is no longer user upgrad...

Страница 4: ...ter button to configure the loop The panel will show Configuration in progress for about 9 seconds then it will then return to the system normal screen The loop is now configured 3 Reduced Loop Simplicity Panels For the reduced loop capacity Simplicity panels EG Simplicity Micro or Simplicity Plus 64 it is possible to address a device outside the panels range Previous versions of simplicity panel ...

Страница 5: ...ER to save or press CANCEL to keep the existing Address 6 The Zone will now change to the selected boundary with the first device of the next zone changing accordingly Eg just changing zone 1 last device to 10 would result in zone 1 being addresses 1 to 10 Zone 2 being 11 to 32 zone 3 being the default 33 to 48 etc NOTE If the building plans have not been finalised it would be wise to leave a few ...

Страница 6: ...equirement to start all the other sounders if the alarm continues for a given time On the Simplicity system we refer to this as the Zonal to Common sounder time Select option 3 from the alarm operation menu This zonal to common sounder time can either be disabled IE alarms stay zonal or it can be enabled IE all the sounders will start after the programmed time delay To alter this delay go to the E...

Страница 7: ...2 Setting Default I O UNIT Operation To set the simplicity panels default I O operation enter configuration menu 2 then select config system to bring up the system menu Select Option 3 Alarms to bring up the alarm operation Menu Select option 5 I O This brings up the following screen Press Prev Next to select the default operation then press enter 6 3 Setting Individual I O UNIT Operation To alter...

Страница 8: ...alarm 5 If a detector WITHOUT verification setting goes into alarm the panel will go straight into full alarm With this method of operation a cooking alarm in one apartment will alarm locally giving the apartment occupants a chance to clear the smoke before the whole building is evacuated Also as a failsafe if a heat detector alarms or if a second smoke detector on the system goes into alarm the s...

Страница 9: ...o their default setting 3 Panel Resets alarm response back to all common resets system timers 4 Devices Clears device information from memory and clears device label device configuration 6 All Performs 2 3 4 in one operation When you select to reset a section the panel will display something like Press enter to confirm or cancel to abort the action The panel will then warn that this action can not...

Страница 10: ...sociated sounder Select alarm verification Turn off associated sounder at this address Disable this device Select specific I O Operation for an I O unit 6 Config System System Menu 1 Clock Adjust time date 2 Zones Change zone boundaries 3 Alarms Alarm Operation 1 Det Choose detectors to cause zonal alarm or common alarm for sounders 2 MCP Choose MCP to cause zonal alarm or common alarm for sounder...

Отзывы: