EXPro Installation Manual
Approved Document No: GLT-212-7-1
Page 25
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
ACCESS LEVELS
Access level
Accessed by
Access method
Functions accessed
1
General public
Default state
View panel
LED test
Manual release
2
Responsible person
User level
password
(default: 2222)
Start/stop sounders
Silence buzzer
Reset panel
Disable sections of the system
Put the panel into test mode
Set the default relay states
View logs
3a
Installer/engineer
Engineer level
password
(default: 1111)
Reset logs and/or panel configuration
Set sounder locale
Set timers
Check software version
Change passwords
Change language
3b
Installer/engineer
Open
enclosure
Connect wiring during install
Battery check during maintenance
Reset system fault
4
Authorised service
engineer
Open
enclosure and
use of
appropriate
programming
tool
Update firmware