INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 8
6. INSTALLING THE SYSTEM
6.1 Considerations before Installation
6.1.1 MOUNTING THE CONTROL PANEL
The control panel should be installed in accordance with the following recommendations:-
•
The panel should be close to the main entrance of the building, so that it can be viewed by any fire-
fighting personnel entering the building.
•
It should be fitted to a sturdy wall that will not flex unnecessarily.
•
It should be mounted at eye level, in order for it to be viewed without need of a ladder.
•
It should be installed in a dry, weatherproof place, preferably NOT in direct sunlight.
•
It should be easily accessible, so that the responsible person can perform their regular fire alarm
checks.
6.1.2 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS
All wiring must be installed to meet BS5839: Pt1: 2013 and BS 7671 (Wiring Regs) standards. Other
National standards of fire alarm system installation should be adhered to where applicable.
Screened cables should be used throughout the installation to help shield the Panel from outside interference
and ensure EMC compatibility.
The two categories of cable according to BS5839: Pt1: 2013, Clause 26 “Fire Detection and Alarm Systems for
Buildings (Code of Practice for System Design, Installation and Servicing)” are:
Standard fire resisting cable – to PH30 classification of EN 50200
Enhanced fire resisting cable – to PH120 classification of EN 50200
(Note that all cables should be at least 1mm
2
cross section
On the ID2 the general recommendation would be to use standard fire resistant cable, such as Firetuff
, FP200
or any equivalent. These cables are screened, and will provide good EMC shielding when properly grounded at
the panel. Certain system specifications may demand the use of a particular type of cable and due regard
should be paid to this fact.
Depending on the environment, the cables may need mechanical protection (such as a conduit).
6.1.3 MAINS WIRING RECOMMENDATIONS
The Mains supply to the FACP is fixed wiring, using
Fire resisting
3-core cable (Between 1 mm² and 2.5mm²) or
a suitable 3-conductor system, fed from an isolating double pole switch fused spur, fused at 3A.
IT SHOULD
NOT BE CONNECTED THROUGH AN RCD.
This should be secure from unauthorised operation and be
marked ‘FIRE ALARM: DO NOT SWITCH OFF’. The supply must be exclusive to the Fire Panel.
MAKE SURE
ANY SPARE ENTRY HOLES ARE COVERED
For information on how to connect Mains to the Panel’s Power Supply PCB, see page 11.
Also refer to rating information on the mains cover inside the FACP.