background image

INFINITY ID2 INSTALLATION MANUAL.  

 

 

Software Versions: PANEL 1.N  & LOOP O.N 

 

Approved Document No: GLT-211-7-1

 

 

 

 

Issue 1.9    Author: MG/NJ     Date: 06/04/2016

 

 

PAGE 28

 

13 ALARM VERIFICATION

 

 
The ID2 includes an option to use alarm verification. It is intended for use in apartments, and similar buildings, 
where it is desirable that an alarm from a smoke detector from one apartment (or area) would need to be 
confirmed before the whole system goes into alarm. 
 

13.1 Alarm Verification Options 

 
The current revision of the panel (Software version 1.H or later) has 2 settings for alarm verification 
 
Device verification. With this setting, an alarm will just operate the sounder connected to that detector. 
 
Zonal verification. With this setting, an alarm will operate sounders connected to all sounders in that zone set to 
Zonal verification. Zonal verification can also be set to heat detectors. But selecting this just allows the heat 
detectors sounder to run on a verification from another detector. An alarm on that heat detector will set the 
system straight into full alarm. 
 
Advantages of  Device verification 

Allows for more "verification" areas per zone 

Advantages of  Zonal verification 

Will set off all sounders for apartments with multiple 
detectors 

 
Note that both types of verification can be set on a zone at the same time if required 
 

13.1 How Alarm Verification Works 

 
The verification function works as follows:- 
 
1. 

Any SMOKE detector on the system can be set to verify an alarm. (Not that an opto-heat detecor is 

 

treated as a smoke detector for verification, whether the alarm is caused by smoke or heat) 

2. 

If a detector with the verification setting senses smoke, the detector alarm LED will turn on. If the 
detector has an associated sounder base, the sounder will turn on with the Alert tone (i.e. pulsed) rather 
than the Evacuate tone. The ID2 panel`s screen will show “Confirming alarm”. 

3. 

If the device in alarm has zonal verification set, the panel will turn on the sounders of all other detectors 
set to zonal verification in that zone. 

4. 

If the detector drops below the alarm level within the programmed verification time (1 minute to 3 
minutes 45 seconds), the sounder will turn off, but the panel will continue displaying “Confirming Alarm” 
for at least 5 minutes. The buzzer will also continue to operate as long as the “Confirming Alarm” 
message is displayed. 

5. 

If the detector stays in alarm by the end of the verification delay, the system will go into full alarm. 

6. 

If another detector WITHOUT verification setting or a call point goes into alarm, the panel will go 
straight into full alarm. 

 

With this method of operation a “cooking alarm” in one apartment will alarm locally, giving the apartment 
occupants a chance to clear the smoke before the whole building is evacuated. Also, as a “failsafe”, if a heat 
detector alarms, or if a second smoke detector on the system goes into alarm, the system will go into full alarm. 
 
 

13.2 Setting the Alarm Verification Delay 

 
To set the verification delay, go to Configuration menu 2 and select option 6  
System menu. 
 
From the engineer menu 2, select option 4  
 
From the Verification screen, select option 1 (Verify time) 
 
Use Prev& Next to adjust the time, then press enter to confirm 
 

 

13.3 Applying Alarm Verification Delay to a detector 

 
To set the verification delay for a detector, go to Engineer menu 2 and select option 4 
Alarm Verify. Then in the Verification menu select option 2 Choose Device. 

 

Scroll to the required device, then press V for Verification. The letter V appears in the top 
right hand corner to confirm that this device has a DEVICE verification delay. Pressing “V”  
again will change the letter to Z for Zonal verification. Press V one more time to toggle the  
Verification off. 

Engineer Menu 2 

4: Alarm Verify 
5: Config Alarms 
6: Misc 

 Detector Verify Time  
         1:30 

 

   ENTER to Confirm

 

Optical    

        

V

 

Normal  
Fl 3 Bedroom 303 
Zone:01ID:011 

Содержание INFINITY ID2

Страница 1: ...2 INSTALLATION MANUAL Software Versions PANEL 1 N LOOP O N Approved Document No GLT 211 7 1 Issue 1 9 Author MG NJ Date 06 04 2016 INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ID TECHNOLOGY INSTALLAT...

Страница 2: ...ONNECTING THE BATTERIES 11 7 ZONE WIRING 12 7 1 Specific device wiring instructions 13 7 1 1 CP3 AD Manual Call Point 13 13 7 1 2 MKII detectors All types Base connection 13 7 1 3 ZAI MI Input Module...

Страница 3: ...ewing a fire alarm event 33 16 2 Viewing Faults during a fire alarm condition 33 16 3 Viewing Zone Disablements during a fire alarm condition 33 16 4 Viewing Device Disablements during a fire alarm co...

Страница 4: ...strap but touching any earth point eg building plumbing will help to discharge any static Always hold the PCB by its sides and avoid touching the legs of any components Keep the PCB away from damp dir...

Страница 5: ...n with requirements Clause 10 Test Condition Option with requirements The ID2 also has the following ancillary functions not required by the Standard Serial repeater output RS485 2 2 Power Supply Sect...

Страница 6: ...designed to use zone powered sounders but also has 2 conventional sounder circuits All sounders on a ID2 panel will activate on any alarm It has been designed to give the advantages of an addressable...

Страница 7: ...ual explains in a step by step manner the procedure for the basic design and installation of the ID2 range of Fire Alarm Control Panels It gives detailed instructions on how to use all the features on...

Страница 8: ...orward matter It just takes a bit of thought to zone allocation during the system design stage 1 Decide on the zone allocation for the system Each default zone can have a maximum of 15 devices fitted...

Страница 9: ...tegories of cable according to BS5839 Pt1 2013 Clause 26 Fire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable...

Страница 10: ...tray on the left hand side that holds the panel manuals If semi flushing or fitting to a tight space remember to remove the manuals before fitting to the wall Fix the enclosure to the wall using the...

Страница 11: ...ant Having entered the panel via the cable gland the mains cable should be passed twice through the provided ferrite This is made easier by removing the outer insulation The cable is then connected to...

Страница 12: ...tion 20 1 STANDBY BATTERY CALCULATIONS The two batteries are wired in series to give 24 Volts Connect the ve of Battery 1 to the black battery charger lead Connect the ve of Battery 2 to the red batte...

Страница 13: ...7 ZONE WIRING The ID2 can be wired with up to 8 separate radial circuits each with 15 devices per circuit It may also be wired as a single loop When Wired as a Loop Zone 1 is used as Loop OUT Side A...

Страница 14: ...eans of not wiring to the negative out terminal on the call point The following terminals are used for connecting the call point 2 x Negative in terminals note if you only connect to the negative in t...

Страница 15: ...1 Issue 1 9 Author MG NJ Date 06 04 2016 PAGE 14 Deep Base MKII CB D Common Base MKII CB 7 1 3 ZAI MI Input Module The end of line resistor value is 20K and the trigger resistor value is 1 K 7 1 4 ZA...

Страница 16: ...agram The EOL for the sounder circuit is 10K When using the ZASC make sure the PSU being used has a fault output relay so that in the event of a power supply fault it is reported to the control panel...

Страница 17: ...ounted on the inside front It may also be programmed via the handheld programming tool Connecting the sounder is done using the terminals in the back box of the device Please refer to the above diagra...

Страница 18: ...tor Ceiling Mount MKII ARL C Wall Mount MKII ARL W There are two versions of the remote LED Wall mounted and Ceiling mounted The ceiling mounted version requires a standard detector base Each version...

Страница 19: ...into zones and Ids The panel translates the address into a zone and ID Each zone starts with ID1 in order to simplify the addressing To assist with setting the dip switches there is a free app availab...

Страница 20: ...F OFF ON ON ON 6 13 OFF ON OFF OFF OFF ON OFF ON 2 14 ON OFF OFF OFF OFF ON ON ON 6 14 ON OFF OFF OFF OFF ON OFF ON 2 15 OFF OFF OFF OFF OFF ON ON ON 6 15 OFF OFF OFF OFF OFF ON OFF ON 3 1 OFF ON ON O...

Страница 21: ...at least 17 Volts with at least 5V of superimposed data signal The exact calculation equations are beyond the scope of this manual because of the distributed load of the sounders on the loop but the f...

Страница 22: ...hieved by fitting extra I O relays to the detector circuits Fault Output FAULT This is a SELV volt free relay that operates in the Fault condition It is Normally Energised which ensures it can give a...

Страница 23: ...TERMINATION 10 1 Terminating the wiring Figure 6 Cable connections All cables entering the enclosure should have cable glands which will prevent unwanted openings in the enclosure The Zone circuits s...

Страница 24: ...rs have full control Up to 2 repeaters can be powered from the Aux24V DC output on the panel If 3 or more are to be connected then they must be powered from external 24V power supplies The panel suppo...

Страница 25: ...ottom left hand corner shows that pressing NEXT button will take you to Engineer Menu 2 4 Press button 1 will bring up the Zone menu Press 1 to view zone contents or press 2 to reconfigure the zones 5...

Страница 26: ...ystem Menu is now displayed Select option 1 to set time date Enter the Day Month Year Hour Minutes as prompted and press enter to save or Cancel at any time to exit 12 6 Changing the alarm Tones sound...

Страница 27: ...ANUAL CALL POINT ALARM I O signals a MCP alarm when operated Used when device being monitored is Manually triggered and the system is set to distinguish manual automatic alarms P PREALARM I O signals...

Страница 28: ...rough the available languages The panel will have one of 2 language banks English Spanish Portuguese French Italian OR English Hungarian Serbian Lithuanian Other languages are available on request 12...

Страница 29: ...D2 panel s screen will show Confirming alarm 3 If the device in alarm has zonal verification set the panel will turn on the sounders of all other detectors set to zonal verification in that zone 4 If...

Страница 30: ...em Menu Select option 6 Reset This brings up the screen to select to reset The panel can be reset as follows Option Item Function 1 Logs Clears event log Note that the Event counter is not reset Code...

Страница 31: ...e label Press ENTER Turn on alarm LED Flasher Press 4 Ring sounder Press GENERAL TEST Select alarm verification Press 8 Configure Sandwich Sounder Base Press 7 Disable this device Press General Disabl...

Страница 32: ...switch setting No message This device is signalling an internal fault by returning a value of less than 8 Device Label This is the 20 character description of the device location entered by the instal...

Страница 33: ...event The types of events recorded are Power On Startup Panel Reset Evacuate Access Level 2 Access Level 1 Sounders Silenced Configure Loops Time Date Set Zone Disabled Zone Enabled Device Disabled D...

Страница 34: ...rough alarm events only The LEDs will show general fault information To show fault event details on the LCD screen press the CANCEL button Prev next will now scroll through the faults Press cancel to...

Страница 35: ...L DISABLEMENT button and the screen will first prompt for a code 248 The screen will then show ZONE DISABLEMENT ZONE 1 The panel is now in SELECT DISABLEMENT MODE 3 Press NEXT key until the required z...

Страница 36: ...wing 17 4 1 VIEWING DISABLED ZONES To view which zones are disabled press 1 and then scroll through all the zones by pressing the Next button If a zone is not disabled the screen will show If a zone i...

Страница 37: ...s zone The General Test and Zone Test LEDs will now be lit 7 Detectors in this zone can now be tested with smoke spray The Detector will light it s LED until the smoke clears then it will reset The So...

Страница 38: ...in doubt contact your supplier If the wiring polarity is correct check that there is no cable break on the loop If there is a break the panel will report the break after 60 seconds or so and the break...

Страница 39: ...ns one at a time to determine the problem line Note connecting other equipment eg an oscilloscope or a PC to the panel can give an earth fault The Screen will indicate if it is a Positive or Negative...

Страница 40: ...abnormal microprocessor running condition due to various unexpected phenomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED...

Страница 41: ...amps of all detection zones 20 2 Device Values for Battery calculation Device Quiescent Alarm Comment ID2 Panel 50mA 102mA This is the current used during mains failure ID2 Repeater 50mA 75mA Fyreye...

Страница 42: ...050A Quiescent current for panel IQD 4 x 10x0 9 0 6 0 65 1 0 1000 4 x 11 25 1000 0 045 A IAP 0 102A IAD 4 x 10x7 2 2 5 7 3 2 0 1000 4 x 83 8 1000 0 3352 A Therefore using the equation Battery Size St...

Страница 43: ...2 Connection of conventional sounders 11 Fault Relay Volt free relay normally energised Operates on any fault 12 Fire Relay Volt free relay Operates on a fire condition 13 RS485 Connection for Repeate...

Страница 44: ...I E OUTPUT 205 mA IMAX B AT C I E OUTPUT 900 mA IMIN AT C I E OUTPUT 0 4 mA OUTPUT VOLTAGE RIPPLE 700mV MAX CURRENT DRAW BY PSE 2mA MAX BATTERY INTERNAL RESISTANCE RIMAX 1 5 CHARGER VOLTAGE 27 6V 22...

Страница 45: ...ated Changed BS5839 1 references to 2013 version 4 occurrences Added loop wiring terminal information Added info to Electrical Spec Max sounders Max loop zone current Aux 28V voltage current Changed n...

Отзывы: