INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT-201-7-2 

 

PAGE 3

 

Issue: 1.2      Authorised:         Date: 27/3/2012 

 
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, 
INCLUDING THE FACP & ITS INTEGRAL PSE 

 

According  to  the  British  Standard  Code  for  Fire  Detection  and  Alarm  Systems  for  Commercial  Buildings 
(BS5839: Pt 1: 2002), the owner or person having control of the premises should appoint a responsible person 
to oversee the effective operation of the Fire Alarm System (Clause 47.1). 

 

Below is a summary of the main functions the “Responsible Person” is expected to carry out.  This summary is 
not intended to replace Section seven (User responsibilities) of BS5839: Pt 1: 2002 (available from BSI, or your 
local  library).  It  is  meant  to  give  a  brief  outline  of  user  responsibilities  for  the  safe  upkeep  of  the  Fire  Alarm 
System.  The number in brackets shows the relevant BS5839: Pt 1: 2002 clauses. 

 

The responsible person must:- 

 

1.  Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a) 
2.  Check the system at least once every 24 hours to ensure there are no faults present (47.2.b) 
3.  Ensure there are arrangements for testing and maintaining the system (47.2.c) 
4.  Ensure the log book is up to date, and available for inspection (47.2.d) 
5.  Instruct  all  relevant  occupants  on  the  basic  operation  of  the  system,  including  start  evacuation,  silence 

alarms, silence faults and system reset (47.2.e) 

6.  Take appropriate action to limit the rate of false alarms (47.2.f) 
7.  Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g) 
8.  Liaise  with  maintenance  personnel  to  ensure  that  cleaning,  maintenance  or  building  work  does  not 

interfere with the functioning and reliability of the fire alarm system (47.2.h). 

9.  Ensure any changes to the system are recorded with updated drawings, operating instructions etc (47.2.i) 
10.  Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2) 
 
With the 

Infinity

 8 Range of Fire Alarm Panels, we recommend the following tests are carried out: - 

 

Daily Inspection

 

 

Check that the green Power LED is lit. 

 

If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated 
site maintenance engineer. 

 

Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

 

Do  not  test  the  same  device  each  week.  Test  a  different  zone  each  week  using  a  different  call  point  or 
detector so that eventually, all the devices will be tested. 

 

Reset the System by pressing (Stop sounders, Silence fault tone, Reset). 

 

Enter access code. Press the LED Test button. Check that all LEDs light, and the buzzer sounds 

 

Check that no call points or fire detectors are obstructed in any way. (e.g. New furniture or decorations) 

 

Quarterly Test (to be carried out by authorised service personnel only)

 

 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

 

Annual Test (to be carried out by authorised service personnel only)

 

 

Check every detector, call point, sounder and all auxiliary equipment for correct operation. 

 

Check Cage output Voltage (30VDC), Charger Voltage (27.6Vnormal and 29.4V fast charge) & Battery 
Voltage (25-27V) 

 

Every Five Years (to be carried out by authorised service personnel only)

 

 

Carry  out  a  complete  wiring  check  in  accordance  with  the  testing  and  inspection  requirements  of  the 
relevant National wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be 
replaced because SLA batteries have a working life of 5 years.

 

Содержание Infinite 8

Страница 1: ...INFINITY 8 USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 Issue 1 2 Authorised Date 27 3 2012 FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Страница 2: ...ACP I E TO EVACUATE THE BUILDING 6 5 5 RESETTING THE PANEL 6 6 THE FAULT CONDITION 7 6 1 DIFFERENT TYPES OF FAULT 7 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS 8 7 DISABLEMENTS 9 7 1 REASONS FOR DISABL...

Страница 3: ...arm or fault During an alarm the panel will start its sounders and indicate which zone has the fire It will also activate its auxiliary relay Fault Monitoring All circuits must be checked for line int...

Страница 4: ...orded with updated drawings operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the Infinity 8 Range of Fire Alarm Panels...

Страница 5: ...g the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid unauthorised changes to critical parts of the Fire Alarm System controls such as silencin...

Страница 6: ...er circuits GEN FLT SYSTEM FLT CONSTANTYELLOW CONSTANTYELLOW A processor fault has occurred To reset If problem persists consult your dealer GEN FIRE ONLY NOLED A manual evacuation has occurred The so...

Страница 7: ...ily pressing the button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit The Auxiliary Fire relay will remain active The Pane...

Страница 8: ...em on a Zone or detector has been removed from its base It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been...

Страница 9: ...ults are cleared the General Fault light will go out and the Panel s Internal Sounder will be silent if not already muted System Fault The System Fault LED and Gen fault lights when the Panel s micro...

Страница 10: ...ot be disabled External sounders can also be disabled as could be required in certain conditions 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Enter the access code default 1245 and press 2 Hold th...

Страница 11: ...efault 1245 Press button Press button again to deactivate sounder delay 8 3 HOW THE PANEL INDICATES SOUNDER DELAY If a Delay has been programmed into the Panel the General Disablement DEL AY LEDs will...

Страница 12: ...be left in test mode if the user needs to access another function e g disable 9 2 TO PROGRAMME ZONE IN TEST 1 Enter access code and press 2 Hold button for 3 seconds 3 Select the zone you want to go...

Страница 13: ...Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs t...

Страница 14: ...ng work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...

Страница 15: ...MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 PAGE 14 Issue 1 2 Authorised Date 27 3 2012 MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK...

Страница 16: ...d Document No GLT 201 7 2 PAGE 15 Issue 1 2 Authorised Date 27 3 2012 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDIN...

Страница 17: ...BOOK Approved Document No GLT 201 7 2 PAGE 16 Issue 1 2 Authorised Date 27 3 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KN...

Страница 18: ...ll points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complian...

Страница 19: ...h I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variatio...

Страница 20: ...uidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commiss...

Страница 21: ...ed below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of lia...

Страница 22: ...e clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with th...

Страница 23: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...

Отзывы: