INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT-201-7-2 

 

PAGE 10

 

Issue: 1.2      Authorised:         Date: 27/3/2012 

 

8. USING SOUNDER DELAYS

 

 

8.1 WHAT IS A SOUNDER DELAY 

 

In certain circumstances it may be desirable to have a delay between the panel detecting a fire, and starting its external 
sounders, to allow the responsible person to check the cause of the alarm, to stop building evacuation by an obvious false 
alarm.  If the cause of the Alarm is found to be a true fire hazard, the Delay can be overridden and the Alarm Sounders 
activated immediately.  Alternatively, in the case of a false alarm, the Panel can be reset. 
 

8.2 SOUNDER DELAY SETTING 

 
On the 

Infinity 

8 panel, the sounder delay can be programmed on zones 2 

– 8 (zone 1 cannot have a delay). That is, all 

zones will be delayed by the same amount. The delay can be set between 1 minute and 10 minutes, or the delay can be 
left  off  (sounders  activate  immediately).  Changing  the  delay  time  should  only  be  done  by  the  engineer  responsible  for 
setting up the system. But turning the delay on or off can be done by the user. 
 

Activate/Deactivate Sounder delay 

 

Enter Access code (default 

1245

 

Press 

 button 

 

Press 

 button again to deactivate sounder delay 

 

8.3 HOW THE PANEL INDICATES SOUNDER DELAY  

 
If  a  Delay  has  been  programmed  into  the  Panel,  the  General  Disablement  &  DEL(AY)  LEDs  will  be  lit.    When  a  zone 
processes an alarm signal, the panel will indicate fire in the usual way, but the sounders will not be active until the delay 
period  has  expired.    To  override  this  delay,  press  Delay  Override  Switch,  which  will  cause  the  external  sounders  to 
energise.  If there is no delay programmed, the Delay Override Switch has no function. 
 

8.4 A FIRE ALARM CONDITION ON A DELAYED PANEL 

 
When an alarm occurs on a Delayed Panel, the panel will: - 
 

 

Light its General Fire and appropriate Fire Zone light(s) 

 

 

Sound its Internal buzzer 

 

 

Start the Delay countdown sequence 

 

 

Wait until the end of the delay, and then start the sounders. 

 
 

 

8.5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE ALARM  

 

If  on  investigation  the  cause  of  the  Alarm  is  found  to  be  a  true  fire  hazard,  pressing  the

,  will  active  the  Alarm 

Sounders and Outputs with immediate effect.  
 

8.6 RESET THE SYSTEM IN THE EVENT OF A FALSE ALARM 

 

If, on investigation, the cause of the Alarm is found to be false, enter the access code and press 

 button. 

 

8.7 TO TURN OFF THE SOUNDER DELAY 

 

Enter access code 1245 

 

 

Press Sounder Delay 

 

 

Press Sounder Delay 

  again to deactivate Sounder Delay 

 

 

 

Содержание Infinite 8

Страница 1: ...INFINITY 8 USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 Issue 1 2 Authorised Date 27 3 2012 FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Страница 2: ...ACP I E TO EVACUATE THE BUILDING 6 5 5 RESETTING THE PANEL 6 6 THE FAULT CONDITION 7 6 1 DIFFERENT TYPES OF FAULT 7 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS 8 7 DISABLEMENTS 9 7 1 REASONS FOR DISABL...

Страница 3: ...arm or fault During an alarm the panel will start its sounders and indicate which zone has the fire It will also activate its auxiliary relay Fault Monitoring All circuits must be checked for line int...

Страница 4: ...orded with updated drawings operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the Infinity 8 Range of Fire Alarm Panels...

Страница 5: ...g the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid unauthorised changes to critical parts of the Fire Alarm System controls such as silencin...

Страница 6: ...er circuits GEN FLT SYSTEM FLT CONSTANTYELLOW CONSTANTYELLOW A processor fault has occurred To reset If problem persists consult your dealer GEN FIRE ONLY NOLED A manual evacuation has occurred The so...

Страница 7: ...ily pressing the button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit The Auxiliary Fire relay will remain active The Pane...

Страница 8: ...em on a Zone or detector has been removed from its base It should be noted that any alarms raised on the fault zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been...

Страница 9: ...ults are cleared the General Fault light will go out and the Panel s Internal Sounder will be silent if not already muted System Fault The System Fault LED and Gen fault lights when the Panel s micro...

Страница 10: ...ot be disabled External sounders can also be disabled as could be required in certain conditions 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Enter the access code default 1245 and press 2 Hold th...

Страница 11: ...efault 1245 Press button Press button again to deactivate sounder delay 8 3 HOW THE PANEL INDICATES SOUNDER DELAY If a Delay has been programmed into the Panel the General Disablement DEL AY LEDs will...

Страница 12: ...be left in test mode if the user needs to access another function e g disable 9 2 TO PROGRAMME ZONE IN TEST 1 Enter access code and press 2 Hold button for 3 seconds 3 Select the zone you want to go...

Страница 13: ...Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs t...

Страница 14: ...ng work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...

Страница 15: ...MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT 201 7 2 PAGE 14 Issue 1 2 Authorised Date 27 3 2012 MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK...

Страница 16: ...d Document No GLT 201 7 2 PAGE 15 Issue 1 2 Authorised Date 27 3 2012 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDIN...

Страница 17: ...BOOK Approved Document No GLT 201 7 2 PAGE 16 Issue 1 2 Authorised Date 27 3 2012 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KN...

Страница 18: ...ll points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complian...

Страница 19: ...h I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variatio...

Страница 20: ...uidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commiss...

Страница 21: ...ed below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of lia...

Страница 22: ...e clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with th...

Страница 23: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...

Отзывы: