Fault

code

Fault descriptions

Possible reasons

Troubleshooting

Improper V/F curve or torque boost

settings

Adjust the V/F curve and torque

boost amount

The grid voltage is too low

Check grid voltage

The motor is blocked or the load

suddenly changes too much

Check the load

Motor overload protection factor

setting is incorrect

Correctly set the motor overload

protection factor

Improper V/F curve or torque boost

settings

Adjust the V/F curve and torque

boost amount

The grid voltage is too low

Check grid voltage

The motor is blocked or the load

suddenly changes too much

Check the load

Motor overload protection factor

setting is incorrect

Correctly set the motor overload

protection factor

BIAS(17)

Current bias error

Hardware malfunction

Contact suppliers for service

VFD power is too small

Select a higher power drive

Sudden change or abnormal of

load

Check the load or reduce the

change of the load

Loose PID feedback line

Check feedback connection

The feedback amount is less than

the disconnection detection value

Adjust the detection input

threshold

Check feedback connection

Adjust the detection input

threshold

EEEP(21)

EPROM read and write

errors

EEPROM malfunction

Contact suppliers for service

CE(22

Dual CPU

communication

malfunction

CPU communication malfunction

Contact suppliers for service

EF(23)

External device

malfunction

External device fault input terminal

is closed

Disconnect the external device

fault input terminal and clear the

fault (pay attention to check the

cause)

EPA(24

)

Parameter setting error

SFOC(27)

Software overcurrent

Adjust the acceleration time,

deceleration time, motor

parameters do not match, re-

parameter identification

ELT

Water shortage

malfunction

EPA1

parameter setting error

VFD three-wire function setting is

incorrect

Check whether the three-wire

system setting of the inverter

terminals is correct

OL1(15)

VFD overload

OL2(16)

Motor overload

CBC(18)

Cycle-by-cycle current

limit malfunction

FBL(19)

PID feedback is lower

than the lower limit

FBH(20)

PID feedback exceeds

upper limit

Warning code

When the PID feedback amount is

greater than the feedback over-

value detection value, and the

duration exceeds the PID feedback

over-value detection time, the

inverter will alarm fault FBH

22

E

485

(2

5

)

Communication 

 error

Содержание ZQ280

Страница 1: ...User Manual ZQ280 ZQ280A Vector Variable Frequency Drive Solar Inverter...

Страница 2: ...ut during normal operation and whether this leads to a safe stop position without damaging machine adjacent equipment and machine operators users This responsibility lies with the user or their machin...

Страница 3: ...plication Motor S 1PH 3PH 220V to 240V Type of Variable Frequency Drive Type Power Power Supply Output Current External Dimensions ZQ280S0D4 0 4KW 2 3 ZQ280S0D7 0 75KW 4 186 5 86 143 5 ZQ280S1D5 1 5KW...

Страница 4: ...RUN STOP Speed control knob To increase parameter number or parameter set value To reduce parameter number or parameter set value To adjust frequency Stop the VFD when the drive is in the RUNNING stat...

Страница 5: ...4 there are two types of panel control start stop and terminal control start stop 1 Panel control start and stop set to panel start and stop F0 04 0 To use the panel control to start and stop the VFD...

Страница 6: ...the running frequency is set by the potentiometer when F0 05 2 the running frequency is input by AVI 0 10V can be connected to a potentiometer when F0 05 3 the running frequency is input by ACI 4 20m...

Страница 7: ...the VFD power If there is LCDI and it is afraid of breakdown please choose the LCDI whose sensitivity level is above 200mA and reaction period last more than 100ms U V W VFD output connected with ele...

Страница 8: ...be the second one of multistage speed ZQ280A factory set defaults is RS485 X5 485 ZQ280 Digital input X5 ZQ280A RS485 ZQ280 Set according to parameter F5 06 and factory set defaults to be external RS...

Страница 9: ...0 10V 3 ACI analog setting 0 20mA 4 Keybord potentiometer setting 5 Multi speed setting 6 Simple PLC 7 PID control 0 7 0 F0 05 Channel A and Channel B calculate result selection 0 1 2 MAX 3 MIN 0 3 0...

Страница 10: ...parameters 2 Clear malfunction records 3 Restore factory default restoring motor parameters 0 3 0 F1 00 V F curve set 0 Beeline 1 VF square curve 2 1 5 respectively VF power curve 3 1 2 respectively V...

Страница 11: ...pression ffunction 0 6 5 F2 00 ASR Low speed Kp 1 100 20 F2 01 ASR Low speed Ki 1 10 00 0 50 F2 02 ASR High speed Kp 1 100 10 F2 03 ASR High speed Ki 1 10 00 1 0 F2 04 ASR Low speed switch frequency L...

Страница 12: ...rt frequency run time 0 0 60 0s 0 F3 03 Start DC brking current Current value for applying DC braking When the rated current of the motor is less than or equal to 80 of the rated current of the VFD it...

Страница 13: ...s Set the jog acceleration and deceleration time 0 1 999 9s Model setting 0 1 999 9s By setting the jump frequency and range the inverter can avoid the mechanical resonance point of the load 0 Control...

Страница 14: ...UF DOWN terminal modification rate Set the frequency modification rate when the UP DOWN terminal sets the frequency That is the UP DOWN terminal is short circuited with COM for one second the magnitud...

Страница 15: ...ulti speed frequency 4 Set multi speed 1 frequency 20 0Hz F7 04 Multi speed frequency 5 Set multi speed 1 frequency 25 0Hz F7 05 Multi speed frequency 6 Set multi speed 1 frequency 37 5 0Hz F7 06 Mult...

Страница 16: ...deviation limit keeping time 0 0 6000 0s 0 0 F8 07 PID deviatiom upper limit 0 0 100 0 100 0 F8 08 PID deviatiom lower limit 0 0 100 0 0 0 F8 09 Proportion gain 0 00 600 00 25 00 F8 10 Integral time 0...

Страница 17: ...ater detect time 0 0 250 0s 0 0 F9 00 Motor rated power Model setting F9 01 Motor rated voltage 1 500V Model setting F9 02 Motor rated current 0 01 99 99A Model setting F9 03 Motor rated speed 0 60000...

Страница 18: ...hold value of the automatic current limit action and its set value is a percentage relative to the rated current of the VFD 30 200 150 FA 06 Frequency drop rate at current limit 0 99 99Hz s 0 FA 07 Cu...

Страница 19: ...20 VF Double speed overcurrent stall action current compensation coefficient 50 200 50 FA 21 VF overvoltage suppression Kp 0 100 60 FA 22 VF Overvoltage Stall Rise Maximum Frequency 0 50 5 FA 23 VF O...

Страница 20: ...1 FB 13 Timing time setting 0 9999s 0 FB 14 Reserve FB 15 Reserve FB 16 Reserve FB 17 Reserve FB 18 Reserve FB 19 Reserve FB 20 Reserve FB 21 Reserve FB 22 Software version Model setting FC 00 Commun...

Страница 21: ...d 07 Analog input ACI mA 0 00 20 00mA 0 01 d 08 Analog output AO1 V 0 00 10 00V 0 01V d 09 Input and output terminal status 0 3FH 1H d 10 Radiator temperature1 0 0 999 9 0 1 d 11 PID setting value 0...

Страница 22: ...supply Sudden change or abnormal of load Check the load or reduce the change of the load VFD power is too small Select a higher power drive VFD output shorted or grounded Check motor wiring VFD instan...

Страница 23: ...the detection input threshold Check feedback connection Adjust the detection input threshold EEEP 21 EPROM read and write errors EEPROM malfunction Contact suppliers for service CE 22 Dual CPU commun...

Страница 24: ...status Control parameter write only Control commands communication settings Data status Status data is divided into d group monitoring parameters inverter fault description inverter running status d...

Страница 25: ...col The serial communication protocol defines the content and format of information transmitted in serial communication These include host polling or broadcast format host encoding method including pa...

Страница 26: ...c parameters etc see the address definition for details When transmitting the high byte comes first and the low byte follows Parameter address L Number of parameters H The number of parameters to be r...

Страница 27: ...status read only Status word address Status word function 3000H 0001 Forward running 0002 Reverse operation 0003 Downtime Inverter fault description Frequency inverter fault address Inverter fault in...

Страница 28: ...he host computer and the inverter FC 03 Communication timeout Factory default 1 0 0 s Predetermined area 0 0 s 600 0 s When this parameter is set to a valid value if the interval between one communica...

Страница 29: ...Zest Electric Co Ltd Address No 121 Suixi Road Suixi China E mail info zest electric com WEB www zest electric com...

Отзывы: