Function
code
Name
Description
Setting
range
Factory
default
FA.14
Cycle-by-cycle current limit
selection
Ones place: select in acceleration
0: invalid, 1: valid
Tens place: Select during deceleration
0: invalid, 1: valid
Hundreds place: select from constant speed
0: invalid, 1: valid
Thousands: reserved
000-111
011
FA.15
Cycle-by-cycle current limit level
VFD
rated current.
80-200%
180
FA.16
Malfunction auto-reset times
When the reset times are set to 0, there is no
automatic reset function, only manual reset.
10 means that the number of times is unlimited,
that is, infinite times.
0-10
0
FA.17
Malfunction auto-reset interval
0.5-25.0s
3.0S
FA.18
VF overcurrent, overvoltage
suppression selection
0
:
Not enabled
1
:
Overcurrent suppression enable
2
:
Overvoltage Suppression enable
3
:
Overcurrent and overvoltage suppression
enable
0-3
3
FA.19
VF overcurrent suppression Kp
0-100
20
FA.20
VF Double-speed overcurrent
stall action current compensation
coefficient
50-200
50
FA.21
VF overvoltage suppression Kp
0-100
60
FA.22
VF Overvoltage Stall Rise
Maximum Frequency
0-50
5
FA.23
VF Overvoltage Stall Regulator
Kp
0-100
80
FA.24
Power-off and under-voltage
shutdown mode
0
:
Report undervoltage fault, free stop
1
:
No undervoltage fault is reported, stop
according to the set stop mode (F3.05)
0-1
0
FB.00
Running monitoring parameters
0
FB.01
Stop monitoring parameters
1
FB.02
Motor speed display coefficient
It is used to correct the display error of the speed
scale and has no effect on the actual speed.
0.01-99.99
1.00
FB.03
Current Malfunction
0-9999
0
FB.04
Last malfunction
0-9999
0
FB.05
First two malfunction
0-9999
0
FB.06
Malfunction Bus Voltage
0-9999
0
FB.07
Malfunction out Current
0.0-999.9
0
FB.08
Malfunction given frequency
0.0-300.0
0
FB.09
Malfunction running frequency
0.0-300.0
0
FB group: Display And Special Parameters
The default display item of the main monitoring
interface. The corresponding numbers are d
group parameters.
0-15
1
8