ZCOM230 |CONTROL PANEL | COMANDO 230V

STEP 3

Connect the power to the control board check if the limit-swi

-

tches are activated correctly. When wiring the limit-switches 

at 01 and 02 terminals, the L1 and L2 LEDs will remain lit. 

When moving the spring manually towards closing position, 

the L1 LED must turn off and when moving it towards opening 

position, the L2 LED must go off too. If the LEDs are turning off 

switched (L1 for opening and L2 for closing), swap the wires 

from 01 and 02 terminals.

STEP 4

Make a START with a help of a wire by connecting the 3 and 7 

terminals with the wire tips and check if the motor is running 

in the correct direction. When the gate starts moving to one 

side, move the limit-switches spring towards the gate’s mo-

vement direction and it should stop. If it doesn’t, pull it the 

other way and it will stop. Swap the motor wires (13 and 15 

terminals from CN1 connector) to put in the right direction.

STEP 5

When the gate is synchronized with the limit-switch correct 

direction, make a START again between 3 and 7 terminals. The 

gate will begin to move to one side. Let it reaches the closed 

position electrically.

STEP 6

When the gate comes to a closed position, press the P1 but

-

ton located on the control board for 2 seconds until the CODE 

LED (see connection diagram page) stays lit. Right away, press 

the transmitter button you want to be the total opening key 

(choose between 1, 3 and 4 buttons shown in the images at 

the right).NOTE: When the transmitter button is pressed, the 

CODE LED must blink, indicating it is receiving the code.

STEP 7

Release the first button and then press the button number 2 

to memorize the pedestrian opening button. Release it and 

wait for the CODE LED turns off. NOTE: If you select a button 

other than the nº 2 for pedestrian opening, the control board 

will recognize it as complete opening button, which means it 

will override the first pressed button. If the pedestrian ope

-

ning is not wished, do not press the nº2 button and wait for 

the CODE LED to turn off.

STEP 8

The transmitter is now configured.NOTE: After setting up a 

transmitter type, the control board will only accept transmit

-

ters from the same type, it means, if the first transmitter is 

Rolling Code, they must all be Rolling Code for the central to 

accept them. To program other transmitters, repeat the steps 

from nº06.

ERASE ALL THE TRANSMITTERS FROM THE CONTROL BOARD

With  the  gate  closed,  hold  the  P1  button  continuously.  The 

CODE LED lights up and wait for 15 seconds until it turns off. 

Release the P1 and the LED will flash twice that signals the ME

-

MORY RESET success.

DIP 7 - OFF

Enables the reading of the closing limit-switch.

NOTE:  The DIP SWITCHS 6 and 7 put a link across the safety 

device and common, instead of using a link wire.

DIP 8  - ON

Disables the safety device reading (such as photocells or sa

-

fety edges).

DIP 8 - OFF

Enables the safety device’s reading (such as photocells or sa

-

fety edges)

NOTE:  The DIP SWITCH 8 puts a link across the safety device 

and common, instead of using a link wire.

DIP 9  - ON

Programming the work and pause time. 

DIP 9 - OFF

Normal functioning.

NOTE: The DIP 9 should only be used to trigger the work and 

pause time configuration function. When the programming is 

complete, put it in OFF mode.

DIP 10  - ON

Enables anti-crushing function.

DIP 10 - OFF

Disables anti-crushing function.

4. CONFIGURATION

INSTALATION PROCESS

TOTAL OPENING AND TRANSMITTER PROGRAMMING

STEP1 

Place all the dippers in OFF position (down). In case of not 

using safety device at 4/M2 terminal (ex: photocells), place 

the DIP 8 in ON to disable it.

STEP 2

Unlock the engine, place the gate in the middle position and 

re-lock the engine.

Содержание COMANDO 230V

Страница 1: ...G1 ZCOM230 CONTROL PANEL COMANDO 230V zero HOME AUTOMATION USER MANUAL AND CONFIGURATION ZCOM230 VER1 0 01052018_REV1 IT EN FR zero HOME AUTOMATION COMANDO CONTROL UNIT SLIDING GATES 230V made in ital...

Страница 2: ...zero HOME AUTOMATION PG2 ZCOM230 CONTROL PANEL COMANDO 230V zero HOME AUTOMATION...

Страница 3: ...nd provide this manual to user Keep remote controls away from children to prevent the au tomated system from being activated involuntarily The customer shall not under any circumstances attempt to rep...

Страница 4: ...ly supports 40W If the consumption is higher intersperse a power relay Capacitator 13 and 15 You should connect the capacitator between the outputs 13 and 15 3 DIP SWITCH FUNCTION DIP 1 ON The SOFT ST...

Страница 5: ...rns off NOTE If you select a button other than the n 2 for pedestrian opening the control board will recognize it as complete opening button which means it will override the first pressed button If th...

Страница 6: ...REGULATION ANTI CRUSHING The control board has 2 trimmers rotary knobs RV1 Allows the engine sensitivity regulation increases sensiti vity by rotating it in the clockwise direction RV2 Allows the eng...

Страница 7: ...G LIMIT SWITCH of motor is reached L03 RED Comes on when the START command is activated and goes off when released L04 RED Always on Goes off when the photocell is intercepted interrupting the PHOTO b...

Страница 8: ...other configuration see the DIP SWICH paragraph OFF DIP 5 ON OFF DIP 6 ON OPENING LIMIT SWITCH READING DISABLED OFF OPENING LIMIT SWITCH READING ENABLED DIP 7 ON CLOSING LIMIT SWITCH READING DISABLED...

Страница 9: ...zero HOME AUTOMATION PG9 ZCOM230 CONTROL PANEL COMANDO 230V FLASHING LIGHT COURTESY LIGHT CONNECTIONS PHOTOCELLS CONNECTION...

Страница 10: ...rol unit is equipped with a CN2 connector to accommodate a magnetic limit switch module directly welded on control panel on demand and just for Z01 model will be also provided two magnetic stoppers fo...

Страница 11: ...zero HOME AUTOMATION PG11 ZCOM230 CONTROL PANEL COMANDO 230V zero HOME AUTOMATION...

Страница 12: ...se Unlock motor and move the gate by hand to closed posi tion Lock motor again and turn off power supply for 5 seconds Reconnect it and send start si gnal using transmitter Gate opened but didn t clos...

Страница 13: ...control board in question If the automa ted system starts working normally check for the problematic device 2 Remove one shunt at a time until you find the malfunction device 3 Replace it for a funct...

Страница 14: ...elow have been applied 2014 35 UE Low voltage Directive 2014 30 UE Electromagnetic compatibility Directive 2014 53 EU RED radio equipment directive EN 301 489 3 V2 1 1 EN 300 220 2 V3 1 1 according to...

Страница 15: ...zero HOME AUTOMATION PG15 ZCOM230 CONTROL PANEL COMANDO 230V zero HOME AUTOMATION...

Страница 16: ...zero HOME AUTOMATION PG16 ZCOM230 CONTROL PANEL COMANDO 230V zero HOME AUTOMATION ZERO SRLS Via Olona 110 Gallarate VA ITALIA info miozero it www miozero it...

Отзывы: