background image

EDA-Z5008, Z5020 & Z5100 – Technical Manual  

 

 ZPControlTechMan_r105 

_____________________________________________________________________________________________________ 

 

32 

 

6.34 - Reprogram Device – commissioning users 

1.Main Menu>>1.Setup>>5.Device Setup>>5.Reprogram Device 

Some  settings  such  as  operating  mode,  sensitivity,  volume,  device  alarm  verification  period  and 
sounder area are stored on the device rather than the control panel. In order to change these settings 
the device will need to be put into programming mode. First remove the device from its base or back 
plate.  

1.

 

If  a  smoke  or  heat  detector  is  being  reprogrammed;  hold  both  the  reset  button  and  the  unit 
removal button down while you place the jumper link to the ON position.  

2.

 

If a sounder, beacon, callpoint, transmitter or I/O unit is being  reprogrammed; hold down the 
unit removal button while holding a magnet over the reed switch and place the jumper link to 
the  ON  position.  Some  newer  callpoints  are  equipped  with  a  ‘log  on’  button.  Hold  this  while 
placing the jumper link to the ON position. 

 
Continue to hold the button(s) until a confirmation of 3 beeps from the device is heard, then release 
the buttons and remove any magnet. The LED on the device will now flash green. Press 

Enter

 to scan 

for the device. Once the device has been found, the device type will be displayed on the screen. The 
LED on the device will stay lit until the device has been successfully reprogrammed. The device number 
for the new unit should be selected using the cursor keys. When correct press 

Enter

. You will now be 

prompted  to  choose  from  using  either  the  device  default  settings  set  by  the  control  panel  or  to 
manually  set  up the  cause  and  effects.  All  options  are  entered  using the  cursor  keys.  Once  you  have 
chosen the options, press 

Enter

 to program. 

 
6.35 - System Test 
 

Test Devices – commissioning users 

1.Main Menu>>1.Setup>>6.System Test>>1.Test Devices 

This  can  be  used  to  activate  certain  functions  on  a  specific  device.  These  can  be  used  to  assist  in 
locating a device, or as a test of functionality. The available options are: 
 

Activate 

A sounder will sound for 3 short tones, a beacon will flash 3 times. 

 

Silence  

The device will silence (if it is currently sounding). 

 

Reset   

The device will reset. 

 

LED On  

The led on the device will illuminate solid green. 

 

Buzzer On 

The buzzer on the device will sound. 

 

 

Panel – Panel Test – commissioning users 

1.Main Menu>>1.Setup>>6.System Test>>2.Panel – Panel Test 

The  panel  to  panel  test  allows  the  user  to  select  two  panels  on  the  system  and  view  the  signal 
strengths between them. 
 

Pager Test Message – commissioning users 

1.Main Menu>>1.Setup>>6.System Test>>3.Pager Test Message 

This tool allows the user to send a test alert message to any pagers set up on the system. 

 

 

 

Содержание EDA-Z5008

Страница 1: ...ZERIO PLUS EDA Z5008 Z5020 Z5100 INSTALLATION OPERATION MANUAL ZPControlTechMan_r105 Revision 1 05...

Страница 2: ...s EN54 2 1997 A1 2006 EN54 4 1997 A1 2002 A2 2006 EN54 25 2008 Control and indicating equipment for fire detection and fire alarm systems for buildings Models EDA Z5008 EDA Z5020 EDA Z5100 Optional fu...

Страница 3: ...is achieved by radio Text locations can be entered on the panel itself or by connecting a standard USB keyboard to the panel Devices for the system are visually the same as the standard Millennium an...

Страница 4: ...evel descriptions V0 13 07 10 2013 Updated PCB layout V0 14 14 10 2013 Filename change DOP updated V0 15 17 10 2013 EN54 approved functions added Formatting changes V1 00 21 10 2013 First release V1 0...

Страница 5: ...ion of fault with 40 characters of location text Event Log Memory 1000 events maximum Mains Supply 230V 50Hz 0 3A max Mains Fuse 1 x 250V 3 15A Battery 1 x 12V 7 0Ah sealed lead acid giving 72 hour st...

Страница 6: ...Keyswitch Options 6 18 Panel Text 6 19 SIM Operations 6 20 Device Assignment 6 21 Panel Assignment 6 22 Add Antenna 6 23 Add Repeater Booster Panel 6 24 Add Pager 6 25 Remove Hardware 6 26 Panel Netwo...

Страница 7: ...and settings some of which can be set in a way that would result in a system that does not comply with EN54 The EN54 approved settings are listed below Setup Type Standard Test Mode Type By Zone Test...

Страница 8: ...ely isolated before working on any mains rated components Cables should only enter the panel housing through the knockouts provided Do not remove more knockouts than is needed to terminate the cables...

Страница 9: ...laced The battery voltage can be viewed on the PSU Info section of the 6 5 Panel Info menu When replacing the battery always do so with a product of equal specification Always dispose of batteries res...

Страница 10: ...A suitable data cable should be used with 2 sets of twisted pairs Cat 5 5e 6 can be used but is not fire rated Wired antennas and displays have two RS485 connectors making it possible to make a chain...

Страница 11: ...free clean contact relays The relay type can be changed in 6 8 User Options and by positioning the jumper links and fuses as detailed below When relays are configured as fire routing or as sounder cir...

Страница 12: ...fire condition exists across multiple zones multiple zone LEDs will be illuminated The EDA Z5008 8 Zone panel is shown The EDA Z5020 panel is equipped with 20 zone LEDs and the EDA Z5100 is equipped...

Страница 13: ...ed by default though it can be programmed to do a number of functions See 6 8 User Options Cancel Used to return to the main screen from a menu or to return to the menu from a programming screen Enter...

Страница 14: ...he fault has been acknowledged and does not re sound the buzzer unless a new fault occurs The LED on the device will continue to flash until the fault is reset see below 4 4 Reset a Fault A fault will...

Страница 15: ...system can be silenced and reset without a code by turning off Code Protect see 6 9 System Options If a device has remained in alarm i e the glass has not been replaced in a callpoint or a smoke detec...

Страница 16: ...ain Menu 4 View Events 2 View Event Log If a non menu screen is selected the Cancel button should be pressed to return to the menu without making any changes Subsequently then pressing Cancel for a se...

Страница 17: ...Menu 1 Setup 2 Access Codes 2 Change Codes Using the cursor keys select the access level for which the access code is to be changed Users can only change the access code for their level and below Once...

Страница 18: ...de the characters and press Confirm the text is correct and press Enter to save To return to the menu press Cancel Change Display Options service and commissioning users 1 Main Menu 1 Setup 3 Panel Di...

Страница 19: ...indicator from 20 to 20 RF Chan The channel the system is using Pan The number of the panel programmed at the antenna Slot Device protocol slot Squelch RF interference filter Non user adjustable View...

Страница 20: ...emoval button down while you place the jumper link to the ON position 2 If a sounder beacon callpoint transmitter or I O unit is being programmed hold down the unit removal button while holding a magn...

Страница 21: ...either a common zone or a dwelling zone The zone designation will affect how the system reacts to an alarm within the zone The zone designation can be changed later in the HMO Zones menu Once complet...

Страница 22: ...ctivates The FIRE SOUNDERS ON setting has been type approved Double Knock Zone Whether a second device in the same zone or any second device operates the double knock Relay 1 Type Choose relay type 0...

Страница 23: ...h goes into alarm will cause the sounders to start sounding again 6 10 Fault Options commissioning users 1 Main Menu 1 Setup 4 System Setup 3 Edit Panel 1 Panel Options 3 Fault Options This menu allow...

Страница 24: ...iggered Evac Relay This relay can be set to on off or pulse when the Evac tone is being sounded React Time If an alert is not silenced within this time period the system will trigger an evacuation Ven...

Страница 25: ...e panel after delay1 Types 0 and 3 are type approved Delay2 Second delay before the sounders operate Tone2 Tone that the sounders sound after delay2 The SWEPT tone has been type approved Area2 The are...

Страница 26: ...device to the panel or antenna it receives the strongest signal from This can be done for one device or for all devices at once Be sure to clear the verify table first and wait 15 minutes before runn...

Страница 27: ...t the next available panel number the main panel is always panel 01 When prompted the memory card from the repeater panel will need to be placed into the memory card slot of the main panel Do not mix...

Страница 28: ...ar Network The clear network option will remove any current network set up from a system It will clear the local panel currently being used the repeater panels on the network and clear the verify tabl...

Страница 29: ...1 Main Menu 1 Setup 5 Device Setup 1 Device Info 3 Device Version Select a device and press Enter to poll that device This will display the version number of the firmware on the selected device Devic...

Страница 30: ...pe will be displayed on the screen The LED on the device will stay lit until the device has been successfully added to the system The device number and zone for the new unit should be selected using t...

Страница 31: ...ons have been edited press until press Enter to save is displayed Zone The zone the device is located in Delay1 The first delay before the sounders operate Tone1 The tone that the sounders should oper...

Страница 32: ...Once the device has been found the device type will be displayed on the screen The LED on the device will stay lit until the device has been successfully reprogrammed The device number for the new un...

Страница 33: ...r can disable a zone indefinitely by selecting a time of 00 hours Press Enter to save the change Device XXX disabled will be displayed on screen and the LED marked Disablements will now be illuminated...

Страница 34: ...led will automatically be enabled again When Fire Routing is disabled open circuit and short circuit faults will not be reported Disable Fault Relay all access levels 1 Main Menu 2 Disable Enable 1 Di...

Страница 35: ...ces zones remain then the Disablements LED will extinguish Enable Panel Input all access levels 1 Main Menu 2 Disable Enable 2 Enable 3 Panel Input Select this option to enable an input that has previ...

Страница 36: ...NO SOUND Alternatively the sounders can be set to 6 SEC SOUND where any activated sounders will automatically silence after 6 seconds This allows the engineer to perform a one man walk test without t...

Страница 37: ...s to be disabled in an alarm test Beacons Choose from Off or On Callpoint Override When set to Yes callpoints will cause an alarm and sounders will sound if operated in test mode If set to No callpoin...

Страница 38: ...in Menu 4 View Events 3 Clear Event Log The event log can be cleared by selecting 3 Clear Event Log and then pressing Enter to confirm 9 4 Dump the Event Log to a USB Flash Drive commissioning users 1...

Страница 39: ...g 10 1 View a Summary of Verify Information for a Single Device service and commissioning users 1 Main Menu 5 Verify Table 1 View Table 1 View Summary From the Verify Table menu select 1 View Table Se...

Страница 40: ...ved transmission Screen 2 By using the cursor key the screen opposite will appear This screen details the number of times the device has failed to transmit within the time period shown This informatio...

Страница 41: ...e 4 Panel Table The panel table gives the user the same information as the verify table but for any panels on the system rather than devices As with the verify table users can view a summary of the in...

Страница 42: ...ew All Displays every signal received on current RF channel View This System Only messages from devices that have been previously programmed on to this system will be listed View Single Device Only me...

Страница 43: ...TYPE ERROR The device reporting to the panel does not match the device information stored on the panel TX RX FAULT Transceiver fault VERIFY FAULT Panel has lost communication with a device 13 2 Panel...

Страница 44: ...Key as a Delay Toggle Switch 1 Main Menu 1 Setup 4 System Setup 3 Edit Panel 1 Panel Options 1 User Options Press the key until the function key screen is displayed Use the and keys to select delay to...

Страница 45: ...compatible with the Q690 batteries How do I disable the sounders See 8 0 Test Mode or select disable sounders in the 7 0 Disable Enable menu What is a removal fault This fault is to alert the user to...

Страница 46: ...5 of detectors and 100 of callpoints The devices tested should be varied so that each device will have been tested at some point in any given 12 month period The panel battery connections and any rela...

Страница 47: ...anel has powered up before reconnecting the battery Display Board Power down the panel by disconnecting the battery and removing the mains fuse from the terminal block Unplug the ribbon cable from the...

Страница 48: ...x EDA Q690 EDA T5000 Radio Transmitter Unit 1 x EDA Q690 EDA T5100 Radio Silence Alarm Button 1 x EDA Q690 EDA T6080 Radio Input Output Unit DC 1 x EDA Q690 EDA Y5000 Dipole Weatherproof Antenna EDA Z...

Отзывы: