Troubleshooting

TROUBLESHOOTING PROCEDURES

Issue

Cause

What to do

After installation, 

the unit doesn’t 

work.

1.  The power source is not turned ON.

1.  Make sure the circuit breaker and the unit’s 

power is ON.

2.  The power line and the cable locking connector 

is not connecting properly.

2.  Check the power connection with the unit is 

connected properly.

3.  The switch board and control board wirings are 

disconnected.

3.  Make sure the wirings between the switch 

board and control board are connected 

properly.

4.  The wires on control board are loose.

4.  Make sure the wires on the control board are 

connected properly.

5.  The switch board or control board is defective.

5.  Change the switch board or control board.

Light works, but 

the blower is not 

turning.

1.  The blower is defective, possible seized.

1.  Change the blower.

2.  The thermally protected system detects if the 

blower is too hot to operate and shuts the blower 

down.

2.  The blower will function properly after the 

thermally protected system cool down.

3.  Damaged capacitor.

3.  Change the capacitor.

4.  The blower wire is not connected.

4.  Make sure the blower wire is plugged into the 

molex connector.

The unit is 

vibrating.

1.  The blower is not secure in place.

1.  Tighten the blower in place.

2.  Damaged blower wheel.

2.  Change the blower.

3.  The hood is not secured in place.

3.  Check the installation of the hood.

The blower is 

working, but the 

lights are not.

1.  Defective halogen bulb.

1.  Change the halogen bulb.

2.  The light bulb is loose.

2.  Tighten the light bulb.

3.  The light bulb plug is disconnected.

3.  Check the light bulb plug connection.

The hood is 

not venting out 

properly.

1.  The hood might be hanging to high from the 

cook top.

1.  Adjust the distance between the cook top and 

the bottom of the hood within 24” and 34” 

range.

2.  The wind from the opened windows or opened 

doors in the surrounding area are affecting the 

ventilation of the hood.

2.  Close all the windows and doors to eliminate 

the outside wind flow.

3.  Blockage in the duct opening or duct work.

3.  Remove all the blocking from the duct work or 

duct opening.

4.  The direction of duct opening is against the wind. 4.  Adjust the duct opening direction.
5.  Using the wrong size of ducting.

5.  Change the ducting to correct size.

Metal filter is 

vibrating.

1.  Metal filter is loose.

1.  Change the metal filter.

2.  Spring clip is broken.

2.  Change the spring clip.

The blower turns 

on by itself.

1.   The clean air function has been enabled turning 

the blower on every 4 hours.

1.   Disable the clean air function by following the 

steps on page 13.

Содержание Titan Island AK7742AS

Страница 1: ...Use Care and Installation Guide Model number Serial Number www zephyronline com SEP19 0101 Zephyr Ventilation LLC Airflow Control Technology TM C Titan Island AK7736AS AK7742AS AK7748AS...

Страница 2: ...pecifications 8 Mounting the Hood 9 11 PBD 1300A Dual Blower Ducting 12 FEATURES CONTROLS Electronic LCD Controls 13 Optional Remote Control 14 MAINTENANCE Cleaning Filter Removal Lights 15 TROUBLESHO...

Страница 3: ...IRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close fitting lid cookie sheet or metal tray then turn off the burner BE CAREFUL TO PREVENT BURNS If the flames do not go out immediately EVACUATE AND...

Страница 4: ...t protected by a 15 or 20 ampere circuit breaker or time delay fuse Wiring must be 2 wire with ground Please also refer to Electrical Diagram on product A cable locking connector not supplied might al...

Страница 5: ...t bulbs AK7736AS AK7742AS 4 LED light bulbs AK7748AS 1 8 in round starting collar for single blower ducting 1 Paper ceiling template 1 Hardware package PARTS NOT SUPPLIED Ducting conduit and all insta...

Страница 6: ...lumn 2 Subtotal column 1 Total ductwork Maximum Duct Length For satisfactory air movement the total duct length should not exceed 100 equivalent feet 6 roundto 3 1 4 x 10 rect transition 1 Ft x Ft 6 r...

Страница 7: ...rtant to install the hood at the proper mounting height Hoods mounted too low could result in heat damage and fire hazard while hoods mounted too high will be hard to reach and will lose its performan...

Страница 8: ...garages All exhaust must be ducted to the outside Use rigid metal ductwork only Fasten all connections with sheet metal screws and tape all joints with certified Aluminum Tape or Duct Tape Some Ducti...

Страница 9: ...6 36 41 15 16 42 47 15 16 48 17 15 16 36 42 21 5 8 48 4 3 5 16 16 1 4 27 15 16 14 5 16 31 5 8 Standard Min 33 Max 50 Z1C 0077 36 42 Z1C 0177 48 Min 49 Max 78 C L C L 7 7 8 18 36 20 15 16 42 23 15 16 4...

Страница 10: ...s located behind the drywall to reinforce the mounting location FIG A1 Secure 2 M6 x 2 wood screws with washers to points A and B of the paper template FIG B Do not completely tighten screws leave app...

Страница 11: ...t on the top support frame faces the front of the hood where the controls will be located FIG D The key holes on the top support frame should cover the wood screws previously installed in the ceiling...

Страница 12: ...Duct Covers together by magnetic strips 9 Secure Top Duct Covers to Top Support Frame by using 4 3 16 x 1 4 screws 2 screws for each Top Duct Cover FIG H 10 Assemble Bottom Duct Covers together over T...

Страница 13: ...wer to female plugs behind switch panel 1 Disconnect blower plug and white and black power cables 2 Remove 4 screws from interior of hood body attaching single blower plate to top of hood body Remove...

Страница 14: ...der delay off and clean air indicator Filter Clean Reminder After 30 hours of fan usage the words Clean grease filters will show on the Display indicating it is time to clean the filters To Reset With...

Страница 15: ...ing the pairing is complete RF REMOTE FUNCTIONS FIG 1 FIG 2 Blower On Speed Selection Press to power on blower and cycle through all six blower speeds Blower On Power Off By pressing the blowers will...

Страница 16: ...w heat or soaked in hot soapy water Dry filters and re install before using hood Removing Baffle Filters 1 Push filter toward back of range hood using handles 2 Pivot front of filter downward 3 Remove...

Страница 17: ...it is vibrating 1 The blower is not secure in place 1 Tighten the blower in place 2 Damaged blower wheel 2 Change the blower 3 The hood is not secured in place 3 Check the installation of the hood The...

Страница 18: ...nd place inside the hood body below the wiring diagram or in another clearly visible location NOTE After re positioning the jumper and powering on the hood the CFM cannot be changed again To verify if...

Страница 19: ...18 www zephyronline com Wiring Diagrams ACT 590 CFM Fan Max 175W 2 6A ACT 390 CFM Fan Max 94W 1 4A ACT 290 CFM Fan Max 63W 0 9A...

Страница 20: ...onal Accessories Duct Cover Extension 36 42 Z1C 0077 Duct Cover Extension 48 Z1C 0177 Dual Internal Blower PBD 1300A Make Up Air Kit Single Blower MUA008A Make Up Air Kit Dual Blower MUA010A To order...

Страница 21: ...ith this warranty All Products must be installed by a qualified professional installer to be eligible for warranty repairs or service Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE AT OUR...

Страница 22: ...phyr product at www zephyronline com registration Zephyr Ventilation 2277 Harbor Bay Pkwy Alameda CA 94502 1 888 880 8368 Prompt registration helps in more ways than one IT S IMPORTANT Ensures warrant...

Отзывы: