7. Error and faults signaling:
The converters are equipped with self-diagnosis routine; in case of anomalous event the
power output is stopped and an error message is displayed.
Signal
Cause
Remedy
DSP X FAIL
Communication error between
the central processor and the
DSP shown by nr. X
Shut off and turn on the equipment; if the
error remains contact the assistance
FAIL
Generic error
Connect a PC to the equipment and by
means of the software “GesPWM” check the
table below
By means of the software GesPWM it’s possible to visualize the following table:
Signal
Cause
Remedy
Temperature
Very high temperature of the
heath-sink
Shut off the equipment and wait a few
minutes. If the phenomenon repeats check
the air vents and make sure the fans work
properly.
Under-voltage
Supply voltage to low <350V
Check the mains and the presence of all
three phases.
Over-voltage
Supply voltage
to high >460V
Check the mains voltage.
Current limit
Maximum allowed current
exceeded
Check the load or the parameters settings.
NTC error
Fault in the temperature
measurement circuit
Contact the assistance.
Fault
IGBT failure
Contact the assistance.
Precharge
Malfunction of the precharge
capacitors circuit
Check the precharge relay.
If the fault persists, contact the assistance.