3. Auxiliary Inputs / Outputs
3.1.1 Inputs
The FVC converters have some inputs for remote control
function
Description
Emergency
Voltage-free NC contact, its opening causes the immediate disengagement of
the line breaker disconnecting the equipment from the mains
on – off
Voltage-free NO contact, allows to start the converter from remote control
Voltage command
Analog input 0 ÷ 10V, remote command for the output voltage 0 ÷ 100%
Frequency command
Analog input 0 ÷ 10V, remote command for the output frequency 0 ÷ 100%
3.1.2 Outputs
The FVC converters have some outputs for remote signaling
function
description
Converter running
PNP digital output, it signals that the converter is running
Max 30V 0,5A
Alarm
PNP digital output, it signals a fault
Max 30V 0,5A
3.2
Communication port
The converter is equipped with a RS484 communication port which allows to connect a
PC or other system for parameters setting, for the alarm register reading and for remote
control.
The Baud Rate is the transfer speed and is set at 9600.