MINiBOX 0-10V X3/X2/X1
Technical Support:
22
170
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
171, 209, 247
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Temperature Source 1
External Sensor Temperature
172, 210, 248
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Temperature Source 2
External Sensor Temperature
173, 211, 249
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Effective Temperature
Effective Control Temperature
174, 212, 250
1 Byte
I
C - W - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode
1-Byte HVAC Mode
175, 213, 251
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Comfort
0 = Off; 1 = On
176, 214, 252
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Standby
0 = Off; 1 = On
177, 215, 253
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Economy
0 = Off; 1 = On
178, 216, 254
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Protection
0 = Off; 1 = On
179, 217, 255
1 Bit
I
C - W - -
DPT_Window_Door
0/1
[Tx] Window Status (Input)
0 = Closed; 1 = Open
180, 218, 256
1 Bit
I
C - W - -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
181, 219, 257
1 Byte
O
C R - T -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode Status
1-Byte HVAC Mode
182, 220, 258
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Basic Setpoint
Reference Setpoint
183, 221, 259
1 Bit
I
C - W - -
DPT_Step
0/1
[Tx] Setpoint Step
0 = Decrease Setpoint; 1 =
Increase Setpoint
184, 222, 260
2 Bytes
I
C - W - -
DPT_Value_Tempd
-671088.64º - 670433.28º
[Tx] Setpoint Offset
Float Offset Value
185, 223, 261
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Setpoint Status
Current Setpoint
186, 224, 262
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Basic Setpoint Status
Current Basic Setpoint
187, 225, 263
2 Bytes
O
C R - T -
DPT_Value_Tempd
-671088.64º - 670433.28º
[Tx] Setpoint Offset Status
Current Setpoint Offset
188, 226, 264
1 Bit
I
C - W - -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - W - -
DPT_Reset
0/1
[Tx] Offset Reset
Reset Offset
189, 227, 265
1 Bit
I
C - W - -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
190, 228, 266
1 Bit
O
C R - T -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
191, 229, 267
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] On/Off
0 = Off; 1 = On
192, 230, 268
1 Bit
O
C R - T -
DPT_Switch
0/1
[Tx] On/Off Status
0 = Off; 1 = On
193, 231, 269
1 Bit
I/O
C R W - -
DPT_Switch
0/1
[Tx] Main System (Cool)
0 = System 1; 1 = System 2