MINiBOX 0-10V X3/X2/X1

 

https://www.zennio.com

 

              

Technical Support:

 

https://support.zennio.com

 

 

17 

ETS PARAMETERISATION 

The 

Manual Control 

(enable by default as explained in section 2.1) is configured from 

the 

“Configuration” sub tab itself under “Manual Control”.  

 

Figure 6. 

Manual control.

 

 

Manual Control 

[

Disabled / Only Test Off Mode / Only Test On Mode / 

Test 

Off Mode + Test On Mode

]: Depending on the selection, the device will permit 

using the manual control under the Test Off, the Test On, or both modes. Note 

that, as stated before, using the Test Off mode does not require any special 

action,  while  switching  to  Test  On  mode  does  require  long-pressing  the 

Prog./Test button. 

 

Lock  Manual  Control 

[

disabled

 

/enabled

]:  unless  the  above  parameter  has 

been  “Disabled”,  the  Lock  Manual  Control  parameter  provides  an  optional 

procedure  for  locking  the  manual  control  in  runtime.  When  this  checkbox  is 

enabled,  object  “

Manual  Control  Lock

”  turns  visible,  as  well  as  two  more 

parameters: 

 

Value 

[

0 = Lock; 1 = Unlock /

 0 = Unlock; 1 = Lock

]: defines whether the 

manual control lock/unlock should take place upon the reception of values 

“0” and “1” respectively, or the opposite. 

 

Initialization 

[

Unlocked / Locked /

 Last Value

]: sets how the lock manual 

control should be after the device start-up (after an ETS download or a 

bus power failure). The option 

“Last Value” will correspond to Unlocked 

on the first start-up. 

 

 

Содержание MINiBOX 0-10V X3

Страница 1: ...MINiBOX 0 10V X3 X2 X1 Multifunction Actuator with 3 2 1 fold 0 10V analog input output ZIO3X010 ZIO2X010 ZIO1X010 USER MANUAL Application program version 1 2 User manual edition 1 2 _a www zennio com...

Страница 2: ...s 3 1 Introduction 4 1 1 MINiBOX 0 10V X3 X2 X1 4 1 2 Installation 5 1 3 Start Up and Power Loss 6 2 Configuration 7 2 1 General 7 2 2 Analog Input 9 2 3 Analog Voltage Output 10 2 3 1 Operating Time...

Страница 3: ...al Support https support zennio com 3 DOCUMENT UPDATES Version Changes Page s 1 2 _a New devices MINiBOX 0 10V X2 y MINiBOX 0 10V X1 Changes in the software library Analog inputs module is added Optim...

Страница 4: ...MINiBOX 0 10V X1 1 channel and all their characteristics will be mentioned respectively and following this order along the entire document 3 2 1 fan coil analog modules to control 2 and 4 pipes units...

Страница 5: ...e into the programming mode making the associated LED 5 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode In such case the LED wi...

Страница 6: ...ticular state and whether the device should send certain objects to the bus after the power recovery Please consult the next sections of this document for further details On the other hand when a bus...

Страница 7: ...ssible to activate deactivate all the required functionality The following image corresponds to the MINiBOX 0 10V X3 The reduced versions only show the number of channels corresponding to each device...

Страница 8: ...tification Note The first sending after download or bus failure takes place with a delay of up to 255 seconds to prevent bus overload The following sendings match the period set Device Recovery Object...

Страница 9: ...puts which can be used to connect different sensors with different voltage 0 10V 0 1V y 1 10V or current 0 20mA y 4 20mA measurement ranges Please refer to the specific user manual Analog Inputs avail...

Страница 10: ...tionality and the configuration of the related parameters 2 3 1 OPERATING TIME COUNTER When an analog output is enabled it is possible to configure the operating time counter a function that offers th...

Страница 11: ...ounter record in hours of the time that the output remains switched on off The maximum value is 65535 when the maximum limit is reached this value is maintained Counting Mode Output Off Output On sets...

Страница 12: ...s incorporate three two one modules to control the fan and valves of a 2 or 4 pipes fan coil unit Please refer to the specific user manual Fan Coil Analog available in the MINiBOX 0 10V product sectio...

Страница 13: ...ncorporate three two one Zennio thermostats that can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the MINiBOX 0 10V product sections...

Страница 14: ...The execution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result af...

Страница 15: ...the beginning On the contrary switching to the Test On mode unless disabled by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer re...

Страница 16: ...ontrol the outputs through the on board pushbuttons Orders received through communication objects will be ignored regardless of the channel or the output they are addressed to Individual output the ac...

Страница 17: ...while switching to Test On mode does require long pressing the Prog Test button Lock Manual Control disabled enabled unless the above parameter has been Disabled the Lock Manual Control parameter prov...

Страница 18: ...8 32767 AIx Measured Value 2 Byte Signed 2 Bytes O C R T 9 xxx 671088 64 670433 28 AIx Measured Value 2 Byte Float 4 Bytes O C R T 14 xxx AIx Measured Value 4 Byte Float 1 Byte O C R T DPT_Scaling 0 1...

Страница 19: ...7 62 1 Bit I C W DPT_DayNight 0 1 AOx Day Night Mode 0 Day Mode 1 Night Mode 1 Bit I C W DPT_DayNight 0 1 AOx Day Night Mode 0 Night Mode 1 Day Mode 33 48 63 1 Bit I C W DPT_Switch 0 1 AOx Day Night M...

Страница 20: ...Protection Status 0 Not Active 1 Active 1 Bit O C R T DPT_Switch 0 1 FCx Valve Anti Seize Protection Status 0 Not Active 1 Active 81 114 147 1 Bit I C W T U DPT_Switch 0 1 FCx Heating Valve Control V...

Страница 21: ...FCx Manual Fan Enumeration Control S0 0 S1 25 S2 50 S3 75 S4 100 1 Byte I C W T U DPT_Fan_Stage 0 255 FCx Manual Fan Enumeration Control S0 0 S1 100 99 132 165 1 Byte I C W T U DPT_Scaling 0 100 FCx M...

Страница 22: ...oor 0 1 Tx Window Status Input 0 Closed 1 Open 180 218 256 1 Bit I C W DPT_Trigger 0 1 Tx Comfort Prolongation 0 Nothing 1 Timed Comfort 181 219 257 1 Byte O C R T DPT_HVACMode 1 Comfort 2 Standby 3 E...

Страница 23: ...ntrol 1 Bit O C R T DPT_Switch 0 1 Tx Sx Control Variable PI Control PWM 201 207 239 245 277 283 1 Bit O C R T DPT_Switch 0 1 Tx Sx PI State Cool 0 PI Signal 0 1 PI Signal Greater than 0 202 208 240 2...

Страница 24: ...0 100 LF Function x Result 1 Byte Percentage 2 Bytes O C R T DPT_Value_2_Count 32768 32767 LF Function x Result 2 Byte Signed 2 Bytes O C R T 9 xxx 671088 64 670433 28 LF Function x Result 2 Byte Flo...

Страница 25: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...

Отзывы: