MAXinBOX SHUTTER 4CH / 8CH v2
Technical Support:
7
Manual Control
[
disabled/
enabled]
:
enables o disables the “Manual Control”
tab on the left menu. See section 2.5 for more details.
Sending of Indication Objects (0 and 1) on Bus Voltage Recovery
[
disabled
/enabled
]: this parameter lets the integrator activate two new
communication objects (“
Reset 0
” and “
Reset 1
”), which will be sent to the
KNX bus with values “0” and “1” respectively whenever the device begins
operation (for example, after a bus power failure). It is possible to
parameterise a certain
delay
[
0
…255
] to this sending.
Figure 3.
Sending of Indication objects on bus voltage recovery.
Heartbeat (Periodic Alive Notification)
[
disabled
/enabled
]: this parameter
lets the integrator incorporate a one-
bit object to the project (“
[Heartbeat]
Object to Send ‘1’
”) that will be sent periodically with value “1” to notify that
the device is still working (
still alive
).
Figure 4
. Heartbeat (Periodical Alive Notification).
Note:
The first sending after download or bus failure takes place with a delay
of up to 255 seconds, to prevent bus overload. The following sendings match
the period set.
Show Relay Switches Counter Objects
[
disabled
/enabled
]: enables two
communication objects to keep track of the number of switches performed by
each of the relays ("
[Relay X] Number of Switches
") and the maximum
number of switches carried out in a minute ("
[Relay X] Maximum Switches
per Minute
").